Earthing of Electrical Transmission Tower

Electrical4u
03/25/2024

What Is Earthing Of Electrical Transmission Tower

We should probably earth each tower of an electrical transmission line. We must measure footing resistance of each tower. We should take the footing resistance of tower in dry season before stringing the earth wire and/or OPGW (where OPGW is applicable). In any circumstances footing resistance of the tower will not be more than 10 ohms.
We should use either pipe earthing or counterpoise for earthing of the electrical transmission line tower. The tower earthing lug should extend beyond the concrete base of the tower leg. We also use lug connector in case of counterpoise earthing. Logically we should pipe earthing to any of the four legs of a tower but practically we should provide earthing to that leg which is specifically marked for providing earthing. Generally the leg members of that leg is marked with capital letter A. It’s a normal practice to avoid mistakes by tower erection gang. In case of river crossing and railway crossing towers we provide earthing at diagonally opposite two legs of a tower.
Let us now discuss these two types of earthing one by one.

Pipe Earthing of Electrical Transmission Tower

In case of pipe earthing system we use galvanised steel pipe of diameter 25 mm and of length 3 meters. We bury the pipe vertically in the soil in such a manner that the top of the pipe shall be 1 meter below the ground level. Where the tower stands on rock we have to bury the earthing pipe in damp soil available nearer to the tower.
Then we connect the tower leg with the pipe with the help of galvanized steel tape of suitable cross section. In that case we have to bury the steel tape in a groove cut on the rock and adequately protect the steel tape from damage.

In case of pipe earthing system we fill surroundings of the pipe with alternating layers of charcoal and salt, which maintain the surrounding soil of the pipe moist. A details pictorial representation of a pipe earthing is down here below.
pipe earthing of electrical transmission tower

Counterpoise Earthing

We use 10.97 mm dia galvanized wire for the purpose of counterpoise earthing of electrical transmission tower. Here we connect the galvanized wire with the leg of the tower with the help of galvanized lug and the galvanized lug is fitted with a tower leg with the help of 16 mm dia nut and bolts. The steel wire used for the purpose must be of minimum 25 meters in length. The wire is buried tangentially under the ground of minimum 1 meter depth from the ground level. Here four legs of a tower are connected together with counterpoise earth wire burried below the ground level of 1 meter depth as already been told.

Statement: Respect the original, good articles worth sharing, if there is infringement please contact delete.

Electrical4u

Electrical4U is dedicated to the teaching and sharing of all things related to electrical and electronics engineering.

What is an electricity meter?
What is an electricity meter?
Definition: An energy meter is a device used to measure the electrical energy consumed by an electrical load. Electrical energy refers to the total power consumed and utilized by a load over a specific period of time. Energy meters are used in domestic and industrial AC circuits to measure power consumption. They are relatively inexpensive and accurate.Construction of an Energy MeterThe construction of a single - phase energy meter is shown in the figure below.The energy meter consists of four m
Edwiin
07/18/2025
Analysis of the Principle of Second - harmonic Restraint for Overcurrent Protection of Distribution Automation Switches
Analysis of the Principle of Second - harmonic Restraint for Overcurrent Protection of Distribution Automation Switches
Substance of Second - harmonic Restraint in Overcurrent ProtectionThe substance of second - harmonic restraint in overcurrent protection is to use the second - harmonic component to judge whether the current is a fault current or an excitation inrush current. When the percentage of the second - harmonic component to the fundamental - wave component is greater than a certain value, it is judged to be caused by the excitation inrush current, and the overcurrent protection is blocked.Therefore, the
Leon
07/18/2025
What are the typical connection methods for 35kV distribution lines?
What are the typical connection methods for 35kV distribution lines?
Typical Wiring Diagram of 35kV Line Radial π ConnectionWhen a 35kV line adopts a radial power grid structure, a single - side power supply or a double - side power supply radial type can be used according to the situation of the power supply points, and a loop - out interval is reserved at the end of the line.Typical Wiring Diagram of 35kV Line Radial T - ConnectionFor double - radial lines, it is advisable to select a double - side power supply. When the power supply points do not meet the r
Leon
07/18/2025
Why are the ground fault point and the accident point not at the same location?
Why are the ground fault point and the accident point not at the same location?
Fault Transfer VoltageIn low - voltage distribution systems, there is a type of personal electric shock accident where the accident occurrence point and the system fault point are not at the same location. This kind of accident occurs because after a ground fault happens elsewhere, the generated fault voltage is conducted to the metal casings of other equipment through the PE wire or PEN wire. When the fault voltage on the metal casing of the equipment is higher than the human - body safe voltag