| Marca | Rw Energy |
| Serie | RW32 |
| Voltaje nominal | 40.5kV |
| Corriente nominal | 630/1250A |
| Frecuencia nominal | 50/60Hz |
Descripción del Producto
Características Clave

|
Serial Number
|
Item
|
Unit
|
Value
|
|
|---|---|---|---|---|
|
1
|
Rated Voltage
|
kV
|
40.5
|
|
|
2
|
Rated Current
|
A
|
630/1250
|
|
|
3
|
Rated Frequency
|
Hz
|
50 or 60
|
|
|
4
|
Power - frequency Withstand Voltage (1min, Wet) (Dry) Phase - to - phase, Phase - to - ground / Across Breaker
|
kV
|
80/95/95
|
|
|
5
|
Lightning Impulse Withstand Current (Peak Value) Phase - to - phase, Phase - to - ground / Across Breaker
|
kV
|
185
|
|
|
6
|
Rated Short - circuit Breaking Current
|
kA
|
20/25/31.5
|
|
|
7
|
Rated Short - circuit Making Current (Peak Value)
|
kA
|
63/80
|
|
|
8
|
Rated Peak Withstand Current
|
kA
|
63/80
|
|
|
9
|
4S Short - time Withstand Current
|
kA
|
25/31.5
|
|
|
10
|
Rated Operating Cycle
|
-
|
O - 0.3s - CO - 180s - CO
|
|
|
11
|
Number of Rated Short - circuit Breaking Current Operations
|
Times
|
30
|
|
|
12
|
Mechanical Life
|
Times
|
10000
|
|
|
13
|
Mechanism Control Voltage
|
V
|
AC/DC220
|
|
|
14
|
Secondary Circuit 1min Power - frequency Withstand Voltage
|
KV
|
2
|
Sí. Aunque la calificación de aislamiento estándar se aplica hasta 1000m, el RCW-40.5 se puede personalizar con un aislamiento externo reforzado utilizando el factor de corrección por altitud Ka (según IEC 62271-1), asegurando la plena resistencia dieléctrica en altitudes de hasta 3000m.
Este se clasifica como Clase M2 para resistencia mecánica. Está diseñado para 10.000 operaciones sin mantenimiento, reduciendo significativamente el costo total de propiedad (TCO) en comparación con las alternativas de Clase M1.