• Product
  • Suppliers
  • Manufacturers
  • Solutions
  • Free tools
  • Knowledges
  • Experts
  • Communities
Search


What are the advantages of using a common grounding system in power distribution, and what precautions should be taken?

Echo
Echo
Field: Transformer Analysis
China

What Is Common Grounding?

Common grounding refers to the practice where a system’s functional (working) grounding, equipment protective grounding, and lightning protection grounding share a single grounding electrode system. Alternatively, it may mean that grounding conductors from multiple electrical devices are connected together and linked to one or more common grounding electrodes.


1. Advantages of Common Grounding

  • Simpler system with fewer grounding conductors, making maintenance and inspection easier.

  • The equivalent grounding resistance of multiple grounding electrodes connected in parallel is lower than the total resistance of separate, independent grounding systems. When the building’s structural steel or rebar is used as the common grounding electrode—due to its inherently low resistance—the benefits of common grounding become even more pronounced.

  • Enhanced reliability: if one grounding electrode fails, others can compensate.

  • Reduced number of grounding electrodes, lowering installation and material costs.

  • In the event of an insulation failure causing a phase-to-chassis short circuit, a larger fault current flows, ensuring protective devices operate quickly. This also reduces touch voltage when personnel contact faulty equipment.

  • Mitigates hazards from lightning overvoltages.

Theoretically, to prevent lightning-induced back-flashover, lightning protection grounding should be kept at a safe distance from building structures, electrical equipment, and their grounding systems. However, in real-world engineering, this is often impractical. Buildings typically have numerous incoming utility lines (power, data, water, etc.) spread over wide areas. Especially when reinforced concrete structural rebars are used as concealed lightning protection conductors, it becomes virtually impossible to electrically isolate the lightning protection system from building piping, equipment enclosures, or power system grounding.

In such cases, common grounding is recommended—connecting the transformer neutral, all functional and protective grounds of electrical equipment, and the lightning protection system to the same grounding electrode network. For example, in high-rise buildings, integrating electrical grounding with the lightning protection system effectively forms a Faraday cage using the building’s internal steel framework. All internal electrical equipment and conductors bonded to this cage are thereby protected from lightning-induced potential differences and back-flashover.

Therefore, when utilizing a building’s metallic structure for grounding, common grounding for multiple systems is not only feasible but advantageous, provided the overall grounding resistance is maintained below 1 Ω.


2. Key Considerations for Common Grounding

Nature of grounding currents:
The risk associated with ground potential rise (GPR) depends on the magnitude, duration, and frequency of grounding currents. For instance, lightning arresters or rods may carry very high currents during a strike, but these events are brief and infrequent—so the resulting GPR poses limited risk.

However, the common grounding resistance must satisfy the most stringent requirement among all connected systems, ideally ≤1 Ω.

In low-voltage distribution systems with solidly grounded neutrals, the common grounding electrode may carry continuous leakage currents from all connected loads, forming circulating ground currents. If the grounding resistance drifts above safe limits, it can endanger both equipment and personnel.

Moreover, with the widespread use of computers and sensitive electronic equipment, filter grounding is often required. Large line-to-ground EMI/RFI filters introduce significant capacitive leakage currents to earth, which also contribute to the total ground current.

Impact of ground potential rise on connected equipment:
Consider an indoor compact substation unit as an example. Traditionally, the transformer neutral, metal enclosure, and load equipment chassis were all connected to a common ground. Meanwhile, lightning arresters were often given a separate ground to avoid dangerous potential rise during discharge.

However, if a load device develops an insulation fault and leaks current, the entire fault loop current flows through the common grounding electrode, raising the local ground potential—and consequently, the enclosure voltage of the switchgear. If maintenance personnel open the cabinet door under these conditions, they risk electric shock. Such incidents have occurred repeatedly.

As a result, modern practice often isolates functional grounding (e.g., transformer neutral) from protective and lightning grounding in indoor substations—even though this increases installation complexity.


3. Relevant Standards and Regulations (China)

  • According to current Chinese power industry standards:

    • For Class B electrical installations, if the supplying distribution transformer is not located within a building containing Class B equipment, and its high-voltage side operates in an ungrounded, Petersen coil (arc-suppression coil)-grounded, or high-resistance grounded system, then the low-voltage system’s working ground may share the same grounding electrode as the transformer’s protective ground, provided the grounding resistance satisfies R ≤ 50/I (Ω) and R ≤ 4 Ω.

    • For Class A electrical installations operating in effectively grounded systems, the transformer’s working ground must be located outside the protective grounding grid—i.e., common grounding is not permitted.

  • If the distribution transformer is installed inside a building with Class B electrical installations, and its high-voltage side uses low-resistance grounding, then the low-voltage working ground may share the protective ground if:

    • Grounding resistance meets R ≤ 2000/I (Ω), and

    • The building implements a main equipotential bonding (MEB) system.

  • Additionally, for systems above 1 kV classified as large grounding short-circuit current systems, common grounding is permissible if rapid fault clearance is ensured, but the grounding resistance must be < 1 Ω.

  • Protective grounding of distribution transformers in Class A installations may share the same grounding electrode as the associated lightning arrester grounding.


4. Conclusion

Practical experience shows that in public low-voltage distribution systems, where complete separation of grounding systems is often unachievable, common grounding—combining working, protective, and lightning grounding—is safer, more economical, simpler to install, and easier to maintain.

To mitigate potential risks of common grounding, engineers should:

  • Fully utilize the building’s structural steel as a natural grounding electrode,

  • Maintain total grounding resistance below 1 Ω, and

  • Implement comprehensive equipotential bonding throughout the facility.

These measures effectively minimize hazards and ensure safe, reliable operation of modern electrical installations.

Give a tip and encourage the author!
Recommended
Causes of Failure in Off-Circuit (De-energized) Tap Changers
Causes of Failure in Off-Circuit (De-energized) Tap Changers
I. Faults in Off-Circuit (De-energized) Tap Changers1. Causes of Failure Insufficient spring pressure on tap changer contacts, uneven roller pressure reducing effective contact area, or inadequate mechanical strength of the silver-plated layer leading to severe wear—ultimately burning out the tap changer during operation. Poor contact at tap positions, or poor connections/welding of leads, unable to withstand short-circuit current surges. Incorrect tap position selection during switching, causin
Felix Spark
11/05/2025
What causes a transformer to be noisier under no-load conditions?
What causes a transformer to be noisier under no-load conditions?
When a transformer is operating under no-load conditions, it often produces louder noise than under full load. The primary reason is that, with no load on the secondary winding, the primary voltage tends to be slightly higher than nominal. For example, while the rated voltage is typically 10 kV, the actual no-load voltage may reach around 10.5 kV.This elevated voltage increases the magnetic flux density (B) in the core. According to the formula:B = 45 × Et / S(where Et is the designed volts-per-
Noah
11/05/2025
Under what circumstances should an arc suppression coil be taken out of service when it is installed?
Under what circumstances should an arc suppression coil be taken out of service when it is installed?
When installing an arc suppression coil, it is important to identify the conditions under which the coil should be taken out of service. The arc suppression coil should be disconnected under the following circumstances: When a transformer is being de-energized, the neutral-point disconnector must be opened first before performing any switching operations on the transformer. The energizing sequence is the reverse: the neutral-point disconnector should be closed only after the transformer is energ
Echo
11/05/2025
What fire prevention measures are available for power transformer failures?
What fire prevention measures are available for power transformer failures?
Failures in power transformers are commonly caused by severe overload operation, short circuits due to winding insulation degradation, aging of transformer oil, excessive contact resistance at connections or tap changers, failure of high- or low-voltage fuses to operate during external short circuits, core damage, internal arcing in oil, and lightning strikes.Since transformers are filled with insulating oil, fires can have severe consequences—ranging from oil spraying and ignition to, in extrem
Noah
11/05/2025
Related Products
Send inquiry
Download
Get the IEE Business Application
Use the IEE-Business app to find equipment, obtain solutions, connect with experts, and participate in industry collaboration anytime, anywhere—fully supporting the development of your power projects and business.