Tensile Test of Conductors

Electrical4u
Electrical4u
Field: Basic Electrical
0
China

What Is The Tensile Test Of Conductors

This test is performed only to confirm tensile strength of aluminum wires used for conductor in electric power cables. This test is significantly performed on conductor material to judge the strength of this material. A cable conductor is often subjected to pull from one end during laying, installing and manufacturing hence it should be strong enough to tolerate the pulling force as well. Hence it becomes necessary to ensure that the conductor material has sufficient tensile strength.

Apparatus required for Tensile Test

  • Tensile Testing Machine: An automatic machine, with two end grips properly designed to hold the conductor with sufficient strength so that the conductor cannot slid by any means during the test. The machine should have sufficient capacity to apply required tension during test.

  • Plane Faced Micrometer which can able to measure accurately even 0.01 mm variation. This is used to measure the diameter of the specimen conductor.

  • Suitable Scale with least scale division 1 mm to measure length of the specimen conductor.

  • Weighing Balance with sensitivity of 0.01g to measure mass of the specimen.

tensile test machineMethod of Tensile Test of Conductors

A specimen of conductor with length little bit longer than gauge length (gauge length is the length of the specimen on which test is carried out) is first taken. To be careful that the minimum length of the entire specimen shall be such that it should have extra length at two ends after its gauge length for holding the same by grips of tensile testing machine. No pre-conditioning of the specimen is required for Tensile test.

Procedure of Tensile Test of Conductors

Before the test is conducted the diameter of the specimen is measured by plane faced micrometer and recorded. In case of shaped solidal conductor, the mass and length of specimen are determined by weigh balance ans measuring scale respectively. Now the test specimen is fixed and fitted in-between the jaws of the machine by means of grips. The load is applied to the specimen and it is increased gradually and uniformly. The rate of separation of jaws of the machine shall not be more than 100 mm per minute. When the Tensile test specimen is fractured, that breaking load is noted down from the dial of the tensile testing machine, and then tension strength is calculated.

Tabulation of Observations of Tensile Test of Conductors

Diameter of Circular Wire in mm

Shaped Solidal Conductor

Cross Sectional Area in mm2

Breaking Load in N


Mass in g

Length in mm



Calculation

Report

Sample No

Aluminum Conductor Grade

Tensile Strength, N/mm2



Observed

Specified

Conclution: Specimen meets/does not meet the requirements of specification.

Statement: Respect the original, good articles worth sharing, if there is infringement please contact delete.

Give a tip and encourage the author!
Recommended
PT Fuse Slow Blow: Causes, Detection & Prevention
PT Fuse Slow Blow: Causes, Detection & Prevention
I. Fuse Structure and Root Cause AnalysisSlow Fuse Blowing:From the design principle of fuses, when a large fault current passes through the fuse element, due to the metal effect (certain refractory metals become fusible under specific alloy conditions), the fuse first melts at the soldered tin ball. The arc then rapidly vaporizes the entire fuse element. The resulting arc is quickly extinguished by quartz sand.However, due to harsh operating environments, the fuse element may age under the comb
Edwiin
10/24/2025
Why Fuses Blow: Overload, Short Circuit & Surge Causes
Why Fuses Blow: Overload, Short Circuit & Surge Causes
Common Causes of Fuse BlowingCommon reasons for fuse blowing include voltage fluctuations, short circuits, lightning strikes during storms, and current overloads. These conditions can easily cause the fuse element to melt.A fuse is an electrical device that interrupts the circuit by melting its fusible element due to heat generated when current exceeds a specified value. It operates on the principle that, after an overcurrent persists for a certain period, the heat produced by the current melts
Echo
10/24/2025
Fuse Maintenance & Replacement: Safety and Best Practices
Fuse Maintenance & Replacement: Safety and Best Practices
1. Fuse MaintenanceFuses in service should be regularly inspected. The inspection includes the following items: Load current should be compatible with the rated current of the fuse element. For fuses equipped with a fuse blown indicator, check whether the indicator has actuated. Check the conductors, connection points, and the fuse itself for overheating; ensure connections are tight and making good contact. Inspect the fuse exterior for cracks, contamination, or signs of arcing/discharge. Liste
James
10/24/2025
Maintenance and Repair Items for 10kV High-Voltage Switchgear
Maintenance and Repair Items for 10kV High-Voltage Switchgear
I. Routine Maintenance and Inspection(1) Visual Inspection of Switchgear Enclosure No deformation or physical damage to the enclosure. Protective paint coating shows no severe rust, peeling, or flaking. Cabinet is securely installed, clean on the surface, and free of foreign objects. Nameplates and identification labels are neatly affixed and not falling off.(2) Check of Switchgear Operating Parameters Instruments and meters indicate normal values (comparable to typical operating data, with no s
Edwiin
10/24/2025
Related Products
Send inquiry
Download
Get the IEE Business Application
Use the IEE-Business app to find equipment, obtain solutions, connect with experts, and participate in industry collaboration anytime, anywhere—fully supporting the development of your power projects and business.