What is Valve Type Lightning Arrester?

04/16/2025

What is Valve Type Lightning Arrester?

Definition

A lightning arrester that comprises single or multiple gaps connected in series with a current - controlling element is referred to as a lightning arrester. The gap between the electrodes blocks the flow of current through the arrester, except when the voltage across the gap exceeds the critical gap flashover voltage. The valve - type arrester is also called a gap surge diverter or a silicon - carbide surge diverter with a series gap.

Construction of Valve - Type Lightning Arrester

The valve - type lightning arrester is constructed with a multiple - spark - gap assembly connected in series with a resistor made of a non - linear element. Each spark gap consists of two elements. To address the non - uniform voltage distribution between the gaps, non - linear resistors are connected in parallel across each individual gap. This construction helps in ensuring the proper functioning of the arrester under different electrical conditions, allowing it to effectively protect electrical equipment from lightning - induced over - voltages.

image.png

The resistor elements are fabricated from silicon carbide combined with inorganic binders. The entire assembly is encased within a sealed porcelain housing that is filled with either nitrogen gas or SF6 gas. This gas - filled environment helps to enhance the electrical insulation and performance of the arrester.

Working of Valve - Type Lightning Arrester

Under normal low - voltage conditions, the parallel resistors prevent spark - over across the gaps. As a result, slow changes in the applied voltage do not pose a threat to the electrical system. However, when rapid voltage changes occur across the terminals of the arrester, such as those induced by lightning strikes or electrical surges, the air gaps in the arrester experience spark - over. The resulting current is then discharged to the ground through the non - linear resistor. Significantly, the non - linear resistor exhibits extremely low resistance under these high - voltage, high - current conditions, effectively shunting the excessive current away from the protected electrical equipment and safeguarding it from potential damage.

image.png

After the passage of the surge, the voltage impressed across the arrester drops. Concurrently, the resistance of the arrester increases steadily until the normal operating voltage is restored. Once the surge has dissipated, a small current at the low - power frequency begins to flow through the path created by the previous flash - over. This particular current is referred to as the power follow current.

The magnitude of the power follow current gradually decreases to a value that can be interrupted by the spark gap as the gap recovers its dielectric strength. The power follow current is extinguished at the first zero - crossing of the current waveform. As a result, the power supply remains uninterrupted, and the arrester is once again ready for normal operation. This process is known as the resealing of the lightning arrester.

Stages of Valve - Type Lightning Arrester Operation

When a surge reaches the transformer, it encounters the lightning arrester, as depicted in the figure below. In approximately 0.25 μs, the voltage reaches the breakdown value of the series gap, triggering the arrester to discharge. This discharge action diverts the excessive current associated with the surge, protecting the transformer and other connected electrical equipment from potential damage caused by the high - voltage transient.

image.png

As the surge voltage rises, the resistance of the non - linear element decreases. This drop in resistance enables the continued discharge of additional surge energy. Consequently, the voltage transmitted to the terminal equipment is limited, as clearly shown in the figure below. This mechanism plays a crucial role in safeguarding the terminal equipment from the harmful effects of high - voltage surges by effectively controlling the amount of voltage reaching it.

image.png

image.png

As the voltage decreases, the current flowing to the ground diminishes simultaneously, while the resistance of the lightning arrester increases. Eventually, the lightning arrester reaches a stage where the spark gap interrupts the current flow, and the arrester effectively reseals itself. This process ensures that once the surge event subsides, the arrester returns to its normal, non - conducting state, ready to protect the electrical system from future surges.

arrester.jpg

The maximum voltage that develops across the arrester terminal and is transmitted to the terminal equipment is termed the discharge value of the arrester. This value is crucial as it determines the extent to which the arrester can safeguard the connected equipment from excessive voltage surges.

Types of Valve - Type Lightning Arresters

Valve - type lightning arresters can be classified into several types, namely station types, line types, arresters for the protection of rotating machines (distribution type or secondary type).

  • Station - Type Valve Lightning Arrester

    • This type of arrester is primarily used to protect critical power equipment in circuits ranging from 2.2 kV to 400 kV and even higher voltage levels. It is characterized by its high energy - dissipation capacity. This enables it to handle large amounts of surge energy, ensuring the safety of the essential power components within the station.

  • Line - Type Lightning Arrester

    • Line - type arresters are utilized for the protection of substation equipment. They have a smaller cross - sectional area, are lighter in weight, and are more cost - effective compared to station - type arresters. However, they allow a higher surge voltage across their terminals in comparison to station - type arresters and possess a lower surge - carrying capacity. Despite these differences, they are well - suited for protecting substation equipment due to their specific design and cost - efficiency.

  • Distribution Arrester

    • Distribution arresters are typically mounted on poles and are employed to protect generators and motors within the distribution network. Their placement on poles makes them easily accessible for installation and maintenance while effectively safeguarding the electrical machinery in the distribution system.

  • Secondary Arrester

    • Secondary arresters are designed to protect low - voltage apparatus. Similarly, arresters for the protection of rotating machines are specifically engineered to shield generators and motors. These arresters play a vital role in ensuring the reliable operation of low - voltage and rotating equipment by preventing damage caused by voltage surges.

The Electricity Encyclopedia is dedicated to accelerating the dissemination and application of electricity knowledge and adding impetus to the development and innovation of the electricity industry.

What is the difference between a dielectric and an insulator?
What is the difference between a dielectric and an insulator?
Dielectrics and insulators are distinguished primarily by their applications. One of the main differences is that a dielectric can store electrical energy by becoming polarized in an electric field, whereas an insulator resists the flow of electrons to prevent current conduction. Other key differences between them are outlined in the comparison chart below.Definition of DielectricA dielectric material is a type of insulator that contains few or no free electrons. When subjected to an electric fi
08/30/2025
Transformer Connection Sections
Transformer Connection Sections
Transformer Connection DesignationsThe transformer connection designation indicates the winding connection method and the phase relationship between the line voltages of the primary and secondary windings. It consists of two parts: letters and a number. The letters on the left denote the connection configurations of the high-voltage and low-voltage windings, while the number on the right is an integer from 0 to 11.This number represents the phase shift of the low-voltage winding's line voltage r
08/15/2025
Automatic Reclosing Scheme in Transmission Systems
Automatic Reclosing Scheme in Transmission Systems
Automatic Reclosing Scheme for Transmission SystemsThe automatic reclosing system is a series-connected network designed to reduce operating costs and enhance network reliability. Extra-high voltage (EHV) transmission lines are used to transmit large amounts of power, on the order of thousands of megawatts (MW), and therefore should not be interrupted at all costs. Although faults on these overhead lines are common, the power transmitted through them should not be interrupted for long periods du
08/07/2025
Transformer operation and maintenance
Transformer operation and maintenance
Transformer Operating TemperatureDuring operation, transformers generate copper losses and iron losses, both of which are converted into heat, causing the transformer’s temperature to rise. Most transformers in China use Class A insulation. Due to heat transfer characteristics, significant temperature differences exist between different components during operation: winding temperature is the highest, followed by the core, and then the temperature of the insulating oil (with upper-layer oil being
07/31/2025
Inquiry
Download
IEE-Business is dedicated to serving the personnel in the global power industry.
Join IEE-Business, not only can you discover power equipment and power knowledge, but also canhnd like - minded friends!