• Product
  • Suppliers
  • Manufacturers
  • Solutions
  • Free tools
  • Knowledges
  • Experts
  • Communities
Search


Understanding Transformer Connection Designations: Types, Symbols, and Applications

Encyclopedia
Encyclopedia
Field: Encyclopedia
0
China

Transformer Connection Designations

The transformer connection designation indicates the winding connection method and the phase relationship between the line voltages of the primary and secondary windings. It consists of two parts: letters and a number. The letters on the left denote the connection configurations of the high-voltage and low-voltage windings, while the number on the right is an integer from 0 to 11.

This number represents the phase shift of the low-voltage winding's line voltage relative to that of the high-voltage winding. Multiplying the number by 30° yields the phase angle by which the secondary voltage lags the primary voltage. This phase relationship is commonly illustrated using the "clock method," where the primary line voltage vector is represented as the minute hand fixed at the 12 o'clock position, and the corresponding secondary line voltage vector acts as the hour hand, pointing to the hour indicated by the number in the designation.

Representation Method

In transformer connection designations:

  • "Yn" denotes a star (Y) connection on the primary side with a neutral conductor (n).

  • "d" indicates a delta (Δ) connection on the secondary side.

  • The number "11" means that the secondary line voltage UAB lags the primary line voltage UAB by 330° (or leads by 30°).

Uppercase letters represent the connection type of the primary (high-voltage) winding, while lowercase letters represent the secondary (low-voltage) winding. "Y" or "y" stands for a star (wye) connection, and "D" or "d" for a delta (triangle) connection. The number, based on the clock method, indicates the phase displacement between the primary and secondary line voltages. The primary line voltage vector is taken as the minute hand fixed at 12 o'clock, and the secondary line voltage vector as the hour hand, pointing to the corresponding hour.

Transformer.jpg

For example, in "Yn, d11," the "11" signifies that when the primary line voltage vector points to 12 o'clock, the secondary line voltage vector points to 11 o'clock—indicating a 330° lag (or 30° lead) of the secondary UAB relative to the primary UAB.

Basic Connection Types

There are four fundamental transformer connection configurations: "Y, y," "D, y," "Y, d," and "D, d." In star (Y) connections, two variants exist: with or without a neutral. The absence of a neutral is not specially marked, whereas the presence of a neutral is denoted by adding "n" after "Y."

Clock Method

In the clock representation, the high-voltage winding’s line voltage vector is treated as the long hand (minute hand), always fixed at the 12 o'clock position. The low-voltage winding’s line voltage vector is treated as the short hand (hour hand), pointing to the hour that corresponds to the phase displacement.

Application of Standard Designations

  • Yyn0: Used in three-phase power transformers within three-phase four-wire distribution systems, supplying combined power and lighting loads.

  • Yd11: Applied in three-phase power transformers for low-voltage systems above 0.4 kV.

  • YNd11: Employed in high-voltage systems above 110 kV where the neutral point of the primary winding must be grounded.

  • YNy0: Used in systems where the primary winding requires grounding.

  • Yy0: Utilized in three-phase power transformers dedicated to three-phase power loads.

Give a tip and encourage the author!
Recommended
What causes a transformer to be noisier under no-load conditions?
What causes a transformer to be noisier under no-load conditions?
When a transformer is operating under no-load conditions, it often produces louder noise than under full load. The primary reason is that, with no load on the secondary winding, the primary voltage tends to be slightly higher than nominal. For example, while the rated voltage is typically 10 kV, the actual no-load voltage may reach around 10.5 kV.This elevated voltage increases the magnetic flux density (B) in the core. According to the formula:B = 45 × Et / S(where Et is the designed volts-per-
Noah
11/05/2025
Under what circumstances should an arc suppression coil be taken out of service when it is installed?
Under what circumstances should an arc suppression coil be taken out of service when it is installed?
When installing an arc suppression coil, it is important to identify the conditions under which the coil should be taken out of service. The arc suppression coil should be disconnected under the following circumstances: When a transformer is being de-energized, the neutral-point disconnector must be opened first before performing any switching operations on the transformer. The energizing sequence is the reverse: the neutral-point disconnector should be closed only after the transformer is energ
Echo
11/05/2025
What fire prevention measures are available for power transformer failures?
What fire prevention measures are available for power transformer failures?
Failures in power transformers are commonly caused by severe overload operation, short circuits due to winding insulation degradation, aging of transformer oil, excessive contact resistance at connections or tap changers, failure of high- or low-voltage fuses to operate during external short circuits, core damage, internal arcing in oil, and lightning strikes.Since transformers are filled with insulating oil, fires can have severe consequences—ranging from oil spraying and ignition to, in extrem
Noah
11/05/2025
What are the common faults encountered during the operation of power transformer longitudinal differential protection?
What are the common faults encountered during the operation of power transformer longitudinal differential protection?
Transformer Longitudinal Differential Protection: Common Issues and SolutionsTransformer longitudinal differential protection is the most complex among all component differential protections. Misoperations occasionally occur during operation. According to 1997 statistics from the North China Power Grid for transformers rated 220 kV and above, there were 18 incorrect operations in total, of which 5 were due to longitudinal differential protection—accounting for approximately one-third. Causes of
Felix Spark
11/05/2025
Related Products
Send inquiry
Download
Get the IEE Business Application
Use the IEE-Business app to find equipment, obtain solutions, connect with experts, and participate in industry collaboration anytime, anywhere—fully supporting the development of your power projects and business.