Why 3-Phase Power? Why Not 6, 12 or More for Power Transmission?

06/05/2025

It is well-known that single-phase and three-phase systems are the most prevalent configurations for power transmission, distribution, and end-use applications. While both serve as fundamental power supply frameworks, three-phase systems offer distinct advantages over their single-phase counterparts.
Notably, multi-phase systems (such as 6-phase, 12-phase, etc.) find specific applications in power electronics—particularly in rectifier circuits and variable frequency drives (VFDs)—where they effectively reduce ripple in pulsating DC outputs. Achieving multi-phase configurations (e.g., 6, 9, or 12 phases) historically involved complex phase-shifting techniques or motor-generator sets, but these approaches remain economically infeasible for large-scale power transmission and distribution over extended distances.

Why 3-Phase Instead of 1-Phase Supply System?

The main advantage of three phase over a single phase or two phase system is that we can transmit more (constant and uniform) power.

Power in Single Phase System

  • P =  V . I  . CosФ

Power in Three Phase System

  • P = √3 . VL . IL . CosФ … Or
  • P = 3 x. VPH . IPH . CosФ

Where:

  • P = Power in Watts
  • VL = Line Voltage
  • IL = Line Current
  • VPH = Phase Voltage
  • IPH = Phase Current
  • CosФ = Power factor

It is evident that the power capacity of a three-phase system is 1.732 (√3) times higher than that of a single-phase system. By comparison, a two-phase supply transmits 1.141 times more power than a single-phase configuration.
A key advantage of three-phase systems is the rotating magnetic field (RMF), which enables self-starting in three-phase motors while ensuring constant instantaneous power and torque. In contrast, single-phase systems lack an RMF and exhibit pulsating power, limiting their performance in motor applications.
Three-phase systems also offer superior transmission efficiency, with reduced power loss and voltage drop. For instance, in a typical resistive circuit:
Single Phase System
  • Power loss in transmission line = 18I2r … (P = I2R)
  • Voltage drop in transmission line = I.6r … (V = IR)

Three Phase System

  • Power loss in transmission line = 9I2r … (P = I2R)
  • Voltage drop in transmission line = I.3r … (V = IR)
It is shown that the voltage drop and power loss in a three-phase system are 50% lower than those in a single-phase system.
Two-phase supplies, similar to three-phase ones, can provide constant power, generate RMF (rotating magnetic field), and offer constant torque. However, three-phase systems carry more power than two-phase systems due to the extra phase. This raises the question: why not use more phases like 6, 9, 12, 24, 48, etc.? We will discuss this in detail and explain how a three-phase system can transmit more power than a two-phase system with the same number of wires.
Why Not Two-Phase?
Both two-phase and three-phase systems can generate rotating magnetic fields (RMF) and provide constant power and torque, but three-phase systems offer a key advantage: higher power capacity. The extra phase in three-phase setups allows for 1.732 times more power transmission than two-phase systems with the same conductor size.
Two-phase systems typically require four wires (two phase conductors and two neutrals) to complete circuits. Using a common neutral to form a three-wire system reduces wiring, but the neutral must carry combined return currents from both phases—needing thicker conductors (e.g., copper) to avoid overheating. In contrast, three-phase systems use three wires for balanced loads (delta configuration) or four wires for unbalanced loads (star configuration), optimizing power delivery and conductor efficiency.、
Why Not 6-Phase, 9-Phase, or 12-Phase?
While higher-phase systems can reduce transmission losses, they aren’t widely adopted due to practical limitations:
  • Conductor Efficiency: Three-phase systems use the fewest conductors (3) to transmit balanced power, while a 12-phase system would need 12 conductors—quadrupling material and installation costs.
  • Harmonic Suppression: The 120° phase angle in three-phase systems naturally cancels third harmonic currents, eliminating the need for complex filters required in higher-phase setups.
  • System Complexity: Higher-phase systems demand reengineered components (transformers, circuit breakers, switchgear) and larger substations, increasing design complexity and maintenance overhead.
  • Practical Constraints: Motors and generators with more than three phases are bulkier and harder to cool, while transmission towers would need greater height to accommodate more conductors.
The Three-Phase Advantage
Three-phase systems strike an optimal balance:
  • They transmit 50% more power than single-phase systems with the same conductors, minimizing losses.
  • The 120° phase configuration balances loads and suppresses harmonics without added complexity.
  • They adapt to both delta (balanced loads) and star (unbalanced loads) setups, supporting diverse power needs.
Higher-phase systems offer diminishing returns—each extra phase raises costs exponentially while providing marginal benefits. For this reason, three-phase technology remains the global standard for power transmission, balancing efficiency, simplicity, and economic viability.

Zhejiang Vziman Electric Group Co., Ltd. is a high-tech enterprise specializing in R&D, manufacturing, and service of power electrical equipment. Committed to innovation, quality, and customer satisfaction, it supplies smart solutions for global power sectors, covering grid construction, new energy, and industrial distribution. Core Business • Switchgear (GIS, circuit breakers, Recloser, Load break switch) • Distribution equipment (transformers, RMU, smart terminals) • Power automation systems • Engineering services (installation, maintenance, consulting) Technical Strength • Provincial R&D center, multiple patents • Modern production, ISO/GB/IEC/CE/UL certified • High capacity, large-scale delivery support Market & Vision Serves State Grid, Southern Grid, and global projects (Asia, Africa, Europe, etc.). Aims to lead in smart grids and new energy, promoting sustainable energy development.

Difference Between Short Circuit & Overload
Difference Between Short Circuit & Overload
One of the main differences between a short circuit and an overload is that a short circuit occurs due to a fault between conductors (line-to-line) or between a conductor and earth (line-to-ground), whereas an overload refers to a situation where equipment draws more current than its rated capacity from the power supply.Other key differences between the two are explained in the comparison chart below.The term "overload" typically refers to a condition in a circuit or connected device. A circuit
08/28/2025
Difference Between Leading and Lagging Power Factor
Difference Between Leading and Lagging Power Factor
Leading and lagging power factors are two key concepts related to the power factor in AC electrical systems. The main difference lies in the phase relationship between current and voltage: in a leading power factor, the current leads the voltage, whereas in a lagging power factor, the current lags behind the voltage. This behavior depends on the nature of the load in the circuit.What is Power Factor?Power factor is a crucial, dimensionless parameter in AC electrical systems, applicable to both s
08/26/2025
Difference Between Electromagnet and Permanent Magnet
Difference Between Electromagnet and Permanent Magnet
Electromagnets vs. Permanent Magnets: Understanding the Key DifferencesElectromagnets and permanent magnets are the two primary types of materials that exhibit magnetic properties. While both generate magnetic fields, they differ fundamentally in how these fields are produced.An electromagnet generates a magnetic field only when an electric current flows through it. In contrast, a permanent magnet inherently produces its own persistent magnetic field once it has been magnetized, without requirin
08/26/2025
Interpretation of the “Five Mandatory Surveys” for On - site Investigation in the Operation and Maintenance Specialty
Interpretation of the “Five Mandatory Surveys” for On - site Investigation in the Operation and Maintenance Specialty
The power outage and work scopes must be clearly inspectedCollaborate with the site survey leader to confirm the equipment to be maintained and the work area involved. Consider requirements such as the use of special vehicles and large machinery, and safe distances from adjacent energized equipment. Verify on-site whether the proposed power outage scope is sufficient to meet the operational needs.On-site safety measures must be clearly inspectedCollaborate with the site survey leader to verify s
Vziman
08/14/2025
Inquiry
Download
IEE-Business is dedicated to serving the personnel in the global power industry.
Join IEE-Business, not only can you discover power equipment and power knowledge, but also canhnd like - minded friends!