Feeder Protection Relay

Encyclopedia
Encyclopedia
Field: Encyclopedia
0
China

Feeder Protection Relay Definition


A feeder protection relay is defined as a device that protects power system feeders from faults like short circuits and overloads.


It measures the feeder line’s impedance (Z) using voltage (V) and current (I) inputs from the potential transformer (PT) and current transformer (CT). Impedance is calculated by dividing voltage by current: Z = V/I.


The relay compares the measured impedance to a preset value that represents the maximum allowable impedance for normal operation. If the measured impedance is lower, there is a fault, and the relay sends a trip signal to the circuit breaker to isolate it. The relay can also show fault parameters like fault current, voltage, resistance, reactance, and fault distance on its screen.


Fault distance is the distance from the relay to the fault, estimated by multiplying the measured impedance by the line impedance per kilometer. For example, if the measured impedance is 10 ohms and the line impedance per kilometer is 0.4 ohms/km, the fault distance is 10 x 0.4 = 4 km. Knowing this helps locate and repair the fault quickly.


Distance Protection Relay


Measures impedance to detect faults and sends a trip signal to isolate the faulty section.


Quadrilateral Characteristic


Distance protection relays can have various operating characteristics, including circular, mho, quadrilateral, or polygonal. The quadrilateral characteristic is popular in modern numerical relays for its flexibility and accuracy in setting protection zones.


A quadrilateral characteristic is a parallelogram-shaped graph that defines the protection zone of the relay. The graph has four axes: forward resistance (R F), backward resistance (R B), forward reactance (X F), and backward reactance (X B). The graph also has a slope angle called the relay characteristic angle (RCA), which determines the shape of the parallelogram.

 

cf7897ea1251129afa4ac29fe0e66dd3.jpeg


 

The quadrilateral characteristic can be plotted by using the following steps:

 


  • Set the R F value on the positive X-axis and the R B value on the negative X-axis.



  • Set the X F value on the positive Y-axis and the X B value on the negative Y-axis.



  • Draw a line from R F to X F with a slope of RCA.



  • Draw a line from R B to X B with a slope of RCA.



  • Complete the parallelogram by connecting R F to R B and X F to X B.


 

The protection zone is inside the parallelogram, which means that if the measured impedance falls inside this area, then the relay will trip. The quadrilateral characteristic can cover four quadrants of operation:


 

  • First quadrant (R and X values are positive): This quadrant represents an inductive load and a forward fault from the relay.



  • Second quadrant (R is negative and X is positive): This quadrant represents a capacitive load and a reverse fault from the relay.



  • Third quadrant (R and X values are negative): This quadrant represents an inductive load and a reverse fault from the relay.



  • Fourth quadrant (R is positive and X is negative): This quadrant represents a capacitive load and a forward fault from the relay.


Zones of Operation


Distance protection relays have different zones of operation, defined by impedance settings and time delays. These zones coordinate with other relays to provide backup protection for adjacent feeders.

 


The typical zones of operation for a distance protection relay are:

 


  • Zone 1: This zone covers 80% to 90% of the feeder length and has no time delay. It provides primary protection for faults within this zone and trips instantaneously.



  • Zone 2: This zone covers 100% to 120% of the feeder length and has a short time delay (usually 0.3 to 0.5 seconds). It provides backup protection for faults beyond zone 1 or in adjacent feeders.



  • Zone 3: This zone covers 120% to 150% of the feeder length and has a longer time delay (usually 1 to 2 seconds). It provides backup protection for faults beyond zone 2 or in remote feeders.



  • Some relays may also have additional zones, such as Zone 4 for load encroachment or Zone 5 for overreaching faults.

 


Selection Criteria


  • Choose numerical relays over electromechanical or static relays for better performance, functionality, flexibility, and diagnostics



  • Choose distance protection relays over overcurrent or differential protection relays for long or complex feeders



  • Choose quadrilateral characteristics over circular or mho characteristics for more accuracy and adaptability



  • Choose low-energy analog sensor inputs over conventional current/voltage inputs for reduced size, weight, and safety hazards.



  • Choose arc-flash detection relays over conventional relays for faster tripping and personnel safety.


Conclusion


Feeder protection relays are vital devices that protect power system feeders from various types of faults. They can improve power system reliability, security, and efficiency by quickly detecting and isolating faults, preventing damage to equipment, and minimizing power outages.


One of the most common types of feeder protection relays is the distance protection relay, which measures the impedance of the feeder line by using the voltage and current inputs from the corresponding potential transformer and current transformer. It compares the measured impedance with a predefined setting value, which represents the maximum allowable impedance for normal operation. If the measured impedance is lower than the setting value, it means that there is a fault on the feeder line, and the relay will send a trip signal to the circuit breaker to isolate the fault.


The distance protection relay can have different operating characteristics, such as circular, mho, quadrilateral, or polygonal. A quadrilateral characteristic is a popular choice for modern numerical relays because it offers more flexibility and accuracy in setting the protection zones.


A quadrilateral characteristic is a parallelogram-shaped graph that defines the protection zone of the relay. The graph has four axes: forward resistance (R F), backward resistance (R B), forward reactance (X F), and backward reactance (X B). The graph also has a slope angle called the relay characteristic angle (RCA), which determines the shape of the parallelogram.

 

Give a tip and encourage the author!
Recommended
What lightning protection measures are used for H61 distribution transformers?
What lightning protection measures are used for H61 distribution transformers?
What lightning protection measures are used for H61 distribution transformers?A surge arrester should be installed on the high-voltage side of the H61 distribution transformer. According to SDJ7–79 "Technical Code for Design of Overvoltage Protection of Electric Power Equipment," the high-voltage side of an H61 distribution transformer should generally be protected by a surge arrester. The grounding conductor of the arrester, the neutral point on the low-voltage side of the transformer, and the
Felix Spark
12/08/2025
How to Implement Transformer Gap Protection & Standard Shutdown Steps
How to Implement Transformer Gap Protection & Standard Shutdown Steps
How to Implement Transformer Neutral Grounding Gap Protection Measures?In a certain power grid, when a single-phase ground fault occurs on a power supply line, both the transformer neutral grounding gap protection and the power supply line protection operate simultaneously, causing an outage of an otherwise healthy transformer. The main reason is that during a system single-phase ground fault, the zero-sequence overvoltage causes the transformer neutral grounding gap to break down. The resulting
Noah
12/05/2025
110kV Transformer Zero-Sequence Protection: Issues & Improvement Measures
110kV Transformer Zero-Sequence Protection: Issues & Improvement Measures
Problems with Zero-Sequence Protection of 110 kV TransformersIn an effectively grounded system, the neutral-to-ground displacement voltage of a transformer is limited to a certain level, and the neutral-point gap protection does not operate. The purpose of installing gap protection is to prevent damage to transformer insulation caused by elevated zero-sequence voltage in non-effectively grounded systems. The discharge gap only operates when a single-phase ground fault occurs, all directly ground
Echo
12/03/2025
Chinese Protection Relay Earns IEC 61850 Ed2.1 Level-A Certification
Chinese Protection Relay Earns IEC 61850 Ed2.1 Level-A Certification
Recently, the NSR-3611 low-voltage protection and control device and the NSD500M high-voltage measurement and control device—both developed by a Chinese protection and control equipment manufacturer—successfully passed the IEC 61850 Ed2.1 Server Level-A certification test conducted by DNV (Det Norske Veritas). The devices have been awarded the international Level-A certification by the Utilities Communication Architecture International Users Group (UCAIug). This milestone marks the manufacturer
Baker
12/02/2025
Related Products
Send inquiry
Download
Get the IEE Business Application
Use the IEE-Business app to find equipment, obtain solutions, connect with experts, and participate in industry collaboration anytime, anywhere—fully supporting the development of your power projects and business.