| Marque | Rw Energy |
| Série | RW32 |
| Tension nominale | 40.5kV |
| Courant nominal | 630/1250A |
| Fréquence nominale | 50/60Hz |
Description du produit
Caractéristiques principales

|
Serial Number
|
Item
|
Unit
|
Value
|
|
|---|---|---|---|---|
|
1
|
Rated Voltage
|
kV
|
40.5
|
|
|
2
|
Rated Current
|
A
|
630/1250
|
|
|
3
|
Rated Frequency
|
Hz
|
50 or 60
|
|
|
4
|
Power - frequency Withstand Voltage (1min, Wet) (Dry) Phase - to - phase, Phase - to - ground / Across Breaker
|
kV
|
80/95/95
|
|
|
5
|
Lightning Impulse Withstand Current (Peak Value) Phase - to - phase, Phase - to - ground / Across Breaker
|
kV
|
185
|
|
|
6
|
Rated Short - circuit Breaking Current
|
kA
|
20/25/31.5
|
|
|
7
|
Rated Short - circuit Making Current (Peak Value)
|
kA
|
63/80
|
|
|
8
|
Rated Peak Withstand Current
|
kA
|
63/80
|
|
|
9
|
4S Short - time Withstand Current
|
kA
|
25/31.5
|
|
|
10
|
Rated Operating Cycle
|
-
|
O - 0.3s - CO - 180s - CO
|
|
|
11
|
Number of Rated Short - circuit Breaking Current Operations
|
Times
|
30
|
|
|
12
|
Mechanical Life
|
Times
|
10000
|
|
|
13
|
Mechanism Control Voltage
|
V
|
AC/DC220
|
|
|
14
|
Secondary Circuit 1min Power - frequency Withstand Voltage
|
KV
|
2
|
Oui. Bien que la classification standard d'isolation s'applique jusqu'à 1000m, le RCW-40.5 peut être personnalisé avec une isolation externe renforcée en utilisant le facteur de déclassement d'altitude Ka (selon IEC 62271-1), garantissant une pleine résistance diélectrique jusqu'à une altitude de 3000m.
Il est classé Classe M2 pour l'endurance mécanique. Il est conçu pour 10 000 opérations sans entretien opérations, réduisant considérablement le coût total de possession (TCO) par rapport aux alternatives de Classe M1.