EMF Equation of a Synchronous Generator

Learn how to derive the EMF equation of a synchronous generator, understand essential winding factors like coil span factor and distribution factor, and their impact on generator performance.

Edwiin
Field: Power switch
10Year<
China
Add us on Google

Synchronous Generator and EMF Equation Derivation

A generator operating at synchronous speed is termed a synchronous generator, which converts mechanical power into electrical energy for grid integration. The derivation of the EMF equation for a synchronous generator is as follows:

Notation:

  • P = number of poles

  • ϕ = flux per pole (Weber)

  • N = rotational speed (revolutions per minute, r.p.m)

  • f = frequency (Hertz)

  • Zph = number of series-connected conductors per phase

  • Tph = number of series-connected turns per phase

  • Kc = coil span factor

  • Kd = distribution factor

Derivation: The flux cut by each conductor in one revolution is Pϕ Weber. The time to complete one revolution is 60/N seconds. The average EMF induced per conductor is given by:

EMF Equation of a Synchronous Generator

Average EMF induced per phase will be given by the equation shown below:

EMF Equation of a Synchronous Generator

Average EMF Equation Assumptions

The derivation of the average EMF equation is based on the following assumptions:

  • Coils exhibit full pitch configuration.

  • All conductors are concentrated within a single stator slot.

The root mean square (RMS) value of the induced EMF per phase is expressed as:Eph = Average Value&times;Form Factor Thus,

EMF Equation of a Synchronous Generator

EMF Equation and Winding Factors

Equation (1) above represents the EMF equation of a synchronous generator.

Coil Span Factor (Kc)

The coil span factor is defined as the ratio of the induced EMF in a short-pitched coil to that in an identical full-pitched coil.

Distribution Factor (Kd)

The distribution factor is the ratio of the induced EMF in a distributed coil group (wound across multiple slots) to that in a concentrated coil group (wound in a single slot).