Research on Low-Voltage Anti-DC Current Transformers and Their Detection Methods

Dyson
Dyson
Field: Electrical Standards
China

1. Overview of Components and Issues

TA (low-voltage current transformer) and electric energy meters are key components of low-voltage electric energy metering. The load current of such meters is no less than 60A. Electric energy meters vary in type, model, and anti-DC performance, and are connected in series in the metering device. Due to the lack of anti-DC capability, they suffer from metering errors under DC component loads, usually caused by non-linear loads. With the increasing use of DC or silicon-controlled equipment, especially in electrified railways and the plastics industry, the risk of DC components has risen. Analyzing low-voltage anti-DC current transformers and detection devices is of great significance for addressing this issue.

2. Reasons for TA Inaccuracy Caused by DC Components

The widespread DC bias in low-voltage current transformers stems from the influence of primary-side DC components. Theoretically, harmonics generated by DC disrupt metering transmission, and changes in the iron core's excitation current fail to produce corresponding magnetic flux changes, ultimately leading to TA inaccuracy. Using half-wave current tests (32% of DC components are half-wave currents), the magnetic permeability decreases after the primary winding, significantly increasing errors (with a negative shift, approaching saturation). Displacement of the secondary winding amplifies waveform changes. Tests show that half-wave currents cause large, geometrically increasing errors in traditional transformers; even tiny DC components can affect low-voltage anti-DC transformers, resulting in errors exceeding the allowable range.

3. R&D of Anti-DC Low-Voltage Current Transformers

Traditional low-voltage transformers use annular magnetic cores (mainly amorphous ribbons, with high magnetic permeability, low saturation coefficients, and unaffected by primary-side DC). Iron-based amorphous cores, though slightly lower in magnetic permeability, are widely used in power transformers due to low iron loss. They have strong initial magnetic susceptibility and low coercivity, with excellent anti-DC capability. Electric waves from the secondary winding can restore the primary current waveform. By combining the complementary magnetic properties of iron-based amorphous and ultra-microcrystalline materials to form composite cores, the metering accuracy of traditional low-voltage anti-DC transformers can be improved.

4.Research on TA anti-DC performance detection methods

The existing anti-DC low-voltage current transformers generally have the problem of lack of detection methods. The previous standards are not standardized and cannot be judged according to unified rules and specifications. Therefore, how to do a good job in the anti-DC performance detection method and optimize it is urgent.

4.1 Comparison of electric energy

After using the low-voltage current transformer, the internal performance of the AC electric energy meter will change, and the proportion of even harmonics will also change. To conduct a clear assessment of it, a half-wave rectification electric energy comparison test line must be applied. Before the test, the half-wave rectification electric energy comparison method experimental line should be appropriately improved based on the actual situation to ensure that it is consistent with the anti-DC performance of the low-voltage current transformer, thereby improving the accuracy of electric energy detection.

4.2 1/1 self-calibration

The circuit diagram selected for this test is based on the data of JJ G1021-2007 "Regulations for the Verification of Power Transformers", and the details are shown in Figure 1.

To optimize the 1/1 self - calibration, the experiment rewinds the secondary winding with the same turns as the test low - voltage current transformer. This avoids error introduction from standard transformers. The circuit measures half - wave current and clarifies errors. Note: the current transformer in the circuit uses a 10/1 ratio to boost the verifier’s current, so test values must be multiplied by 10 for accuracy.

Experiments prove this method effectively detects anti - DC performance, enabling circuit testing and self - calibration while avoiding measurement errors. However, rewinding is needed before measurement. Current and detection efficiency are inversely related: as current rises, efficiency plummets but labor intensity increases. Thus, half - wave DC composite error can’t accurately reflect individual anti - DC performance.

5. Test Verification
5.1 Test Method

Simulating half - wave DC electricity theft by electric furnace users, the test installs three distinct energy metering devices. Repeated comparisons of performance results show manganin - resistance energy meters have superior anti - DC shunting ability, meeting on - site stability needs.

5.2 Test Data

Adequate prep, scientific plans, and pre - test site verification are key. During 80 - day assessments, energy is repeatedly compared/calculated, with detailed records.Results: Initial ordinary transformer meters show 40.08% relative error, rising to 90.58% after 80 days. Manganin meters keep errors ≤1% even in harsh conditions, while traditional devices exceed 90% over time. Enhancing anti - DC transformer research is vital for on - site demands.

6. Conclusion

The new composite - core low - voltage anti - DC current transformer accurately measures current, meeting standards even under DC loads. Unlike traditional designs, it retains familiar winding/pouring processes for easy promotion.DC - AC standard - based transformers offer strong operability, solving traceability issues and boosting detection accuracy.

Give a tip and encourage the author!
Recommended
Minimum Operating Voltage for Vacuum Circuit Breakers
Minimum Operating Voltage for Vacuum Circuit Breakers
Minimum Operating Voltage for Trip and Close Operations in Vacuum Circuit Breakers1. IntroductionWhen you hear the term "vacuum circuit breaker," it might sound unfamiliar. But if we say "circuit breaker" or "power switch," most people will know what it means. In fact, vacuum circuit breakers are key components in modern power systems, responsible for protecting circuits from damage. Today, let's explore an important concept — the minimum operating voltage for trip and close operations.Though it
Dyson
10/18/2025
Efficient Wind-PV Hybrid System Optimization with Storage
Efficient Wind-PV Hybrid System Optimization with Storage
1. Analysis of Wind and Solar Photovoltaic Power Generation CharacteristicsAnalyzing the characteristics of wind and solar photovoltaic (PV) power generation is fundamental to designing a complementary hybrid system. Statistical analysis of annual wind speed and solar irradiance data for a specific region reveals that wind resources exhibit seasonal variation, with higher wind speeds in winter and spring and lower speeds in summer and autumn. Wind power generation is proportional to the cube of
Dyson
10/15/2025
Wind-Solar Hybrid Powered IoT System for Real-Time Water Pipeline Monitoring
Wind-Solar Hybrid Powered IoT System for Real-Time Water Pipeline Monitoring
I. Current Status and Existing ProblemsCurrently, water supply companies have extensive networks of water pipelines laid underground across urban and rural areas. Real-time monitoring of pipeline operation data is essential for effective command and control of water production and distribution. As a result, numerous data monitoring stations must be established along the pipelines. However, stable and reliable power sources near these pipelines are rarely available. Even when power is accessible,
Dyson
10/14/2025
How to Build an AGV-Based Intelligent Warehouse System
How to Build an AGV-Based Intelligent Warehouse System
Intelligent Warehouse Logistics System Based on AGVWith the rapid development of the logistics industry, growing land scarcity, and rising labor costs, warehouses—serving as key logistics hubs—are facing significant challenges. As warehouses become larger, operational frequencies increase, information complexity grows, and order-picking tasks become more demanding, achieving low error rates and reduced labor costs while improving overall storage efficiency has become a primary goal for the wareh
Dyson
10/08/2025
Related Products
Send inquiry
Download
Get the IEE Business Application
Use the IEE-Business app to find equipment, obtain solutions, connect with experts, and participate in industry collaboration anytime, anywhere—fully supporting the development of your power projects and business.