Location of Shunt Capacitors

Electrical4u
Field: Basic Electrical
0
China

Where Is The Location Of Shunt Capacitors

The power factor improver capacitor can be installed at system bus, distribution point and at load itself. But decision should be taken in view of expenditure and utility.
In certain loads mainly in industrial load, the entire load is switch ON or OFF based on need. In such cases it is recommended to install capacitor bank with the feeder which provides entire of this particular load. This scheme is known as branch capacitor bank scheme. As
capacitor bank is directly connected to feeder or branch, it does not help to reduce losses in primary system from where the branch comes out.
location of shunt capacitors

In this scheme, the individual capacitor bank connected with individual load feeder, is which ON and OFF individually along with load feeder. Hence the scheme provides better control over reactive power but the scheme is expensive.
Although installing shunt capacitor bank at every individual load point, compensates reactive power individually of every load and hence it provides better improvement of voltage profile, better reduction in individual load losses, and better reduction in energy bill of individual customer but still it is not practicable as it makes the system complex and expensive. The main reasons of complexity is in that case, different sizes and capacities of capacitor bank are required to be installed depending upon the demand of individual load. To overcome this difficulty, it is always preferable to install a bulk capacitor bank at high voltage
bus system instead of installing smaller capacitor bank at every load point. Although the control over reactive power of the system is little bit compromised but still it is much practical approach in the view of complexisity and cost. So capacitor bank at load and capacitor bank at primary systems both have their own benefits. Depending upon the demand of system, both schemes are used.
Capacitor bank can be installed in ∑ HV system, high voltage system, feeders and individual distribution system.

Distribution System Capacitor Bank

In distribution feeder capacitor bank are installed on pole to compensate reactive power of that particular feeder. These banks are normally mounted on one of the poles on which the distribution feeders run. The mounted capacitor banks are normally interconnected with over head feeder conductors by means of insulated power cable. The size of the cable depends upon the voltage rating of the system. The voltage range of the system for which pole mounted capacitor bank can be install, may be from 440 V to 33 KV. The rating of capacitor bank may be from 300 KVAR to MVAR. The pole mounted capacitor bank can be either fixed unit or switched unit depending upon varying load condition.

EHV Shunt Capacitor

In extra high voltage system, the generated electrical power may have to be transmitted a long distance via transmission line. During journey of power, sufficient voltage may be dropped due to inductive effect of the line conductors. This voltage drop may be compensated by providing ∑ HV capacitor bank at ∑ HV sub-station. This drop of voltage is maximum at peak load condition, hence, the capacitor bank installed for in this case should have switching control to make it off and on as when required.

Substation Capacitor Bank

When high inductive load has to be delivered from a high voltage or medium voltage substation, one or more capacitor bank of suitable size should be installed at substation to compensate inductive VAR of the entire load. These capacitors banks are controlled by circuit breaker and provided with lightening arrestors. Typical protection scheme along with protection relays are also provided.

Metal Encoder Capacitor Bank

For small and industrial subtraction indoor type capacitor banks may also be used. These capacitor bank are installed in metal cabinet. This design is compact and bank requires less maintenance. The uses of these banks are more compared to outdoor bank, as these are not exposed to external environment.

Distribution Capacitor Bank

Distribution capacitor banks are normally pole mounted capacitor bank installed nearer to load point or installed at distribution subtraction.
These banks do not help to improve power factor of primary system. These capacitors bank are cheaper than other power capacitors bank. All types of protection schemes for capacitor bank cannot be provided to a pole mounted capacitor bank. Although pole mounted cap bank is outdoor type but sometimes it is kept in metal enclosure to protect from outdoor environmental conditions.

Fixed Capacitor Bank

There are certain loads mainly certain industrial loads which need fixed reactive power to meet power factor. In this type feeder fixed capacitor bank is used. These banks do not have separate control system to switch ON or OFF. These banks run with feeders. The banks are connected to the feeders as long as the feeders are live.

Switched Capacitor Banks

In high voltage power system, compensation of reactive power is mainly required during peak load condition of system. There may be reverse effect if the bank is connected to the system at mean load condition. At low load condition, the capacitive effect of bank may increase the reactive power of the system instead of decreasing it.
In this situation capacitors bank must be switched ON during peak load poor power factor condition and must also be switched OFF during low load and high power factor condition. Here switched capacitor banks are used. When a
capacitor bank is switched ON it provides more or less constant reactive power to the system. It helps to maintain desired power factor of the system even at peak load condition. It prevents, over voltage of system during low load condition as capacitor is disconnected from the system during low load condition. During operation of bank, it reduces losses both of the feeders and transformer of the system as it is directly installed at primary power system.

Statement: Respect the original, good articles worth sharing, if there is infringement please contact delete.

Give a tip and encourage the author!
Recommended
Ensuring Reliability: A Deep Dive into Transformer Maintenance
IntroductionElectric transformers are the backbone of modern power distribution systems, silently enabling the reliable delivery of electricity to homes, businesses, and industries. As these critical assets age and the demand for uninterrupted power grows, the importance of diligent transformer maintenance has never been greater. This essay explores the essential role of transformer maintenance, highlighting the value of proactive care, the impact of advanced diagnostic technologies, and the tra
Vziman
09/03/2025
How does a transformer work?
Transformer Operation PrincipleA transformer is an electrical device that operates on the principle of electromagnetic induction to transfer electrical energy from one circuit to another. It enables the adjustment of voltage levels within an alternating current (AC) system, either stepping up (increasing) or stepping down (decreasing) voltage while maintaining the same frequency.Working Principle:Basic ComponentsA transformer consists of two coils, known as windings—the "primary winding" connect
Rockwell
09/03/2025
What is the difference between a dielectric and an insulator?
Dielectrics and insulators are distinguished primarily by their applications. One of the main differences is that a dielectric can store electrical energy by becoming polarized in an electric field, whereas an insulator resists the flow of electrons to prevent current conduction. Other key differences between them are outlined in the comparison chart below.Definition of DielectricA dielectric material is a type of insulator that contains few or no free electrons. When subjected to an electric fi
Edwiin
08/30/2025
What losses occur during operation of the transformer? How to reduce losses?
Transformers experience various types of losses during operation, primarily categorized into two main types: copper losses and iron losses.Copper LossesCopper losses, also known as I²R losses, are caused by the electrical resistance of the transformer windings—typically made of copper. As current flows through the windings, energy is dissipated in the form of heat. These losses are proportional to the square of the load current (I²R), meaning they increase significantly with high
Rockwell
08/29/2025
Seed Inquiry
Download
Get the IEE Business Application
Use the IEE-Business app to find equipment, obtain solutions, connect with experts, and participate in industry collaboration anytime, anywhere—fully supporting the development of your power projects and business.