Rankine Cycle: What is it? (Ideal vs. Actual + T-s Diagram)

Electrical4u
Electrical4u
Field: Basic Electrical
0
China

What Is Rankine Cycle

What is the Rankine Cycle?

The Rankine Cycle is a mechanical cycle commonly used in power plants to convert the pressure energy of steam into mechanical energy through steam turbines. The Rankine Cycle’s major components include a rotating steam turbine, a boiler pump, a stationary condenser, and a boiler.

A boiler is used to heat the water for steam at the required pressure and temperature as per the turbine’s requirement for power generation.

The turbine exhaust is directed to the radial or axial flow condenser for condensing the steam to condensate and recycled back to the boiler through boiler pumps for heating again.

This might make more sense if we take a step back, and understand what a typical power plant cycle looks like.

Typical Power Plant Cycle

Electrical power is generated by using vapor cycle power plants by using Coal, Lignite, Diesel, Heavy furnace oil as a fuel depending upon the availability and cost. The flow scheme of the vapor power cycle is given below:
rankine cycle
The entire power plant can be broken down into the following sub-systems.

  • Sub-system A: Classified as the main-components of power plant (Turbine, Condenser, Pump, Boiler) for power generation.

  • Sub-system B: Classified as the stack/chimney, from where the waste gases are exhausted to the atmosphere.

  • Sub-system C: Classified as an electric generator for converting mechanical energy to electrical energy.

  • Sub-system D: Classified as the cooling water system for absorbing the heat of the rejected steam in the condenser and changing the steam phase to liquid (condensate).

We will be analyzing the sub-system within this power plant cycle which deals with the Rankine cycle.

Many of the practical limitations related to the Carnot cycle can be conveniently overcome in the Rankine cycle.

Ideal Rankine Cycle

In a vapor cycle, if the working fluid in a vapor cycle passes through various components of the power plant without irreversibility and frictional pressure drop, then the cycle is called an Ideal Rankine Cycle.

The Rankine cycle is the basic operating cycle for all power plants where a working fluid is continuously changing its phase from liquid to vapor and vice-versa.

rankine cycle

The (p-h) and (T-s) diagrams are useful in understanding the working of the Rankine cycle along with the description given below:


1-2-3 Isobaric Heat Transfer or Constant pressure heat addition in a boiler

The boiler is a large heat exchanger where heat liberating fuel like coal, lignite, or oil transfers the heat indirectly to water at constant pressure. Water enters the steam boiler from the boiler feed pump as a compressed liquid at state-1 and is heated to the saturation temperature as shown in the T-s diagram as state-3.

The energy balance in the boiler is or energy added in a steam generator,
qin= h3-h1

3-4 Isentropic Expansion or Isentropic expansion in a turbine

Vapor from the boiler outlet enters the turbine at state 3, where it expands isentropically over the turbine fixed and moving blade to produce work done in the form of mechanical rotation of the turbine shaft, which is connected to the electrical generator.
Work delivered by the turbine (Neglecting heat transfer with the surroundings)
Wturbine out= h3-h4

4-5 Isobaric Heat Rejection or Constant pressure heat rejection in a condenser

At state-4, vapor enters the condenser. The change of phase occurs as vapor is condensed to liquid at constant-pressure in the condenser by transferring the steam’s heat to the circulating water flow through the tubes of the condenser. Change of phase occurs in the condenser, and the working fluid leaving the condenser is in a liquid state and marked as point 5.
Energy rejected in the condenser, qout= h4-h5

5-1 Isentropic Compression or Isentropic compression in a pump

Water exits the condenser at state 5 and enters the pump. This pump raises the pressure of the water by imparting work during the processes. In units of smaller size and low specific volume, this small work can be neglected compared to the work-output of a steam turbine.
Work was done on the pump per kg of water, W51= h5-h1.

The thermal efficiency of the Rankine cycle is given by:


OR

Difference Between Ideal and Actual Rankine Cycle

The efficiency of the ideal Rankine cycle is close to the efficiency of the Carnot Cycle.

But in real plants, each stage of the Rankine cycle is associated with some irreversible processes. Thus the efficiency of the actual Rankine cycle is far lower than the ideal Rankine cycle efficiency.

Given below Fig. 1-a and Fig 1-b represents the Rankine cycle on P-v and T-s diagram
ideal verses actual in rankine cycle v vs p and s vs t

Rankine Cycle Representation is as follows on P-v and T-s diagrams:


Ideal Rankine Cycle

1-2-b-3-4-1

Actual Rankine Cycle

1-2-b-3-4-1


Critical Point (CP) is in the curve’s center, as shown in Fig 1-a and 1-b above. The curved lines on the left side of the CP are saturated-liquid lines, and the region/area to the left of these lines are called sub-cooled liquid regions.

Similarly, curved lines on the right side of the CP are saturated- vapor lines and the region/area to the right of these lines are called super-heat vapor regions.

Energy Analysis of Ideal Rankine Cycle

All Rankine cycle components (boiler, turbine, condenser, and pump) are examples of a steady flow process and analyzed accordingly. The energy balance for the Ideal cycle is as follows:

Ideal Rankine Cycle Components

Heat

Work

Boiler feed Pump Wpump-in

Boiler

Turbine

Condenser

Thermal efficiency of Ideal Rankine cycle

Energy Analysis of Actual Rankine Cycle

The actual vapor cycle differs from the ideal Rankine Cycle as a result of irreversibility in various components. Two major factors of irreversibility are Fluid friction and heat loss.

Fluid Friction

It causes a major pressure drop in the boiler circuitry, the condenser, and the low-pressure piping circuit. Because of the fluid friction pressure drop in the boiler circuitry, the steam’s pressure leaving the boiler will be somewhat lower.

The steam has to be conveyed to the steam turbine via steam piping which also accounts for further pressure drop.

The steam that reaches the turbine stop valve will be at a lower pressure than that of the boiler discharge pressure, and the same is represented by 3’ (Fig-1a) in the actual Rankine Cycle instead of 3 in the Ideal Rankine Cycle.

If we don’t want to compromise on the turbine output, then we must compensate for the pressure drop/loss and restore the turbine inlet pressure to point 3 in Fig 1-a by increasing the boiler pump pressure sufficiently higher to compensate the losses/drop and in the process increasing the size of the pump and the requirement of input power.

The other reason for irreversibility is the loss of steam in steam in its transportation and malfunctioning of the steam traps.

Thus, to compensate for these losses, we need to generate more steam and that too much pressure for the desired rated power generation from the turbine, thus lowering the cycle efficiency.

Energy balance for the actual Rankine Cycle is as follows:

Actual Rankine Cycle Components

Heat

Work

Boiler feed Pump Wpump-in

Boiler

Turbine

Condenser

Thermal efficiency of Ideal Rankine cycle

While calculating the overall cycle efficiency, Turbine and pump irreversibilities need to be given due importance. For small units, usually pump work is negligible and can be neglected, but in larger units, pump work is appreciable and can’t be neglected like that.

Actual/Practical Rankine cycle is based on the deviation of flow in turbine and pressure requirement in the pump from the isentropic one and is defined as follows:

Where:

  • h2a Actual enthalpy at the pump exit

  • h4a Actual enthalpy at the turbine exit

  • h2s Ideal isentropic enthalpy at the pump exit

  • h4s Ideal isentropic enthalpy at the turbine exit

Other Factors of Irreversibility

Other factors responsible for the irreversibility of the actual vapor power cycle are:

  • Sub-cooling of condensate in the condenser

  • Losses associated with bearings

  • Steam leakages

  • Condenser air-leaks

Statement: Respect the original, good articles worth sharing, if there is infringement please contact delete.

Give a tip and encourage the author!
Recommended
THD Measurement Error Standards for Power Systems
THD Measurement Error Standards for Power Systems
Error Tolerance of Total Harmonic Distortion (THD): A Comprehensive Analysis Based on Application Scenarios, Equipment Accuracy, and Industry StandardsThe acceptable error range for Total Harmonic Distortion (THD) must be evaluated based on specific application contexts, measurement equipment accuracy, and applicable industry standards. Below is a detailed analysis of key performance indicators in power systems, industrial equipment, and general measurement applications.1. Harmonic Error Standar
Edwiin
11/03/2025
Busbar-Side Grounding for 24kV Eco-Friendly RMUs: Why & How
Busbar-Side Grounding for 24kV Eco-Friendly RMUs: Why & How
Solid insulation assistance combined with dry air insulation is a development direction for 24 kV ring main units. By balancing insulation performance and compactness, the use of solid auxiliary insulation allows passing insulation tests without significantly increasing phase-to-phase or phase-to-ground dimensions. Encapsulation of the pole can address the insulation of the vacuum interrupter and its connected conductors.For the 24 kV outgoing busbar, with the phase spacing maintained at 110 mm,
Dyson
11/03/2025
How Vacuum Tech Replaces SF6 in Modern Ring Main Units
How Vacuum Tech Replaces SF6 in Modern Ring Main Units
Ring main units (RMUs) are used in secondary power distribution, directly connecting to end-users such as residential communities, construction sites, commercial buildings, highways, etc.In a residential substation, the RMU introduces 12 kV medium voltage, which is then stepped down to 380 V low voltage through transformers. The low-voltage switchgear distributes electrical energy to various user units. For a 1250 kVA distribution transformer in a residential community, the medium-voltage ring m
James
11/03/2025
What Is THD? How It Affects Power Quality & Equipment
What Is THD? How It Affects Power Quality & Equipment
In the field of electrical engineering, the stability and reliability of power systems are of paramount importance. With the advancement of power electronics technology, the widespread use of nonlinear loads has led to an increasingly serious problem of harmonic distortion in power systems.Definition of THDTotal Harmonic Distortion (THD) is defined as the ratio of the root mean square (RMS) value of all harmonic components to the RMS value of the fundamental component in a periodic signal. It is
Encyclopedia
11/01/2025
Send inquiry
Download
Get the IEE Business Application
Use the IEE-Business app to find equipment, obtain solutions, connect with experts, and participate in industry collaboration anytime, anywhere—fully supporting the development of your power projects and business.