Rating of Circuit Breaker | Short Circuit Breaking Making Current

03/25/2024

Circuit Breaker Ratings

The rating of a circuit breaker includes:

  1. Rated short circuit breaking current.

  2. Rated short circuit making current.

  3. Rated operating sequence of circuit breaker.

  4. Rated short time current.

Short Circuit Breaking Current of Circuit Breaker

This is the maximum short circuit current which a circuit breaker (CB) can withstand before it, finally cleared by opening its contacts.

When a short circuit flows through a circuit breaker, there would be thermal and mechanical stresses in the current carrying parts of the breaker. If the contact area and cross-section of the conducting parts of the circuit breaker are not sufficiently large, there may be a chance of permanent damage in insulation as well as conducting parts of the CB.

As per Joule’s law of heating, the rising temperature is directly proportional to square of short circuit current, contact resistance and duration of short circuit current. The short circuit current continuous to flow through circuit breaker until the short circuit is cleared by opening operation of the circuit breaker.

As the thermal stress in the circuit breaker is proportional to the period of short circuit, the breaking capacity of electrical circuit breaker, depends upon the operating time. At 160oC aluminum becomes soft and losses its mechanical strength, this temperature may be taken as limit of temperature rise of breaker contacts during short circuit.

Hence short circuit breaking capacity or short circuit breaking current of circuit breaker is defined as maximum current can flow through the breaker from time of occurring short circuit to the time of clearing the short circuit without any permanent damage in the CB.
The value of short circuit breaking current is expressed in RMS.

During short circuit, the CB is not only subjected to thermal stress, it also suffers seriously from mechanical stresses. So during determining short circuit capacity, the mechanical strength of the CB is also considered.

So for choosing suitable circuit breaker it is obvious to determine the fault level at that point of the system where CB to be installed. Once the fault level of any part of electrical transmission is determined it is easy to choose the correct rated circuit breaker for this part of network.

Rated Short Circuit Making Capacity

The short circuit making capacity of circuit breaker is expressed in peak value not in rms value like breaking capacity. Theoretically at the instant of fault occurrence in a system, the fault current can rise to twice of its symmetrical fault level.

At the instant of switching on a circuit breaker in faulty condition, of system, the short circuit portion of the system connected to the source. The first cycle of the current during a circuit is closed by circuit breaker, has maximum amplitude. This is about twice of the amplitude of symmetrical fault current waveform.

The breaker’s contacts have to withstand this highest value of current during the first cycle of waveform when breaker is closed under fault. On the basis of this above mentioned phenomenon, a selected breaker should be rated with short circuit making capacity.

As the rated short circuit making current of circuit breaker is expressed in maximum peak value, it is always more than rated short circuit breaking current of circuit breaker. The normal value of short circuit making current is 2.5 times more than short circuit breaking current. This holds true for both standard and remote control circuit breaker.

Rated Operating Sequence or Duty Cycle of Circuit Breaker

This is mechanical duty requirement of circuit breaker operating mechanism. The sequence of rated operating duty of a circuit breaker has been specified as:

Where, O indicates opening operation of CB.

CO represents closing operation time which is immediately followed by an opening operation without any intentional time delay.

t’ is time between two operations which is necessary to restore the initial conditions and/or to prevent undue heating of conducting parts of circuit breaker. t = 0.3 sec for circuit breaker

intended for first auto re closing duty, if not otherwise specified.

Suppose rated duty circle of a circuit breaker is:


This means, an opening operation of circuit breaker is followed by a closing operation after a time interval of 0.3 sec, and then the circuit breaker again opens without any intentional time delay. After this opening operation the CB is again closed after 3 minutes and then instantly trips without any intentional time delay.

Rated Short Time Current

This is the current limit which a circuit breaker can carry safely for certain specific time without any damage in it. The circuit breakers do not clear the short circuit current as soon as any fault occurs in the system. There always some intentional and an intentional time delays present between the instant of occurrence of fault and instant of clearing the fault by CB.

This delay is because of time of operation of protection relays, time of operation of circuit breaker and also there may be some intentional time delay imposed in relay for proper coordination of power system protection. Even a circuit breaker fails to trip, the fault will be cleared by next higher positioned circuit breaker.

In this case the fault clearing time is longer. Hence, after fault, a circuit breaker has to carry the short circuit for certain time. The summation of all time delays should not be more than 3 seconds; hence a circuit breaker should be capable of carrying a maximum faulty current for at least this short period of time.

The short circuit current may have two major affects inside a circuit breaker.

  1. Because of the high electric current, there may be high thermal stress in the insulation and conducting parts of CB.

  2. The high short circuit current, produces significant mechanical stresses in different current carrying parts of the circuit breaker.

A circuit breaker is designed to withstand these stresses. But no circuit breaker has to carry a short circuit current not more than current for a specified short period. The rated short time current of a circuit breaker is at least equal to rated short circuit breaking current of the circuit breaker.

Rated Voltage of Circuit Breaker

Rated voltage of circuit breaker depends upon its insulation system. For below 400 KV systems, the circuit breaker is designed to withstand 10% above the normal system voltage. For above or equal 400 KV system the insulation of circuit breaker should be capable of withstanding 5% above the normal system voltage.

That means, rated voltage of circuit breaker corresponds to the highest system voltage. This is because during no load or small load condition the voltage level of power system is allowed rise up to highest voltage rating of the system.

A circuit breaker is also subject to two other high voltage conditions.

  1. Sudden disconnection of huge load for any other cause, the voltage imposed on the CB and also between the contacts when the CB is open, may be very high compared to higher system voltage. This voltage may be of power frequency but does not stay for very long period as this high voltage situation must be cleared by protective switchgear.
    But a circuit breaker may have to withstand this power frequency over voltage, during its normal life span.
    The Circuit Breaker must be rated for power frequency withstands voltage for a specific time only. Generally the time is 60 seconds. Making power frequency withstand capacity, more than 60 second is not economical and not practically desired as all the abnormal situations of electrical power system are definitely cleared within much smaller period than 60 seconds.

  2. Like other apparatuses connected to power system, a circuit breaker may have also to face lighting impulse and switching impulses during its life span.
    The insulation system of CB and contact gap of an open CB have to withstand these impulse voltage waveform amplitude of this disturbance is very very high but extremely transient in nature. So a circuit breaker is designed to withstand this impulse peaky voltage for microsecond range only.

Nominal System Voltage

Highest System Voltage

Power Frequency Withstand Voltage

Impulse Voltage Level

11 KV

12 KV

33 KV

36 KV

70 KV

170 KV

132 KV

145 KV

275 KV

650 KV

220 KV

245 KV

460 KV

1050 KV

400 KV

420 KV

Statement: Respect the original, good articles worth sharing, if there is infringement please contact delete.

Hello,I'm Wdwiin. A decade of hands-on experience in electrical engineering, specializing in high-voltage systems, smart grids, and renewable energy technologies. Passionate about technical exchange and knowledge sharing, committed to interpreting industry trends with professional insights to empower peers. Connection creates value—let’s explore the boundless possibilities of the electrical world together!

What is the difference between a dielectric and an insulator?
What is the difference between a dielectric and an insulator?
Dielectrics and insulators are distinguished primarily by their applications. One of the main differences is that a dielectric can store electrical energy by becoming polarized in an electric field, whereas an insulator resists the flow of electrons to prevent current conduction. Other key differences between them are outlined in the comparison chart below.Definition of DielectricA dielectric material is a type of insulator that contains few or no free electrons. When subjected to an electric fi
08/30/2025
What losses occur during operation of the transformer? How to reduce losses?
What losses occur during operation of the transformer? How to reduce losses?
Transformers experience various types of losses during operation, primarily categorized into two main types: copper losses and iron losses.Copper LossesCopper losses, also known as I²R losses, are caused by the electrical resistance of the transformer windings—typically made of copper. As current flows through the windings, energy is dissipated in the form of heat. These losses are proportional to the square of the load current (I²R), meaning they increase significantly with high
Rockwell
08/29/2025
Cable Fault Detection, Testing, Location and Repair
Cable Fault Detection, Testing, Location and Repair
I. Methods for Cable Testing and Inspection:Insulation Resistance Test: Use an insulation resistance tester to measure the insulation resistance value of the cable. A high insulation resistance value indicates good insulation, while a low value may suggest insulation problems requiring further investigation.Voltage Withstand Test: Apply a high-voltage test using a high-voltage tester to verify whether the cable can withstand high voltage under its rated operating conditions. Under normal circums
08/29/2025
Cable Quality Inspection and Cable Detection & Testing
Cable Quality Inspection and Cable Detection & Testing
Power cable quality inspection and cable testing are conducted to ensure that the cable's quality and performance meet specified requirements, thereby guaranteeing the safe and stable operation of power systems. Below are some common contents of power cable quality inspection and cable testing:Visual Inspection: Check the cable surface for physical defects such as damage, deformation, or scratches to ensure the cable's exterior is intact.Dimensional Measurement: Measure dimensional parameters su
08/29/2025
Inquiry
Download
IEE-Business is dedicated to serving the personnel in the global power industry.
Join IEE-Business, not only can you discover power equipment and power knowledge, but also canhnd like - minded friends!