| Marca | Rw Energy |
| Serie | RW32 |
| Tensione nominale | 40.5kV |
| Corrente nominale | 630/1250A |
| Frequenza nominale | 50/60Hz |
Descrizione del prodotto
Caratteristiche principali

|
Serial Number
|
Item
|
Unit
|
Value
|
|
|---|---|---|---|---|
|
1
|
Rated Voltage
|
kV
|
40.5
|
|
|
2
|
Rated Current
|
A
|
630/1250
|
|
|
3
|
Rated Frequency
|
Hz
|
50 or 60
|
|
|
4
|
Power - frequency Withstand Voltage (1min, Wet) (Dry) Phase - to - phase, Phase - to - ground / Across Breaker
|
kV
|
80/95/95
|
|
|
5
|
Lightning Impulse Withstand Current (Peak Value) Phase - to - phase, Phase - to - ground / Across Breaker
|
kV
|
185
|
|
|
6
|
Rated Short - circuit Breaking Current
|
kA
|
20/25/31.5
|
|
|
7
|
Rated Short - circuit Making Current (Peak Value)
|
kA
|
63/80
|
|
|
8
|
Rated Peak Withstand Current
|
kA
|
63/80
|
|
|
9
|
4S Short - time Withstand Current
|
kA
|
25/31.5
|
|
|
10
|
Rated Operating Cycle
|
-
|
O - 0.3s - CO - 180s - CO
|
|
|
11
|
Number of Rated Short - circuit Breaking Current Operations
|
Times
|
30
|
|
|
12
|
Mechanical Life
|
Times
|
10000
|
|
|
13
|
Mechanism Control Voltage
|
V
|
AC/DC220
|
|
|
14
|
Secondary Circuit 1min Power - frequency Withstand Voltage
|
KV
|
2
|
Sì. Sebbene la classificazione standard dell'isolamento si applichi fino a 1000m, il RCW-40.5 può essere personalizzato con un isolamento esterno rinforzato utilizzando il fattore di derating altitudinale Ka (secondo IEC 62271-1), garantendo la piena resistenza dielettrica fino a un'altitudine di 3000m.