Circuit Breaker Ratings

Edwiin
Edwiin
Field: Power switch
China

The rating of a circuit breaker is determined by the duties it performs. For complete specifications, standard ratings and various tests for switches and circuit breakers should be consulted. In addition to the normal operation of circuit breakers, they are required to perform the following three major duties under short-circuit conditions:

  • Breaking the faulty section of the system, defined as the breaking capacity of the circuit breaker.

  • Making the circuit under the greatest asymmetrical current in the current wave, referring to the making capacity of the circuit breaker.

  • Carrying fault current safely for a short time while another breaker clears the fault, known as the short-time capacity of the circuit breaker.

In addition to the above ratings, circuit breakers should be specified in terms of:

  • Number of poles

  • Rated voltage

  • Rated current

  • Rated frequency

  • Operating duty

Detailed explanations of these terms:
Rated Voltage

The rated maximum voltage of a circuit breaker is the highest RMS voltage (above nominal voltage) for which it is designed, serving as the upper limit for operation. Rated voltage is expressed in kVrms and uses phase-to-phase voltage for three-phase circuits.

Rated Current

The rated normal current of a circuit breaker is the RMS value of the current it can continuously carry at rated frequency and voltage under specified conditions.

Rated Frequency

The frequency at which a circuit breaker is designed to operate, with the standard frequency being 50 Hz.

Operating Duty

The operating duty of a circuit breaker consists of the prescribed number of unit operations at stated intervals. The operating sequence refers to the opening and closing operations of the circuit breaker contacts.

Breaking Capacity

This term denotes the highest short-circuit current a breaker can interrupt under specified conditions of transient recovery voltage and power-frequency voltage, expressed in KA RMS at contact separation. Breaking capacities are categorized into:

  • Symmetrical breaking capacity

  • Asymmetrical breaking capacity

Making Capacity

When a circuit breaker closes under short-circuit conditions, its making capacity is the ability to withstand electromagnetic forces (directly proportional to the square of the peak making current). The making current is the peak value of the maximum current wave (including the DC component) in the first cycle after the breaker closes the circuit.

Short-Circuit Current Withstand Capacity

This is the RMS value of current a breaker can carry in a fully closed state without damage for a specified time interval under prescribed conditions, typically expressed in KA for 1 second or 4 seconds. These ratings are based on thermal limitations. Low-voltage circuit breakers generally lack such short-circuit current ratings, as they are typically equipped with straight-acting series overload trips.

Give a tip and encourage the author!
Recommended
PT Fuse Slow Blow: Causes, Detection & Prevention
PT Fuse Slow Blow: Causes, Detection & Prevention
I. Fuse Structure and Root Cause AnalysisSlow Fuse Blowing:From the design principle of fuses, when a large fault current passes through the fuse element, due to the metal effect (certain refractory metals become fusible under specific alloy conditions), the fuse first melts at the soldered tin ball. The arc then rapidly vaporizes the entire fuse element. The resulting arc is quickly extinguished by quartz sand.However, due to harsh operating environments, the fuse element may age under the comb
Edwiin
10/24/2025
Why Fuses Blow: Overload, Short Circuit & Surge Causes
Why Fuses Blow: Overload, Short Circuit & Surge Causes
Common Causes of Fuse BlowingCommon reasons for fuse blowing include voltage fluctuations, short circuits, lightning strikes during storms, and current overloads. These conditions can easily cause the fuse element to melt.A fuse is an electrical device that interrupts the circuit by melting its fusible element due to heat generated when current exceeds a specified value. It operates on the principle that, after an overcurrent persists for a certain period, the heat produced by the current melts
Echo
10/24/2025
Fuse Maintenance & Replacement: Safety and Best Practices
Fuse Maintenance & Replacement: Safety and Best Practices
1. Fuse MaintenanceFuses in service should be regularly inspected. The inspection includes the following items: Load current should be compatible with the rated current of the fuse element. For fuses equipped with a fuse blown indicator, check whether the indicator has actuated. Check the conductors, connection points, and the fuse itself for overheating; ensure connections are tight and making good contact. Inspect the fuse exterior for cracks, contamination, or signs of arcing/discharge. Liste
James
10/24/2025
Maintenance and Repair Items for 10kV High-Voltage Switchgear
Maintenance and Repair Items for 10kV High-Voltage Switchgear
I. Routine Maintenance and Inspection(1) Visual Inspection of Switchgear Enclosure No deformation or physical damage to the enclosure. Protective paint coating shows no severe rust, peeling, or flaking. Cabinet is securely installed, clean on the surface, and free of foreign objects. Nameplates and identification labels are neatly affixed and not falling off.(2) Check of Switchgear Operating Parameters Instruments and meters indicate normal values (comparable to typical operating data, with no s
Edwiin
10/24/2025
Related Products
Send inquiry
Download
Get the IEE Business Application
Use the IEE-Business app to find equipment, obtain solutions, connect with experts, and participate in industry collaboration anytime, anywhere—fully supporting the development of your power projects and business.