Ultra-Fast Current Limiter Data sheet
Catalogue · Rw Energy

Ultra-Fast Current Limiter Data sheet

Ultra‑fast high‑voltage fault current limiter. Rated voltage 7.2‑40.5kV, rated current 1250‑6300A, total operating time <10 ms, current‑limiting ratio 15‑50%. It suppresses short‑circuit peak current and avoids switchgear upgrade.

Add us on Google
Updated2026.10
LanguageEnglish
FilePDF · 1.1 MB
Data sheetFault Current LimiterUltra-Fast Current Limiter

Document description

This document introduces ultra‑fast high‑voltage fault current limiter. Its internal fuse complies with IEC 60282‑1:2020 and passes KEMA test. 50/60 Hz, available as cabinet or loose‑part supply.

It limits first‑peak fault current by detecting instantaneous current and current rise rate. Suitable for bus‑tie, generator feeder and reactor‑parallel applications.

Optional selective‑tripping unit isolates fault zones, mitigates voltage sag for sensitive loads and reduces grid‑retrofit cost.

Related Products

Frequently asked questions

Suppresses short‑circuit peaks to avoid equipment replacement, reduces voltage sag, enables multi‑source parallel for stable sensitive‑load operation.

No. It works as normal‑state bypass. It may be paralleled with reactor to eliminate reactor losses.

For multi‑source /multi‑bus systems, to isolate only faulty sections while keeping healthy circuits alive.

Pyrotechnic interrupter and fuse need replacement; control unit is reusable.