• Product
  • Suppliers
  • Manufacturers
  • Solutions
  • Free tools
  • Knowledges
  • Experts
  • Communities
Search


Inverse Time Relay | Definite Time Lag Relay

Electrical4u
Field: Basic Electrical
0
China

What Is Inverse Time Relay

In this type of relays, the time of operation depends upon the magnitude of actuating quantity. If the magnitude of actuating quantity is very high, the relay operation is very fast. In other words, the relay operating time that is time delay in the relay is inversely proportional to the magnitude of actuating quantity.
The general characteristics of an inverse time relay is shown are in figure below.
inverse time relay curve

Here, in the graph it is clear that, when, actuating quantity is OA, the operating time of the relay is OA’, when actuating quantity is OB, the relay operating time is OB’ and when actuating quantity is OC, the relay operating quantity is OC’.
In the graph above, it is also observed that, when actuating quantity is less than OA, the relay operating time becomes infinity, which means for actuating quantity less than OA, the relay does not at all actuate. This minimum value of actuating quantity for which a relay initiates its operation is known as pick up value of actuating quantity. Here it is denoted as OA.
It is also seen from the graph that, when actuating quantity approaches to infinity along x axis the operating time does not approach to zero. The curve approaches to an approximately constant operating time. This is approximately minimum time required to operate the relay.

The inverse time relay, where the actuating quantity is current, is known as inverse current relay.
In this type of relay, the inverse time is achieved by attaching some mechanical accessories in the relay.
Inverse time delay is achieved in induction disc relay by providing a permanent magnet in such a way, that, when disc rotates, it cuts the
flux of permanent magnet. Due to this, current is induced in the disc which slows down the movement of the disc. A solenoid relay can be made inverse time relay, by providing a piston and an oil dash-pot. A piston, attached to the moving iron plunger, is immersed in oil in a dash-pot. When the solenoid relay is actuated, the piston moves upwards along with iron plunger.

Viscosity of oil slows the upward movement of plunger. The speed of this upward movement against gravity also depends upon how strongly the solenoid attracts the iron plunger. This attraction force of the solenoid depends upon the magnitude of actuating current. Hence, time of operation of relay is inversely proportional to actuating current.

Definite Time Lag Relay

During relay coordination in electrical power system protection scheme, there is some time intentionally required, to operate some specific relays after some specific time delays. Definite time lag relays are those which operate after a specific time.
The time lag between instant when the actuating current crosses the pickup level and the instant when relay contacts finally closed, is constant. This delay does not depend up on magnitude of actuating quantity. For all actuating quantity, above pick up values, the relay operating time is constant.

Statement: Respect the original, good articles worth sharing, if there is infringement please contact delete.

Give a tip and encourage the author!
Recommended
Transmission Line
In transmission lines, a "π" connection involves breaking the original line from Substation A to Substation B and inserting Substation C, forming a "π" configuration. After the "π" connection, the original single line is divided into two independent transmission lines. Following the "π" connection, Substations B and C may both be powered by Substation A (in this case, Substation C receives power via a feeder from Substation B's busbar, or possibly from another voltage point within Substation B);
Encyclopedia
09/04/2025
What are the principles of forced re-energization of transmission lines?
Principles of Forced Re-energization of Transmission LinesRegulations for Forced Re-energization of Transmission Lines Correctly select the forced re-energization end of the line. If necessary, change the connection configuration before forced re-energization, taking into account the reduction of short-circuit capacity and its impact on grid stability. There must be a transformer with its neutral point directly grounded on the busbar at the forced re-energization end. Pay attention to the impact
Edwiin
09/04/2025
Analysis of Accident Handling in Transmission Lines
Analysis of Transmission Line Fault HandlingAs a fundamental component of the power grid, transmission lines are widely distributed and numerous, often exposed to diverse geographical and climatic conditions, making them highly susceptible to faults. Common causes include overvoltage, pollution flashover, insulation damage, tree encroachment, and external damage. Line tripping is one of the most frequent faults in power plant and substation operations, with fault types including single-phase-to-
Leon
09/04/2025
The difference between transmission and distribution lines
Transmission lines and distribution lines are both used to carry electrical power from one location to another. However, they differ significantly in key aspects such as primary function, voltage levels, phase configuration, and conductor placement. These differences are essential for understanding their distinct roles in the power system.The Difference Between Transmission and Distribution Line is given below in the tabulated form.Electricity generation is a critical component of the power syst
Edwiin
09/04/2025
Related Products
  • KW-1 Series simulation rain - shower tester
  • IPXX Series Ingress Protection professional testing tool
Seed Inquiry
Download
Get the IEE Business Application
Use the IEE-Business app to find equipment, obtain solutions, connect with experts, and participate in industry collaboration anytime, anywhere—fully supporting the development of your power projects and business.