Types of Electrical Power Cables (Sizes & Ratings)

Electrical4u
Electrical4u
Field: Basic Electrical
0
China

What Are The Types Of Electrical Power Cables

Electric power can be transmitted or distributed either by overhead transmission systems or by underground cables. Cables are mainly designed for a specific requirement. Power cables are mainly used for power transmission and distribution purposes. It is an assembly of one or more individually insulated electrical conductors, usually held together with an overall sheath. The assembly is used for transmission and distribution of electrical power.

Electrical power cables may be installed as permanent wiring within buildings, buried in the ground, and run overhead or exposed. Flexible power cables are used for portable devices, mobile tools, and machinery.

These are designed and manufactured as per voltage, current to be carried, operating maximum temperature and purpose of applications desired by the customer.

For mining, we give extra mechanical strength to cable with double armoring. For wind power plant customers generally, require flexible and UV protected cable with the mechanical tough sheath so we design as per their requirement. The underground cables have several advantages such as less liable to damage through storms, lightning, low maintenance cost, a lower chance of faults, a smaller voltage drop, and a better general appearance.

Rating of Power Cable

Short Circuit Rating

It happens frequently that the conductor size necessary for installation is dictated by its ability to carry short-circuit current rather than sustained current. During a short-circuit, there is a sudden inrush of current for a few cycles followed by a steadier flow of current for a short period until the protection switchgear operators, normally between 0.1 – 0.3 seconds.

Conductor Size and Material

Insulation Material

Operating Maximum Temperature

Short Circuit Rating

120 sq-mm Copper conductor

PVC Insulation

70oC

13.80 KA/SEC

120 sq-mm Aluminium conductor

PVC Insulation

70oC

9.12 KA/SEC

120 sq-mm Copper conductor

PVC Insulation

85oC

12.48 KA/SEC

120 sq-mm Aluminium conductor

PVC Insulation

85oC

8.28 KA/

Current Carrying Capacity

The current carrying capacity is an important aspect is the selection of the optimum size of the conductor. Voltage drop and short rating is also a very important aspect to select the economical and optimum size of conductor. The safe current carrying capacity of an underground cable is determined by the maximum permissible temperature rise. The cause of temperature rise is the losses that occur in a cable which appear as heat.

Continuous Current Rating of (Cables laid singly)

2 Core × 16 mm2

2 Core × 25 mm2

(i) In Ground (Ground Temp 30oC)

103 A

131 A

(ii) In Duct (Ground Temp 30oC)

86 A

111 A

(iii) In Air (Ambient AirTemp 40oC)

94 A

125 A

Voltage Drop

The allowable maximum voltage drops from source to load is another aspect of power cable conductor design.

As per Ohm’s law, V = IR. The first is the choice of material used for the wire. Copper is a better conductor than The first is the choice of material used for the wire. Copper is a better conductor than and will have less voltage drop than aluminum for a given length and wire size.

Wire size is another important factor in determining voltage drop. Larger wire sizes (those with a greater diameter) will have less voltage drop than smaller wire sizes of the same length. In American wire gauge, every 6 gauge decrease gives a doubling of the wire diameter, and every 3 gauge decrease doubles the wire cross-sectional area. In the Metric Gauge scale, the gauge is 10 times the diameter in millimeters, so a 50 gauge metric wire would be 5 mm in diameter.

Construction of Power Cable

There are various parts of a cable to be taken care of during construction. The power cable mainly consists of

  1. Conductor

  2. Insulation

  3. LAY for Multicore cables only

  4. Bedding

  5. Beading/Armouring (if required)

  6. Outer Sheath

electrical power cable

Conductor

Conductors are the only power carrying path in a power cable. Conductors are of different materials. Mainly in the cable industry, we use copper (ATC, ABC) and aluminum conductors for power cables. There are different types of a conductor as Class 1: solid, Class 2 stranded, Class 5 flexible, Class 6 Extra flexible (Mostly used for cords and welding), etc. Conductor sizes are identified with conductor resistance.

Insulation

The insulation provided on each conductor of a cable by mainly PVC (Poly Vinyl Chloride), XLPE (Crosslinked Polyethylene), RUBBER (Various Types of Rubber). The insulating material is based on operating temperature.

Insulation Material

Maximum Operating Temperature

PVC TYPE A

75oC

PVC TYPE B

85oC

PVC TYPE C

85oC

XLPE

90oC

RUBBER – EPR IE-1

90oC

RUBBER – EPR IE-2, EPR IE-3, EPR IE-4, SILICON IE-5

150oC

Cores are identified by color-coding by using different colors on insulation or by number printing on cores

Beading (Inner Sheath)

This portion of the cable is also known as the inner sheath. Mostly it is used in Multi-core cables. It works as a binder for insulated conductors together in multi-core power cables and provides bedding to armor/braid. This portion of the cable is mainly made of PVC( PVC ST-1, PVC ST-2 ), RUBBER (CSP SE-3, CSP SE-4, and PCP SE-3, PCP SE-4, HOFR SE-3 HOFR SE-4, HD HOFR SE-3 ETC).

Armoring

There are mainly G.I. WIRE ARMOURING, G.I. STEEL STRIP armoring. It is done by placing G.I. WIREs, GI, or STEEL STRIPs one by one on inner sheath. Armoring is a process that is done mainly for providing an earthing shield to the current-carrying conductors as well as it is also used for earthing purposes of the cable for safety.

When there is any insulation failure in the conductor, the fault current gets enough paths to flow through the armor if it is properly earthed. Providing extra mechanical protection and strength to cable is an important added advantage of armoring. In mining cables this is done for conductance.

Beading

ANNEALED TINNED COPPER WIRE, NYLON BRAID, COTTON BRAID are mainly used for this purpose. Braiding is the process which gives high mechanical protection to cable and also used for earthing purpose. The significance of braiding is it is more flexible in comparison to armoring.

Outer Sheath

This is the outermost cover of the cable normally made of PVC (Poly Vinyl Chloride), RUBBER (Various Types of Rubber), and often the same material as the bedding. It is provided over the armor for overall mechanical, weather, chemical, and electrical protection. The outer sheath is the protection offered to the cable not much electrically but more mechanically.

Material

Advantages

Disadvantages

Max Operating Temperature

PVC

Cheap, Durable, Widely available

Highest dielectric losses, Melts at high temperatures, Contains halogens

70oC for general-purpose 85oC for heat-resisting purpose

PE

Lowest dielectric losses, High initial dielectric strength

Highly sensitive to water treeing, Material breaks down at high temperatures


XLPE

Low dielectric losses, Improved material properties at high temperatures

Does not melt but thermal expansion occurs, Medium sensitivity to water treeing (although some XLPE polymers are water-tree resistant)

90oC

EPR

Increased flexibility, Reduced thermal expansion (relative to XLPE), Low sensitivity to water treeing

Medium-High dielectric losses, Requires inorganic filler/additive

90oC

Paper / Oil

Low-Medium dielectric losses, Not harmed by DC testing, Known history of reliability

High weight, High cost,

Requires hydraulic pressure/pumps for insulating fluid, Difficult to repair, Degrades with moisture

70oC

Mainly above 6 square mm cables are called power cables but it depends upon the use of a cable. For PVC power cables we use IS:1554 and for XLPE power cables we use IS:7098 and for Rubber-based power cables, we use IS:9968 and other relevant specifications. Power cables are defined by voltage grade and nominal cross-sectional area.

Statement: Respect the original, good articles worth sharing, if there is infringement please contact delete.

Give a tip and encourage the author!
Recommended
PT Fuse Slow Blow: Causes, Detection & Prevention
PT Fuse Slow Blow: Causes, Detection & Prevention
I. Fuse Structure and Root Cause AnalysisSlow Fuse Blowing:From the design principle of fuses, when a large fault current passes through the fuse element, due to the metal effect (certain refractory metals become fusible under specific alloy conditions), the fuse first melts at the soldered tin ball. The arc then rapidly vaporizes the entire fuse element. The resulting arc is quickly extinguished by quartz sand.However, due to harsh operating environments, the fuse element may age under the comb
Edwiin
10/24/2025
Why Fuses Blow: Overload, Short Circuit & Surge Causes
Why Fuses Blow: Overload, Short Circuit & Surge Causes
Common Causes of Fuse BlowingCommon reasons for fuse blowing include voltage fluctuations, short circuits, lightning strikes during storms, and current overloads. These conditions can easily cause the fuse element to melt.A fuse is an electrical device that interrupts the circuit by melting its fusible element due to heat generated when current exceeds a specified value. It operates on the principle that, after an overcurrent persists for a certain period, the heat produced by the current melts
Echo
10/24/2025
Fuse Maintenance & Replacement: Safety and Best Practices
Fuse Maintenance & Replacement: Safety and Best Practices
1. Fuse MaintenanceFuses in service should be regularly inspected. The inspection includes the following items: Load current should be compatible with the rated current of the fuse element. For fuses equipped with a fuse blown indicator, check whether the indicator has actuated. Check the conductors, connection points, and the fuse itself for overheating; ensure connections are tight and making good contact. Inspect the fuse exterior for cracks, contamination, or signs of arcing/discharge. Liste
James
10/24/2025
Maintenance and Repair Items for 10kV High-Voltage Switchgear
Maintenance and Repair Items for 10kV High-Voltage Switchgear
I. Routine Maintenance and Inspection(1) Visual Inspection of Switchgear Enclosure No deformation or physical damage to the enclosure. Protective paint coating shows no severe rust, peeling, or flaking. Cabinet is securely installed, clean on the surface, and free of foreign objects. Nameplates and identification labels are neatly affixed and not falling off.(2) Check of Switchgear Operating Parameters Instruments and meters indicate normal values (comparable to typical operating data, with no s