ROCKWILL 12kV Indoor Vacuum Circuit Breaker (VSC Series) Technical Solution

12kV indoor VCB, vacuum circuit breaker, spring mechanism, KYN28 compatible, switchgear, short-circuit protection, IEC compliant, customization, power distribution

Rockwill
Wenzhou Rockwill Electric Co., Ltd.
Add us on Google

Ⅰ. Core Functions & Performance

Electrical Parameters

Parameter Value Notes
Rated Voltage 12kV -
Rated Current 630A, 800A, 1250A, 1600A Customizable
Short-Circuit Breaking Capacity 20kA, 25kA, 31.5kA Customizable
Power-Frequency Withstand Voltage (1min) Dry: 48kV / Wet: 38kV DL/T403 Compliant
Lightning Impulse Withstand Voltage 75kV -
Mechanical Life ≥10,000 operations Spring mechanism, oil-free design
Short-Time Withstand Current (4s) 31.5kA -

Control Characteristics

  • Operating Mechanism: Spring-operated (maintenance-free)

  • Coil Voltage (Closing/Tripping): AC/DC 110V/220V (optional)

  • Motor Operating Voltage: Customizable

  • Auxiliary Contacts: 8 NO (Normally Open) + 8 NC (Normally Closed)

  • Monitoring: Mechanical counter (operation records)

Ⅱ. Applications & Compatibility

Typical Applications

  • Power Systems: Power plants, substation in/outlet protection

  • Industrial: Petrochemical, metallurgical, main distribution cabinets for manufacturing

  • Public Facilities: Airports, data centers, residential distribution networks

Switchgear Compatibility

Cabinet Series Compatible Models
Domestic Cabinets KYN28, KYN96, XGN series
International Cabinets ABB ZS series
  • Installation Type: Fixed (Lateral Type)

  • Note: Custom non-standard cabinets supported; installation drawings required.

Ⅲ. Technical Advantages & Innovations

Reliability Enhancement

  • Vacuum Interrupter: Explosion-proof, maintenance-free

  • APG Epoxy Casting: Monolithic insulation parts (humidity resistance ≤95%, pollution-proof)

  • VSC Terminal Buffer: Shock/vibration resistant (-25℃ ~ +40℃)

Safety & Maintenance

  • Interlocking: Mechanical lock to prevent load switching errors

  • Visual Position Indicator: Mechanical ON/OFF status display

  • Modular Design: Rapid replacement of coils/auxiliary switches

Ⅳ. Customization Services

Customization Item Options
Insulation Medium Air-insulated / Gas-insulated (SF₆ alternative)
Secondary Wiring Layout Front/Rear/Side wiring
Special Current Ratings >1600A or >31.5kA designs
High-altitude Adaptation ≤2500m (derating required for higher elevations)

Ⅴ. Installation & Maintenance

Environmental Requirements

  • Altitude: ≤2500m (15% derating beyond)

  • Temperature: -25℃ ~ +40℃

  • Humidity: Daily average ≤90% (non-condensing)

  • IP Rating: IP2X (upgrades to IP4X when installed)

Documentation Support

  • Certificates, installation drawings, wiring diagrams

  • Type test reports compliant with GB/DL/IEC standards

Ⅵ. Typical Configurations (Examples)

Application Scenario Recommended Configuration Protection Target
Substation Inlet Cabinet VSC-1250A/31.5kA + Motorized Main transformer short-circuit
Industrial Distribution Center VSC-1600A/25kA + Rear Wiring Large motor control
Commercial Complex VSC-800A/20kA + Front Wiring LV busbar segmentation

Ⅶ. Support Services

Rockwill Electric Technical Guarantee:

  • Technical Consultation: +86-577-27869966, support@rockwill.com

  • Customization Response: ≤3 business days

  • Warranty: 2 years (core components included)

  • Resources: http://www.rockwill.cn

Deployed Equipment

Leave your contact information to receive the full technical documentation and a free consultation from our engineers.

Comments

Share your question or perspective
WhatsApp
Send inquiry
+86
Click to upload file
Download
Get the IEE Business Application
Use the IEE-Business app to find equipment, obtain solutions, connect with experts, and participate in industry collaboration anytime, anywhere—fully supporting the development of your power projects and business.
Login
or continue with
New here?
Register