High-Breaking-Capacity Fuse | Fast Short-Circuit Protection

James
James
Field: Electrical Operations
China

In the power plants and substations of various voltage levels that we operate and maintain, high-voltage current-limiting fuses are widely used, primarily for protecting voltage transformers, small transformers, and small high-voltage motors. So why are they called high-breaking-capacity fuses? And why can't ordinary fuses be used? Today, let's learn about this topic together.

High-breaking-capacity fuses, also known as high-voltage current-limiting fuses, differ from ordinary fuses in two main aspects: First, they have a strong capability to interrupt short-circuit currents—this is where the name "high-breaking-capacity" comes from. Second, they have a significant current-limiting effect. This means that when a short circuit occurs in the protected circuit, the fuse can reliably interrupt the circuit before the short-circuit current reaches its peak value. This is the so-called current-limiting effect.

In simple and plain terms, the first characteristic is reliability: ordinary fuses are like switch blades and cannot interrupt short-circuit currents, whereas high-breaking-capacity fuses are like circuit breakers, capable of reliably interrupting short-circuit currents. The second characteristic is speed: they can quickly clear short-circuit faults before the short-circuit current fully develops, and they do so without causing the fuse itself to explode.

Structurally, high-voltage current-limiting fuses are generally cylindrical, with a hard ceramic outer shell and a seven-point column (or star-shaped) frame inside to secure the fuse element. For lower rated currents, the fuse element is typically wire-shaped, while for higher rated currents, it is usually ribbon-shaped.

The ribbon-shaped element has evenly spaced notches cut in a sawtooth pattern. The spacing and shape of these notches determine the performance parameters of the fuse. The interior is filled with quartz sand to extinguish the arc generated when the fuse element melts. Additionally, some models are equipped with striker indicators. When the fuse element blows, the indicator pops out, triggering an external position switch to send an alarm, alerting operation and maintenance personnel.

Regarding the model designation of high-voltage current-limiting fuses, let's take XRNP-12/0.5-50, used for voltage transformers, as an example. The meanings of each part are as follows:

  • X stands for current-limiting type

  • R stands for fuse

  • N stands for indoor use

  • P stands for use with voltage transformers

  • 12 indicates the voltage rating of 12 kV

  • 0.5 indicates the rated current of the fuse element is 0.5 A

  • 50 indicates the maximum short-circuit breaking capacity is 50 kA

The fifth letter code indicates the protected object:

  • P for protecting voltage transformers

  • M for protecting motors

  • T for protecting transformers

  • C for protecting capacitors

  • G for protecting specified objects

Give a tip and encourage the author!
Recommended
How to select a dry-type transformer?
How to select a dry-type transformer?
1. Temperature Control SystemOne of the main causes of transformer failure is insulation damage, and the greatest threat to insulation comes from exceeding the allowable temperature limit of the windings. Therefore, monitoring temperature and implementing alarm systems for transformers in operation are essential. The following introduces the temperature control system using the TTC-300 as an example.1.1 Automatic Cooling FansA thermistor is pre-embedded at the hottest spot of the low-voltage win
James
10/18/2025
How to Choose the Right Transformer?
How to Choose the Right Transformer?
Transformer Selection and Configuration Standards1. Importance of Transformer Selection and ConfigurationTransformers play a critical role in power systems. They adjust voltage levels to suit different requirements, enabling electricity generated at power plants to be efficiently transmitted and distributed. Improper transformer selection or configuration can lead to serious issues. For example, if the capacity is too small, the transformer may not support the connected load, causing voltage dro
James
10/18/2025
How to Choose Vacuum Circuit Breakers Correctly?
How to Choose Vacuum Circuit Breakers Correctly?
01 PrefaceIn medium-voltage systems, circuit breakers are indispensable primary components. Vacuum circuit breakers dominate the domestic market. Therefore, correct electrical design is inseparable from the proper selection of vacuum circuit breakers. In this section, we will discuss how to correctly select vacuum circuit breakers and common misconceptions in their selection.02 Interrupting Capacity for Short-Circuit Current Need Not Be Excessively HighThe short-circuit interrupting capacity of
James
10/18/2025
Vacuum vs Air Circuit Breakers: Key Differences
Vacuum vs Air Circuit Breakers: Key Differences
Low-Voltage Air Circuit Breakers vs. Vacuum Circuit Breakers: Structure, Performance and ApplicationLow-voltage air circuit breakers, also known as universal or molded frame circuit breakers (MCCBs), are designed for AC voltages of 380/690V and DC voltages up to 1500V, with rated currents ranging from 400A to 6300A or even 7500A. These breakers use air as the arc-quenching medium. The arc is extinguished through arc elongation, splitting, and cooling by an arc chute (arc runner). Such breakers c
Garca
10/18/2025
Send inquiry
Download
Get the IEE Business Application
Use the IEE-Business app to find equipment, obtain solutions, connect with experts, and participate in industry collaboration anytime, anywhere—fully supporting the development of your power projects and business.