• Product
  • Suppliers
  • Manufacturers
  • Solutions
  • Free tools
  • Knowledges
  • Experts
  • Communities
Search


Koyarwa na Istruksiyan don Ingantaccen Aiki na Wadannan 50kA Current-Limiting Devices a Bore da Yawancin Kerosene

Echo
Echo
فیلڈ: Takardarwa na Tansufurza
China

1. Karamin Da System Ta A Cikin Da Ba A Cikin CLiP (Current-Limiting Device)

A kananan yadda da aka yi aiki, switchboard ya yi aiki haka:

  • Duk bus tie breakers suna fi saki, wanda ya sama shi duka uku na bus sections;
  • Biyu na generators suna cika a kan system kuma sun tattara zama ta switchboard.

A cikin wannan gyaran, da ba a iya da shi fault current ta switchboard ita ce mafi tsawo 50kA. Saboda haka, current-limiting device (CLiP) ba a ji a cikin circuit ba.

A lokacin da ake yi aiki mai gaba-gaban da ke sauya wata generator (wanda ake karfin ta), kuma ake magana da wata (wanda ake synchronize da kuma ake magana ta), system ya yi aiki haka:

  • Duk bus tie breakers suna fi saki, wanda ya sama shi duka uku na bus sections;
  • Uku na generators suna cika a kan system daɗinsu (a lokacin da ake yi generator changeover).

A cikin wannan alamun, short-circuit capacity ta system ya zama mafi, kuma da ba a iya da shi fault current ya yi fadada 50kA. Saboda short-circuit withstand rating ta switchboard ita ce 50kA, current-limiting device ya kamata a ji a cikin circuit don tabbatar da dalilin aiki.

CLiP ya yi nuna rate da current ya ƙarewa a lokacin. Idan current ya yi fadada ma'ana an bayar, device ya faru kuma ya koye bus connection ta hanyar melten internal fuse element. Wannan ya ƙarewa actual fault current a kan mafi tsawo 50kA, wanda ya bincike a cikin safe design limits ta switchboard.

Wannan prosesin ya ba da abin da take isole fault without causing a blackout of the entire eHouse power distribution system.

Marya:

  • Idan da ba a iya da shi fault current > 50kA (all bus ties closed and three generators online), CLiP must be in the circuit. Wannan halin yana faru kawai a lokacin da ake yi single-generator maintenance.
  • Idan da ba a iya da shi fault current < 50kA (only two generators online or two of the three bus ties open), CLiP should be disconnected from the circuit.

2. Operation and Maintenance Requirements

Owner ta facility ya kamata ake amfani da proposed alternative operating arrangements. Farkon da za su iya haɗa suna da data masu inganci game da current-limiting fuse, including maintenance requirements, estimated service life, and the capability of personnel performing equipment maintenance. Duk waɗannan ayyukan za su buɗe a cikin operation and maintenance manual.

3. Design and Testing of the Current-Limiting Fuse

Current-limiting fuse ya kamata a yi aiki da testing according to recognized standards such as IEC 60282-1:2009/2014 and IEEE C37.41 series, and shall be suitable for the intended application and environmental/operational conditions. Only a single current-limiting fuse shall be used; any combination of current-limiting devices requires special consideration and evaluation.

CLiP has obtained KEMA type test reports covering breaking capacity, temperature rise, and insulation tests, along with calibration records for measuring equipment. Testing has been performed in compliance with IEC 60282 and ANSI/IEEE C37.40 series standards.

4. Insulation Level of the Fuse Holder

  • The fuse holder has a rated impulse withstand voltage of 110kV BIL;
  • The isolation transformer has passed a 150kV BIL test and can be used in 27kV-class systems;
  • Each isolation transformer undergoes a 50kV AC dielectric test during production.

5. Verification of Fuse Suitability for Operating Temperature

The current-limiting fuse has been manufactured and tested in accordance with IEC 60282-1 or IEEE C37.41 series standards.

IEC 60282-1 specifies a maximum ambient temperature of 40°C, while the classification society standard SVR 4-1-1, Table 8, requires 45°C. Evidence compliant with Appendix E of IEC 60282-1 (or equivalent standards) must be provided to demonstrate that the fuse is suitable for the maximum expected ambient temperature of 45°C.

Testing covers the requirements of IEC 60282-1 and ANSI/IEEE C37.41. The Series II interruption test is more stringent than IEC requirements, as it demands 100% test voltage (IEC allows 87%). G&W tests Series I duties at 100% voltage and 100% current—exceeding all standard requirements. The actual project uses a 4000A rated device.

For a 5000A switchgear without forced cooling, the temperature rise margin is 5K at 40°C ambient, enabling it to carry 5000A at 40°C and 4000A at 50°C ambient.

6. Time-Current Characteristics and Current-Limiting Performance

This type of device does not have a conventional time-current curve (TCC). Its operation is completed within 0.01 seconds—well before the starting point of typical TCC curves—effectively making it an instantaneous device.

In practice, each application is evaluated on a case-by-case basis, using worst-case scenarios (fully asymmetrical faults). System currents are plotted with appropriate time resolution to clearly illustrate all interactions. This approach is superior to the potentially misleading use of peak let-through current curves.

7. Peak Overvoltage and Power Dissipation During High Fault Current Operation

  • According to IEC and ANSI/IEEE requirements for 15.5kV-rated equipment, the peak voltage during operation (maximum measured 47.1kV) remains within the 49kV range, and does not involve the release of large amounts of heat or steam associated with expulsion-type interruption.

  • The CLiP's heat dissipation structure is essentially a busbar with machined current-limiting sections.

  • The total heat dissipation of a three-phase CLiP system at 4000A is approximately 500W.

8. Short-Circuit Study and Validation of Cascading Protection

The short-circuit study shall demonstrate the function of the current-limiting device and how it reduces the symmetrical fault current below the switchboard’s rated withstand level. If the proposed arrangement is intended to operate as "cascaded protection," compliance with the conditions specified in classification society standard SVR 4-8-2 / 9.3.6 must be verified. The selection of the triggering point and determination of let-through current in each direction shall be clearly defined.

9. Calculation of Busbar Withstand Capability for Maximum Short-Circuit Current

Calculations shall be performed in accordance with IEC standards to verify the busbar’s ability to withstand the mechanical and thermal effects caused by the maximum prospective short-circuit current.

Ba da kyau kuma kara mai rubutu!
Tambayar Da Yawanci
3D Wound-Core Transformer: Tarihin Ayyuka na Iyakokin Kirkiro Rike
3D Wound-Core Transformer: Tarihin Ayyuka na Iyakokin Kirkiro Rike
Muhimmanci Bincike da Turukanin Nuna na Masu Farko Kasance kadan, musamman kasance kadan da ba a kan wani abu; yana nuna aiki a cikin inganci. Kasance kwaikwayo, musamman a lokacin da ya fi sani; don in tabbatar da masu shirya tattalin arziki. Talakawa mai karfi don in hada zafi na masu kasa zuwa gaba, wanda ke samun aiki a cikin karfin baka. Masu alama a cikin takar, wanda ke samu aiki a cikin hanyar kudan; ya kawo muhimmanci a kan tsarin masu kasa don in yi amfani da shi a kan yanayin. Yana iy
Echo
10/20/2025
Kaduna Dabara Da Digital MV Circuit Breakers
Kaduna Dabara Da Digital MV Circuit Breakers
Amince Wata Daga Samun Digitized Medium-Voltage Switchgear da Circuit Breakers"Wata" - wannan wani kalma da ba ake so in fuskantar ma'aikatar gida bai, musamman idan ya shafi da haka. Na gode da circuit breakers (MV) na farko da switchgear, za ku iya amfani da tushen digital don kare masu shiga da zama mai kyau.Switchgear da circuit breakers na MV na zamani suna da sensors digital da suka fito da su, wanda ke taimaka da kawo abubuwan da za a duba game da manyan abubuwa. Wannan yana ba ku karfin
Echo
10/18/2025
Wani Maqala Don Fahimtar Yadda Makashe A Cikin Kirkiro Vakuumi Ne
Wani Maqala Don Fahimtar Yadda Makashe A Cikin Kirkiro Vakuumi Ne
Tsunukan Gwamnati na Tafin Maimaita: Tashin Tafi, Tashin Tafin Maimaita, da Jirgin YawanciYanayi 1: Tafin Daga Bari (Tashin Tafi, 0-3 mm)Limadda tana bayarwa cewa yanayin tafin daga bari (0-3 mm) yana da muhimmanci sosai wajen tushen tafin maimaita gwamnatin tsunukan. A farkon tafin daga bari, takambari tafi yana zama daga hali na sauki zuwa hali na tafina - ya kamata wannan tashin zama kadan da kyau saboda haka yana ba da tushen tafin maimaita.Dalilu uku suna iya taka tashin daga hali na sauki
Echo
10/16/2025
Mafiya da Tattalin Aiki na Kirkiro Masu Sauci a Tsakiyar Karamin Kirkiro Masu Sauci Da Rike Kadan
Mafiya da Tattalin Aiki na Kirkiro Masu Sauci a Tsakiyar Karamin Kirkiro Masu Sauci Da Rike Kadan
Maimaito da Amfani da Maimaito na Tsakiyar Karamin Rike na Zafiya: Muhimman Matafi, Amfani, da MuhimmanciSaboda darajinsa na rike da zafiya, maimaito na tsakiyar karamin rike na zafiya suna da fara da yawa da dama cewa mai tsarki da suka. A kan wannan farar da yawa, tattalin magana mai tsayi (TMF) ya fi shahara da tattalin magana mai ci (AMF) don gudanar da amfani da karamin rike mai yawa. Idan an gudanar da amfani da karamin rike masu yawa, tsakiyar zafiya yana haifi don koyar da yanayi mai yaw
Echo
10/16/2025
Aika tambaya
Kwamfuta
Samun IEE Business Application
Yi amfani da IEE-Business app don samun abubuwan aikin, samun halayyin, haɗi da malamai, kuma kai tsauraran takaiddun kasoshin duka lokaci, duka wurin—dole bai karfin takamaltar hulɗin ku na alintakargida da kasuwanci.