| Item |
Neutral Grounding Resistor (NGR) |
Neutral Grounding Reactor (NER) |
| Grounding Component |
Resistor R connected in series at neutral point |
Inductor L connected in series at neutral point |
| Single-phase Earth Fault Current |
Limited to tens to hundreds of amperes (value can be precisely set)
Controllable |
Determined by system capacitive current and reactor compensation degree
Difficult to control accurately |
| Overvoltage Suppression |
Resistive component dissipates energy, arcs are easy to extinguish
Excellent performance in suppressing arc overvoltage |
Pure inductive characteristic, compensates capacitive current; resonance overvoltage will occur under detuning condition
Risk of resonance |
| Fault Feeder Selection & Protection |
Large zero-sequence current, sensitive protection and reliable fault feeder detection
Easy to implement |
Small residual current, difficult fault feeder identification; dedicated fault detection equipment is required
High implementation difficulty |
| Operation with Persistent Fault |
Relatively large earth fault current, generally requires rapid fault clearance
Short allowable fault duration |
Low residual current; short-term earth fault operation is theoretically permitted (arc suppression coil mode)
Short-time fault operation supported |
| Equipment Damage |
Resistor heats up during faults, design must comply with short-time withstand current
Resistor thermal rise needs verification |
Low fault current leads to mild thermal stress on equipment
Low thermal load |
| Adjustment Difficulty |
Fixed resistor type is simple and reliable; additional mechanical structure is required for variable resistors |
Arc suppression coil needs tap switching according to variation of system capacitive current (automatic tuning)
Dynamic tuning is mandatory |
| Typical Application Scenarios |
Industrial power distribution (6~35 kV), offshore platforms, mines, data centers, and scenarios requiring fast protection response |
Urban medium-voltage power grids (large capacitive current), rural overhead lines (continuous power supply required under faults) |
| National & Industry Standards |
GB/T 14285, DL/T 620 |
GB/T 14285, DL/T 620 (for arc suppression coil grounding) |