What should be noted when choosing a current transformer for a 10kV station transformer circuit?

James
07/04/2025

Practical Experience Sharing from an Electrical Engineer in the Field
By James, 10 Years in the Electrical Industry

Hi everyone, I'm James, and I've been working in the electrical industry for 10 years.

From early involvement in substation design and equipment selection, to later taking charge of relay protection and automation system commissioning for entire projects, one of the most frequently used devices in my work has been the current transformer (CT).

Recently, a friend who's just starting out asked me:

“What should I pay attention to when selecting current transformers for 10kV station transformer circuits?”

Great question! Many people think choosing a CT is all about the rated current ratio — but to truly match the needs of a circuit, you need to consider multiple factors.

Today, I’ll share with you in simple language — based on my hands-on experience over the past few years — what key points to consider when selecting CTs for 10kV station transformer circuits, what each parameter means, and how to make the right choice.

No complicated jargon, no endless standards — just practical knowledge you can use in real life.

1. Why Is It Important to Carefully Choose CTs for Station Transformer Circuits?

Although the station service transformer isn't the main power transformer, it plays a critical role in supplying internal power within a substation — including control power, lighting, maintenance power, and UPS systems.

If the station transformer fails or its protection malfunctions, it could lead to:

  • Loss of control power;
  • DC system losing charging capability;
  • The entire substation shutting down.

And since the current transformer is the core component for protection and measurement, its selection directly affects whether the protection is reliable and the measurements are accurate.

So, choosing the right CT = safety + reliability + cost-effectiveness.

2. Six Key Points When Selecting CTs for 10kV Station Transformer Circuits

Based on my 10 years of field experience and project practice, here are the six most important considerations:

Point 1: Rated Primary and Secondary Current

Purpose: Ensure the CT operates normally and meets protection sensitivity requirements.

This is the most basic and important parameter.

Common combinations:

  • Primary current: 50A, 75A, 100A, 150A (depending on station transformer capacity)
  • Secondary current: 5A or 0.5A (most modern protection devices use 0.5A)

My advice:

  • Usually choose primary current as 1.2~1.5 times the station transformer’s rated current;
  • For microprocessor-based protection, prefer 0.5A output to reduce secondary load;
  • Avoid selecting too high a rating — otherwise accuracy may be poor at low currents, affecting protection performance.

Point 2: Accuracy Class Matching the Application

Purpose: Ensure different functions (like protection, measurement, metering) receive accurate signals.

Different applications require different accuracy levels.

Common classes:

  • Measurement winding: Class 0.5
  • Metering winding: Class 0.2S
  • Protection winding: 5P10, 5P20, 10P10, etc.

My experience:

  • Station transformer circuits usually don’t require high-precision metering unless there's billing involved;
  • Protection windings must maintain linearity during short circuits;
  • Multi-winding CTs offer more flexibility and are recommended.

Point 3: Rated Output Capacity (VA Value)

Purpose: Ensure the CT can drive the connected meters or protection devices.

Insufficient capacity can cause voltage drop, affecting measurement accuracy or protection operation.

Calculation formula:

Total Load = Cable Impedance + Instrument/Protection Device Input Impedance

My advice:

  • Typically choose between 10–30 VA;
  • Microprocessor protection devices consume less power — lower capacity acceptable;
  • If the secondary cable is long (e.g., over 50 meters), increase the capacity appropriately;
  • Don’t blindly select high capacity — avoid core saturation.

Point 4: Thermal and Dynamic Stability Check

Purpose: Ensure the CT can withstand short-circuit current without damage.

In 10kV systems, short-circuit currents can reach thousands of amps.

How to do it:

  • Check maximum short-circuit current (Ik);
  • Verify CT thermal stability current (It) and dynamic stability current (Idyn);
  • Generally, It ≥ Ik (for 1 second), Idyn ≥ 2.5 × Ik

Real case: I once had a CT explode after a short circuit — turned out the dynamic stability current didn’t meet system requirements. Replacing with a higher-rated CT solved the problem.

Point 5: Installation Method and Structure Type

Purpose: Ensure the CT is easy to install and maintain, and fits the available space.

Common CT types include:

  • Core-type (common in switchgear)
  • Post-type (suitable for outdoor use)
  • Bushing-type (often used on transformers)

My advice:

  • In 10kV switchgear, core-type CTs are most common;
  • Make sure the conductor size matches the core hole diameter;
  • For tight spaces, consider split-core CTs for easier installation and removal;
  • In humid or corrosive environments, choose moisture-resistant or corrosion-proof models.

Point 6: Polarity and Wiring Method

Purpose: Ensure the signal direction to protection relays and instruments is correct, avoiding misjudgment.

Incorrect polarity can lead to:

  • Misoperation or failure of protection;
  • Wrong power flow direction judgment;
  • False alarms in differential protection.

My experience:

  • All CTs should clearly mark polarity terminals (P1, P2);
  • Use subtractive polarity connection consistently;
  • Always perform a polarity test after installation or maintenance;
  • Use a dedicated polarity tester or DC method for verification.

3. Other Practical Tips

In addition to the six key points above, here are some other important notes:

Multi-winding Configuration:

  • Separate windings for protection, measurement, and metering to avoid interference;
  • Reserve spare windings for future expansion.

Excitation Characteristics:

  • Especially for protection windings, good excitation characteristics improve protection reliability;
  • If possible, perform an excitation curve test to confirm core performance.

Sample Selection Reference for a 50kVA Station Transformer

4. My Final Suggestions

As someone with 10 years of field experience, I want to remind all professionals:

“Don’t just look at the model number — always consider the actual circuit, protection setup, and installation environment when selecting a CT.”

Especially in seemingly "simple" 10kV station transformer circuits, improper selection often leads to serious consequences.

Here are my recommendations for different roles:

For Maintenance Personnel:

  • Learn how to read CT nameplate information;
  • Understand basic parameter meanings;
  • Be familiar with polarity testing methods;
  • Report any abnormalities promptly.

For Technical Staff:

  • Master CT selection calculation methods;
  • Understand protection winding characteristics;
  • Know how to interpret system short-circuit parameters;
  • Be able to analyze excitation curves.

For Managers or Procurement Teams:

  • Clearly define technical specifications;
  • Choose reputable manufacturers with stable quality;
  • Request full test reports from suppliers;
  • Maintain equipment records for traceability.

5. Closing Thoughts

Current transformers may look small, but they are the eyes and ears of the entire power system.

They’re not just about reducing current — they’re the basis for protection, the foundation for metering, and the guarantee of safety.

After 10 years in the electrical field, I often say:

“Details determine success or failure, and proper selection ensures safety.”

If you ever run into difficulties selecting CTs, dealing with frequent protection misoperations, or unsure if your parameters are suitable, feel free to reach out — I’m happy to share more hands-on experience and solutions.

May every current transformer operate stably and safely, safeguarding the accuracy and reliability of our power grid!

— James

James

Professionalism builds strength. As an expert in the installation and operation of electrical equipment, I am proficient in the installation process and strictly adhere to standards. I skillfully master the operation essentials and can swiftly eliminate faults. With a heart that constantly explores new knowledge, I illuminate the path to the efficient operation of electrical equipment.

A Quick Verification Method for Low-Voltage Current Transformers
A Quick Verification Method for Low-Voltage Current Transformers
1. Selection of Low - Voltage Current Transformer ConfigurationThere are many factors leading to wrong selection of low - voltage current transformers in civil construction projects. For example, common factors include design problems: the calculated coefficient designed for the load of electrical equipment is relatively large, or the transformation ratio of the current transformer is selected incorrectly. Such a series of reasons will affect the use of electrical equipment. Therefore, in the co
James
07/16/2025
What are the key technical points for the selection and installation of AIS voltage transformers in 66kV outdoor substations?
What are the key technical points for the selection and installation of AIS voltage transformers in 66kV outdoor substations?
Hey everyone! I'm James, a professional with over 10 years of experience installing voltage transformers. Today, I want to talk about the selection and installation of Air Insulated Switchgear (AIS) voltage transformers in 66kV outdoor substations.These devices are critical for measurement and protection in power systems. Their proper selection and installation directly affect the safety and stability of the entire electrical grid. With the advancement of smart grid technology, electronic AIS vo
James
07/15/2025
Fault Analysis and Diagnosis on Current Transformer
Fault Analysis and Diagnosis on Current Transformer
Current transformers are numerous in substations and are key equipment to ensure the normal operation of the system. If a current transformer fails, it will cause the circuit breaker to trip and may even evolve into a power outage event, which will have an adverse impact on the safe and stable operation of the power grid. Taking an event of the main transformer differential protection operation caused by the failure of the current transformer on the low-voltage side of the main transformer in a
Felix Spark
07/14/2025
What does the maintenance of current transformers involve?
What does the maintenance of current transformers involve?
Fault Prevention and Handling of Current Transformers1 Handling of Oil Leakage in Current TransformersOil - immersed current transformers are most prone to oil leakage. Common oil - leakage parts mainly include the secondary outlet box, the upper and lower sealing surfaces of the porcelain sleeve, the oil tank, the base, the oil conservator, and the metal expander.Methods for handling oil leakage: For oil leakage at the secondary outlet box, if the small porcelain sleeve or terminal board is cra