• Product
  • Suppliers
  • Manufacturers
  • Solutions
  • Free tools
  • Knowledges
  • Experts
  • Communities
Search


Fault Diagnosis and Troubleshooting of 10kV High-Voltage Switchgear

Garca
Field: Design & Maintenance
Congo

I. Common Fault Types and Diagnostic Methods

Electrical Faults

  • Circuit Breaker Failure to Operate or Maloperation: Check the energy storage mechanism, closing/tripping coils, auxiliary switches, and secondary circuits.

  • High-Voltage Fuse Blown: Measure voltage across the fuse terminals; inspect busbar joints, cable terminations, and protection relay settings.

  • Busbar Discharge or Insulator Damage: Listen for discharge sounds, check temperature at busbar connections, and visually inspect insulators for flashover traces.

Mechanical Faults

  • Disconnector Stuck or Jammed: Inspect lubrication of mechanical linkages, operating spring condition, and auxiliary switches.

  • Operating Mechanism Spring Failure: Check for spring fatigue or aging; test the energy storage mechanism.

Insulation Faults

  • Insulator Damage or Busbar Discharge: Visually inspect insulator surfaces for flashover marks; use an infrared thermal imager to monitor temperature at busbar joints.

Control Circuit Faults

  • Relay Protection Maloperation: Verify protection relay settings, inspect CT secondary circuits, and check stability of control power supply.

II. Fault Handling Methods

Electrical Fault Handling

  • Circuit Breaker Failure to Operate or Maloperation: Manually store energy and test closing operation; replace damaged coils; repair or replace faulty auxiliary switches.

  • High-Voltage Fuse Blown: Tighten busbar joints, adjust protection settings, and replace the fuse.

  • Busbar Discharge or Insulator Damage: Tighten busbar connection bolts, clean dust from insulator surfaces, and install dehumidification devices.

Mechanical Fault Handling

  • Disconnector Stuck or Jammed: Lubricate linkage mechanisms, replace springs, and manually reset auxiliary switches.

  • Operating Mechanism Spring Failure: Replace the spring, apply lubricant, and manually test the energy storage function.

Insulation Fault Handling

  • Insulator Damage or Busbar Discharge: Replace damaged insulators; perform power-frequency withstand voltage tests on the busbar.

Control Circuit Fault Handling

  • Relay Protection Maloperation: Recalibrate protection settings, repair CT secondary circuits, and stabilize the control power supply.

III. Preventive Maintenance Measures

  • Perform regular infrared thermography to detect overheating issues.

  • Conduct partial discharge (PD) testing to identify early signs of insulation aging.

  • Maintain mechanical components by lubricating moving parts to prevent jamming.

  • Inspect cable terminations regularly to prevent loosening or oxidation, reducing arc discharge risks.

  • Clean dust and moisture periodically to improve insulation performance.

Note: These methods should be applied flexibly according to actual site conditions. Always ensure safety during troubleshooting. When necessary, contact qualified professionals for assistance.

Give a tip and encourage the author!

Recommended

How to Judge, Detect and Troubleshoot Transformer Core Faults
1. Hazards, Causes, and Types of Multi-Point Grounding Faults in Transformer Cores1.1 Hazards of Multi-Point Grounding Faults in the CoreUnder normal operation, a transformer core must be grounded at only one point. During operation, alternating magnetic fields surround the windings. Due to electromagnetic induction, parasitic capacitances exist between the high-voltage and low-voltage windings, between the low-voltage winding and the core, and between the core and the tank. The energized windin
01/27/2026
5 Fault Diagnosis Techniques for Large Power Transformers
Transformer Fault Diagnosis Methods1. Ratio Method for Dissolved Gas AnalysisFor most oil-immersed power transformers, certain combustible gases are produced in the transformer tank under thermal and electrical stress. The combustible gases dissolved in oil can be used to determine the thermal decomposition characteristics of the transformer oil-paper insulation system based on their specific gas content and ratios. This technology was first used for fault diagnosis in oil-immersed transformers.
12/20/2025
Classification of Equipment Defects for Relay Protection and Safety Automatic Devices in Substations
In daily operations, various equipment defects are inevitably encountered. Whether maintenance personnel, operation and maintenance staff, or specialized management personnel, all must understand the defect classification system and adopt appropriate measures according to different situations.According to Q/GDW 11024-2013 "Operation and Management Guide for Relay Protection and Safety Automatic Devices in Smart Substations," equipment defects are classified into three levels based on severity an
12/15/2025
Under What Conditions Will the Line Circuit Breaker Auto-Reclosing Signal Be Locked Out?
The line circuit breaker auto-reclosing signal will be locked out if any of the following conditions occur:(1) Low SF6 gas pressure in circuit breaker chamber at 0.5MPa(2) Insufficient energy storage in circuit breaker operating mechanism or low oil pressure at 30MPa(3) Busbar protection operation(4) Circuit breaker failure protection operation(5) Line distance protection zone II or zone III operation(6) Short lead protection operation of circuit breaker(7) Presence of remote tripping signal(8)
12/15/2025
Related Products
Send inquiry
+86
Click to upload file
Download
Get the IEE Business Application
Use the IEE-Business app to find equipment, obtain solutions, connect with experts, and participate in industry collaboration anytime, anywhere—fully supporting the development of your power projects and business.