• Product
  • Suppliers
  • Manufacturers
  • Solutions
  • Free tools
  • Knowledges
  • Experts
  • Communities
Search


Proteksyon sa mga fuse sa American-style box-type transformer

Felix Spark
Felix Spark
Larangan: Pagkabag-o ug Pagpangutana
China

Pangutana sa mga Fuses sa American-style Box Transformers
Ang mga American-style box transformers kasagaran nagamit og kombinasyon sa mga plug-in fuses ug backup protection fuses sa series aron mobati sa proteksyon. Ang prinsipyong proteksyon maayo ug reliable, ug ang operasyon simple. Ang backup protection fuse usa ka oil-immersed current-limiting fuse, kasagaran gisulod sa loob sa box transformer. Kini mohimo lamang kung adunay sayop sa loob sa box transformer, ug gamiton niini aron mobati sa high-voltage line. Ang plug-in fuse usa ka oil-immersed plug-in fuse, kini mohimo kung adunay short-circuit fault sa secondary side, o kung adunay overload o ang temperatura sa langis taas. Ang plug-in fuse usa sa pangunahon nga accessory alang sa over-current protection sa mga oil-immersed box transformers sa power distribution system.

Ang mga fuses sa loob mahimong maklasipikarha isip tulo ka tipo: current type, dual-sensitive type, ug dual-factor type. Ang fuse mahimo molihok para sa paglihok sa bag-ong fuse walay pagkonekta sa box transformer. Ang current-type fuse, kapag giconnect sa series sa backup protection fuse, makaform og "double-fuse protection". Ang current-type fuse gamiton alang sa overload protection, ug ang backup protection fuse gamiton aron mobati sa internal faults sa transformer (tulad sa coil short circuits, etc.). Ang dual-sensitive fuse, kapag giconnect sa series sa backup protection fuse, usab makaform og "double-fuse protection". Ang dual-sensitive fuse mobati sa faults o overloads sa low-voltage side sa transformer gikan sa aspeto sa current ug temperatura.

Ang backup protection fuse gamiton aron mobati sa internal faults sa transformer (tulad sa coil short-circuit faults, etc.). Ang standard ampere-second curve makapagtugot ng mga fuses ug circuit breakers sa upper ug lower levels. Ang dual-factor fuse, kapag giconnect sa series sa backup protection fuse, makaconstitute og "double-fuse protection". Ang dual-factor fuse mobati sa faults o overloads sa low-voltage side sa transformer gikan sa aspeto sa current ug temperatura. Ang backup protection fuse gamiton aron mobati sa internal faults sa transformer (tulad sa coil short-circuit faults, etc.), ug ang iyang standard ampere-second curve makapagtugot ng mga fuses ug circuit breakers sa upper ug lower levels.
Basic Structure of Fuses
Ang mga fuses adunay lain-laing struktura batas sa mga kinahanglan nga ililok. Kini nga artikulo gibriyef ang McGraw Edison NX type current-limiting fuse sa COOPER (Cooper) Company sa United States.

Ang struktura sa McGraw Edison NX type current-limiting fuse makita sa Figure 1. Kini naglakip og fusible element nga may pure silver fuse strip. Ang pure silver fuse strip gikurbada sa mica support (spider-type support component), ug kini nga support makapag-generate og ionized gas nga makatabang sa pagbukas sa circuit. Ang fuse ug silica sand gisulod sa glass fiber insulation tube.

1 - High-purity silica sand filler;2 - Mica support;3 - Solid copper terminal;4 - Double-sealing system;5 - Identification label;6 - Glass fiber cover;7 - Pure silver fuse strip.

Figure 1. Basic constituent elements of the McGraw Edison NX type current-limiting fuse.

As shown in Figure 1, the McGraw Edison NX type current-limiting fuse (other fuse models have similar structures to this fuse) mainly includes:

  •  High-purity silica sand filler. The specific particle size, purity, and density provide heat absorption and arc extinguishing characteristics, which are essential for the fuse to maintain consistent clearing characteristics and a low energy passing level.

  •  Mica support. During the operation of the fuse, the mica support provides stable winding support without generating gas and pressure accumulation.

  • Solid copper terminal. The brass plug is selected to provide an electrical conductive joint with a length ranging from 0.25 to 10 inches.

  • Double-sealing system. The nitrile rubber gasket and epoxy resin sealant can ensure the integrity of the fuse seal.

  • Firm identification label. It is convenient for users to obtain voltage, current parameters, order numbers, and other information.

  • Glass fiber cover. It provides high strength for the fuse and the integrity of maintenance, enabling the fuse to withstand a protection range from the minimum fusing current to a maximum of 50 kA during any interruption process.

  • Pure silver fuse strip. It can maintain stability under current circulation and thermal pressure conditions and provides consistent fusing characteristics. During the interruption of large currents, the fuse strip can effectively control and reduce the peak level of the arc voltage. During the interruption process, this component can effectively control and limit the allowable passing current and energy.

Operating Characteristics and Protection Principle of the Fuse
The working process of the fuse depends on the model of the fuse element inside it. For all fuses, the clearing of large fault currents is basically the same. The flow of current will melt the fusible element along its entire length, and the generated arc will cause the fusible element to explode, vitrifying the silica sand and forming a glassy channel that restricts the development of the arc. This glassy channel limits the arc by increasing the resistance value, reducing the current and forcing it to reach zero in advance.

In the local or full-range fuse, the clearing of the medium or small currents must be prevented. For example, in the McGraw Edison type current-limiting fuse, an "M" point (i.e., a tin alloy wire) is placed in the center of the main fusible element to lower its melting temperature, as shown in Figure 2(a). Once the fusible element melts at the M point, the current is transferred to the auxiliary fusible element. A thin wire is connected to the main fusible element with a 1/4 gap from one end of the main element. A voltage gradient spans the arc at the M point and the gap of the auxiliary fusible element, as shown in Figure 2(b). Therefore, if the main fusible element continues to arc, this wire connection will inevitably appear at three positions, expanding the length of the arc by three times and using this area to dissipate the energy of the circuit, as shown in Figure 2(c). In the initial stage of arcing, sufficient heat is gathered to decompose the spider structure in that area, and the gas blown out from the spider structure can cool the molten rock and reduce the length of the arc until the fault point can be disconnected.

Figure 2 The process of the McGraw Edison NX type current-limiting fuse reducing the current

The selection of current-limiting fuses is primarily based on their rated voltage parameters. When determining the appropriate parameters, several factors need to be taken into account, including the type of electrical system, the maximum voltage of the system, the winding conditions of the transformer (if the fuse is used for transformer protection), the grounding status of the neutral wire, and the type of load.

Generally, a single-phase circuit can be protected by a current-limiting fuse with a rated parameter greater than the single-phase grounding voltage. However, for a three-phase circuit, the fuse must have suitable inter-phase parameters. In specific cases, assuming that the positive-sequence breaking voltage applied to the fuse does not exceed the maximum design voltage, the single-phase grounding parameters may be applicable to the three-phase system. Under such circumstances, it is assumed that two series-connected current-limiting fuses will share the applied voltage in the given fault condition. Table 1 illustrates the relationship between the recommended rated voltage parameters and the application parameters of current-limiting fuses.

For the protection of electrical devices, the breaking requirements of current-limiting fuses must be coordinated with the devices they protect. Additionally, the time-current curves of the fuses must also be coordinated with the protection devices in the system, especially when backup fuses are involved and the clearing of low-current faults relies on a expulsion fuse.

Table 1 Recommended Rated Voltage Parameters of Current-Limiting Fuses and the Application Parameters of Current-Limiting Fuses

Similar to ordinary fuses, current-limiting fuses may also experience a reduction in power under a certain ambient temperature. The derating factors for various application scenarios are shown in Figure 3.

Figure 3 Ambient Temperature Derating Factors for Applications of NX - type Current - Limiting Fuses

The key to applying fuse protection for distribution transformers is that the fuse must meet the following requirements:

  • Provide short-circuit protection and separate the faulty transformer from the system first. The fuse should not blow during inrush current, cold load starting current, and short-term overcurrent. It should cooperate with the upper-level device (blow before the sectionalizer operates).

  • Prevent severe overcurrent situations that may cause overheating damage or mechanical damage to the transformer. It should be noted that if necessary, item ② can be postponed because the primary purpose of fuse protection is overload protection rather than short-circuit protection.

The time-current curve of the inrush current/cold load starting current of the distribution transformer is estimated based on the following situations: at 0.01 s, the current is 25 times the full-load current; at 0.1 s, the current is 12 times the full-load current; at 1 s, the current is 6 times the full-load current; at 10 s, the current is 3 times the full-load current; and at 100 s, the current is 2 times the full-load current.

To ensure that the fuse used for the protection of the distribution transformer does not blow during inrush current or cold load starting current, the fuse curve should be on the right side of the inrush current/cold load starting current curve. That is to say, the blowing time of the fuse should be longer than the duration of these currents.

The transformer damage curve can be obtained from the manufacturer or the ANSIC57 standard and can be plotted on the same curve graph. As mentioned before, if concessions need to be made, the transformer damage curve should be prioritized over the inrush current curve.

Figure 4 shows the inrush current/cold load starting current curve of a single-phase transformer with a voltage level of 13.8 kV and a rated capacity of 50 kV·A. The full-load current of the transformer is 3.62 A. A fuse curve is assumed in the figure. In fact, there are two fuse curves. The minimum melting curve gives the shortest time for the fuse to be damaged, and the maximum clearing curve gives the longest time for the fuse to clear the fault. The maximum clearing time of the expulsion fuse should never be lower than 0.8 cycles (i.e., 0.0133 s), so this curve is horizontally plotted at 0.0133 s.

Figure 4 shows the inrush current/cold load starting current time-current curve of the distribution transformer. It should be noted that the fuse curve should ensure the coordination between the fuse and the upper-level protection device. The upper-level device may be a line sectionalizing device, such as a fuse or a recloser. The transformer protection fuse should blow before the upper-level fuse is damaged or before the upper-level recloser is locked.

Some distribution transformers are considered to have a full self-protection function (CSP), that is, they have the functions of overcurrent and inrush current protection.

Self-protection transformers usually have a large current-limiting fuse and a secondary circuit breaker for overload prevention in their casings. Ordinary transformers are usually protected by a fuse added to the primary side. Box transformers generally have a fuse that is independent of the casing (non-fixed front panel design), either located in the transformer oil or in a dry bushing well or cylinder (fixed front panel design). In any case, appropriate design should be adopted to simplify the on-site fuse replacement.

The fuse ratio is the ratio of the minimum blowing current of the fuse to the full-load current of the transformer. This ratio indicates the importance of overload protection for the continuous operation of the device. A high fuse ratio allows more transformer failures without blowing during inrush current or overload; a low fuse ratio increases the number of fuse blowings, and some blowings may be unnecessary, but it can better protect the transformer from overload. A typical fuse ratio ranges from 2 to 4.

In a self-protection transformer, the fuse ratio of the internal fuse is approximately 8 because the secondary side of the self-protection transformer is equipped with a circuit breaker that is not affected by overload.

Protection Range and Coordination of Fuse Protection

When selecting a fuse for the protection of a box transformer, generally, the fusing rate can be calculated by dividing the full-load current of the transformer by the minimum melting current of the fuse. Using a high fusing rate can protect the system from faulty transformers, but it only provides limited overload protection; a low fusing rate can provide maximum overload protection, but the fuse is vulnerable to impact current and inrush current.

In addition, comprehensive factors should be considered, including the continuity of operation, transformer failures caused by overload, the coordination between the transformer fuse and the sectionalizing device, and the impact of inrush current and cold load starting. If the characteristics curve of the transformer is known, the fuse can be simply adjusted by making the time characteristic curve of the fuse fall within the area between the transformer inrush curve and the transformer damage curve.

These curves are formulated according to standards, but they are not always applicable, so the fuse needs to be selected. The inrush current largely depends on the residual magnetic flux in the iron core of the voltage wave during closing. To withstand the inrush current, the fuse should be able to withstand 25 times the full-load current at 0.01 s and 12 times the full-load current at 0.1 s. Re-energization after a primary power outage will generate a cold load start. When the inrush current curve is known, the selected fuse curve should be slower than the inrush current curve. The lightning discharge voltage can saturate the iron core of the transformer and generate inrush current. Generally, if lightning damage is a problem, it is better to use a larger-sized fuse.

In addition, when selecting a fuse for the protection of a box transformer, the coordination between fuses must also be considered. Here, the coordination issues in two situations are discussed:

  • Coordination between two current-limiting fuses. To achieve the coordination objective, the curve must start from 0.01 s. For times above 0.01 s, the coordination between two different fuses in the same set can be achieved by simply overlaying the TCCS and using the 75% coordination method; for times below 0.01 s, the coordination can be achieved by using the minimum melting and total clearing values. When two current-limiting fuses are coordinated in series, the maximum current passing through the protection fuse or the load-side fuse should not exceed the minimum melting current of the protected or power-source-side fuse. That is, the load-side fuse will limit the passing current to a level that is not sufficient to melt the power-source-side fuse. Coordination detection above 0.01 s is not required because the coordination boundaries have fixed values. The coordination is conservative and forms a coordination standard for any fault current. If the fault current is limited, the coordination can be achieved by changing the current in the curve.

  • Coordination between the backup current-limiting fuse and the expulsion fuse. This protection method is often adopted because it allows most faults (under small currents) to be cleared by an inexpensive expulsion fuse. When a fault occurs in the protected device, the current-limiting fuse will limit the magnitude of the current. It is very important that the expulsion fuse can clear small current faults without damaging the current-limiting fuse. The current-limiting fuse can pass sufficient current after the expulsion fuse is blown and can provide obvious fault indication. The fuse characteristics will form the intersection of the maximum clearing curve of the expulsion fuse and the minimum fusing curve of the current-limiting fuse, resulting in a larger current, which will lead to synchronous operation. If the two current-limiting fuses are properly selected, the box transformer can achieve full-range protection.

Operation and Maintenance of Fuse Protection

When using a fuse for the protection of a box transformer, the following situations should be noted:

  • The plug-in fuse is manually operated, and users need certain skills and experience. Before using the plug-in fuse to disconnect the energized transformer, the operator should have experience in removing the plug-in fuse from the fuse holder. Improper handling may lead to switching faults and may require the replacement of the transformer or cause a fire.

  • If the plug-in fuse is used for fault closing, it may cause serious personal injury. Internal faults may cause the transformer to crack or the top cover to detach. Therefore, the transformer should always be powered from a remote location to ensure safety.

  • (3) If the transformer is located in an enclosed building or cellar, or if the operator is directly above the transformer, the plug-in fuse assembly should not be used to connect or disconnect the transformer. In such situations, it is inconvenient for the operator to operate correctly, and it is difficult to leave safely in case of improper operation.

  • Before operating the plug-in fuse, the status of the transformer should be carefully judged. Check whether there is an arc discharge sound in the casing; check whether the casing is bulged or there are traces of oil leakage or overflow; check whether there are traces of oil leakage, overflow, or carbon black stains on the casing near the pressure relief device. If the above situations occur, the plug-in fuse should not be used to connect or disconnect the transformer, otherwise, it may lead to a fire or cause casualties.

  • The pressure of the transformer should be released before operating the plug-in fuse. Incorrectly discharging the pressure of the transformer casing may cause the insertion assembly of the plug-in fuse to be violently ejected together with the hot oil. This may cause impact injuries, burns, and environmental pollution.

  • Using a plug-in fuse with an excessively high ampere value may lead to a mismatch with the backup current-limiting fuse in the transformer or other parts of the system. In this case, when a fault occurs inside the transformer, it may cause a larger power outage or lead to the ignition or explosion of the transformer. Installing a plug-in fuse with an ampere value smaller than the recommended value will cause unnecessary fusing and interruptions in operation.

  • Damage to the fuse tube will affect the correct installation of the fuse. Carefully check the fuse tube to ensure that there is no corrosion larger than pitting on any part of the brass, and that the blackening or ablation of the insulating components is not longer than 1/2 in (13 mm). If the damage exceeds this degree, the damaged fuse tube should be replaced with a new one. If a large amount of brass melting occurs, or the ablation extends beyond half of the length of the fuse tube, the plug-in fuse holder should also be replaced. If the component is damaged, it may prevent the disconnection of subsequent faults and cause greater damage.

Conclusion

The technical level of fuse protection is relatively advanced, and it has an excellent performance-price ratio, with broad development prospects in both domestic and foreign markets. Currently, a large number of American-style box transformers in China use fuses for protection. Compared with other protection methods, fuse protection not only has high reliability but also a relatively low price, which is particularly suitable for the current situation in China. Therefore, fuse protection has good application prospects in China.

Maghatag og tip ug pagsalig sa author
Gipareserbado
10kV RMU Common Faults & Solutions Guide

Gidagway sa mga Karaniwang Sayop ug Solusyon alang sa 10kV RMU
10kV RMU Common Faults & Solutions Guide Gidagway sa mga Karaniwang Sayop ug Solusyon alang sa 10kV RMU
Mga Isyu sa Pag-apply ug mga Pamaagi sa Pag-handle para sa 10kV Ring Main Units (RMUs)Ang 10kV ring main unit (RMU) usa ka kasagaran nga pananglitan sa elektrikal nga distribusyon sa urban nga mga network sa kuryente, gamiton sa paghatag ug distribusyon sa medium-voltage nga kuryente. Sa aktwal nga operasyon, mahimong madungog ang uban pang mga isyu. Ania ang mga kasagaran nga problema ug ang naka-corresponding nga mga pamaagi sa pag-handle.I. Mga Electrical Faults Internal Short Circuit o Pobre
Echo
10/20/2025
Mga Tipo sa High-Voltage Circuit Breaker ug Guide sa Mga Pagsayop
Mga Tipo sa High-Voltage Circuit Breaker ug Guide sa Mga Pagsayop
High-Voltage Circuit Breakers: Classification and Fault DiagnosisAng mga high-voltage circuit breakers mao ang mga kritikal nga protective devices sa mga power systems. Sila nag-intererrupt sa current ngadto sa pag-occur og fault, nang maprevent ang pag-damage sa equipment gikan sa overloads o short circuits. Sa wala pa, tungod sa long-term operation ug uban pang factors, ang mga circuit breakers mahimong mag-develop og faults nga angay nga i-diagnose ug troubleshoot niadtong maayo nga panahon.I
Felix Spark
10/20/2025
10 Prohibitions para sa Pag-install ug Paggamit sa Transformer!
10 Prohibitions para sa Pag-install ug Paggamit sa Transformer!
10 Prohibitions for Transformer Installation and Operation! Dili ang pag-install sa transformer nang labi ka layo—ayaw ihatag kini sa mga remote nga bukid o wilderness. Ang labi ka dako nga distansya wala lang magwasto sa cables apan adunay mas daghan pa nga line losses, ug mahadlok usab ang pag-manage ug maintenance. Dili ang pagpili sa capacity sa transformer nang random. Importante nga ang tama nga capacity. Kon ang capacity mubo, ang transformer mahimong mag-overload ug madaling mapuslan—ang
James
10/20/2025
Paunsa ang mga Transformer nga walay Lanas sa Maayo nga Paraan?
Paunsa ang mga Transformer nga walay Lanas sa Maayo nga Paraan?
Ang mga Prosidyur sa Pagmamaintain sa Dry-Type Transformers Ibutang ang standby transformer sa operasyon, buksan ang circuit breaker sa low-voltage side sa transformer nga gi-maintain, tangtangon ang control power fuse, ug ihapad ang "DO NOT CLOSE" sign sa switch handle. Buksan ang high-voltage side circuit breaker sa transformer nga gi-maintain, isara ang grounding switch, fully discharge ang transformer, lock ang high-voltage cabinet, ug ihapad ang "DO NOT CLOSE" sign sa switch handle. Para sa
Felix Spark
10/20/2025
Mga Produktong Nakarrelasyon
Inquiry
Pangutana
Pangutana sa IEE-Business Application
Pangita og mga equipment gamit ang IEE-Business app asa asa ug kailan man sugad og pagkuha og solusyon pagsulay sa mga eksperto ug pagpadayon sa industriya nga pakisayran suportahan ang imong proyekto sa kuryente ug negosyo