RWB-400Z: secondary microcomputer protection & measurement device, sampling 100V/380V and 1A/5A. No primary switchgear parameters (lightning impulse, short-time withstand, making); only for secondary signal acquisition and protection logic output.

Add us on Google
Updated2026.09
LanguageEnglish
FilePDF · 1015.7 KB
Microcomputer Protection DeviceTechnical Specification
Download

Document description

Suitable for 35kV and below small‑current / small‑resistance grounding system, supports feeder, transformer, motor, capacitor multi‑scenario protection; 32‑bit CPU &16‑bit AD, event & fault recording, RS485 communication. No explicit IEC number, generally complies with IEC 60255 relay protection standards.

Related Products

Frequently asked questions

Device auxiliary power: AC/DC 110/220V or DC24V/48V. Operating power: DC220V, AC220V, DC110V, DC48V. Sampling voltage:100V / 380V; sampling current:1A / 5A. These parameters shall be specified when placing order.

It can store up to 32 fault wave‑recording files, record no less than 1000 event records with power‑off data retention; high‑precision clock chip keeps accurate time even after device power loss.

It adopts RS485 bus communication; built‑in 24VDC for passive digital‑input terminals; supports YY and VV PT wiring modes, and terminal short‑circuit setting for anti‑jump function.