Systema automatis pro protectionem et distributionem lineae PMU est novum systema automationis distributionis lineae.
ad solvendum praesentia problemata, praecipue falli terrae.
quod fundatur in Distributione Reticuli Synchronous Phasor Measurement-μPMU.
PMU (phasor measurement unit), dispositivum aut modulatum. Data sampling voltage/current omnia cum timestamp BDS/GPS accurata ad US level.
Functiones basic: • Phasor: amplitudo, angulus phase, • Frequensia (f) et Variatio Frequensiae (△f/△t)

μPMU Diagramma Architecturae Hardware
Systema Mensurae Lati Areae (WAMS)
• Mensurationes PMU absolute synchronizantur cum Tempore Mundiali Standard (UTC)
• Synchronizatio mensurae latis areae multorum PMU in diversis locis installatorum
• Expressio mathematica signalis voltage/current:

Sensor Currentis Overhead i-WCS – Unicam Chanellum Current PMU
Solutio pro problema reticuli distributionis quae fundatur in PMU reticuli distributionis et technologia mensurae phasoris synchronous latis areae.
• Acquisitio currentis altae precisionis et altae frequentiae
• Synchronizatio latis areae, inductio potentiae
• Installatio viva, protectio IP67
• Supportat fluxum potentiae bidirectionalem vel operationem reticuli anularis
• Communicatio 3G/4G/5G:
a. Reportatio periodiciter harmonica singula
b. Eventus localis trigerat upload data
c. Vocatio remota et test datum specifici momenti

• 1μs Synchronizatio latis areae
• 12.8kHz Frequentia sampling
• 60 min Recordatio et playback undarum
• 0.5 Precisio mensurae
• 3.5A Minima operatio currentis full function
Sensor Currentis Typi Cabel RCMU – Multichannel Current PMU

RCMU - Sensor currentis cable subterranei
• 1μs Synchronizatio latis areae
• 12.8kHz Frequentia sampling
• 0.5 Precisio mensurae
• 60 min Playback datarum
• 3 mensurationes currentis
• Transmissio remota wireless/wired
• Collectio triphase currentis, similiter principium typi overhead, apta pro unitate main anulari, statione commutationis, substatione.
• Synchronizatio latis areae, inductio potentiae, vel alimentatio DC 24V/48V
• Algorithmus decisionis defectus localis basatus in currenti:
a. Supercurrentis circuitus brevis
b. Supercurrentis sequentia nulli
c. Currentis phase asymmetrica
• Recordatio undarum vocata mensura, supportat locationem defectus distributivam
• Supportat fluxum potentiae bidirectionalem vel operationem reticuli anularis
• 3G/4G/5G vel communicatio rete
Unitas Collectio Bus BDCU – Unicam/Multas Voltage PMU


Typus interior et exterior
• Alimentatio AC 220V/DC 24V • Fiber optic, wired, wireless
• IEC 60870-5- 101/104/DNP3 • 300 sensoribus currentis possunt accedere Acquisitionis Voltage:
• 1μs Synchronizatio latis areae
• 1.0 Precisio mensurae
• 12.8kHz Frequentia sampling
• 60 min Playback recordationis undarum
Pro defectu grounding uniphase cum currenti terreno maior quam 1A, detectio et accurate locatio est 100%, sine falsis positivis
• Collectio sequentiae nulli voltage, initium recordationis defectus terrae
• Collectio et processus recordationis undarum, et determinatio integralis defectus
• Accessus securus ad principalem stationem distributionis potentiae
a. Utitur ut dispositivum monitoring insulationis grounding stationis
b. Utitur ut dispositivum monitoring insulationis grounding intra stationem
c. Non dependet a statione magistra ad completionem defectus
Compositio Systematis Intelligentis Monitoring Conditionis Reticuli Distributionis Basata in Mensura PMU

Scenarii Usus Reticuli Distributionis

Usus Typicus PMU - Assessio Conditionis Lineae

Usus Typicus PMU - Recordatio Distributa Undarum

Data recordationis omnium punctorum monitoring in linea et statione sunt munita tempore absoluto ad microsecondo. Quaelibet dispositiva potest triggerare recordationem quando initia praescripta sunt satis facta. Praebet "instantaneam" totius rete basata in recall tempore cuiuslibet eventus in loco quocumque usque ad data recordationis omnium sensorum. Praebet data globalia pro analysis detailata eventuum et facilitat inversionem processus, traceabilitatem, et praevidentiam status abnormalis, etc.
Usus Typicus PMU - Monitoring Qualitatis Potentiae

Sensor potest calculare et reportare harmonicas in real time. Basatus in data synchronous latis areae, variis indicibus qualitatis potentiae sicut imbalance triphase, frequensia rete et ratio mutationis frequensiae, et pollutio fontis oneris potest locari convenienter.
Usus Typicus PMU - Anti-furtum Electricitatis

Secundum data oneris lateris high-voltage usuaris et formam undarum currentis, characteristica oneris analysantur et identificantur, et comportamentum electricum usuaris terminalis monitoratur, quod uti potest pro monitoring remote et diagnosi status dispositivorum electricorum.
Usus Typicus PMU: Monitio Defectus, Traceabilitas et Inversio Processus

Monitio:
• 2017-10-30 12:15:39:081719, linea 115, columna 1# 64#, phase A ad terram
• 2017-10-30 12:15:39:093125, linea 117, columna 29#, phase B grounded short circuit, flumen peak superat 1000A
• 2017-10-30 12:15:39:115468, Linea 115, inter columnas 1# et 64#, phase A et C short circuit, Flumen peak in columna 1# superat 5000A Feedback campi et inversio processus defectus:
• Accidit accidente collisionis automobilis in columna 52# linea 115
• Inspectio deprehendit signum ustionis in cabinetu cabilis ubique post columnam 29# linea 117
• Coniecturam facit phase A conductoris lineae 115 decidit de bracchio transversali et causat grounding, et voltus electricus non-defectus crescit, quod ducit ad breakdown insulationis weak point phase B post columnam 29# lineae 117, formans short circuit phases A et B differentium lineae et generans flumen peak super 1000A
• Post decem millisecondes, phase C conductor in columna 52# lineae 115 etiam decidit de bracchio transversali, causans short circuit Phase A et C. Quando peak fluminis short-circuit superat 5000A, protection relais ad outlet lineae operatur. Post trip switch, systema normaliter operatur, indicans quod insulatio originalis breakdown point columnae 29# lineae 117 restituitur.
Usus Typicus PMU: Locatio defectus disconnectionis grounding

• 2018-10-05,15:27:45:395312,primum monitio, notitia assignationis recepta.
“Notitia assignationis: 10kV Section 2 Phase A connectitur ad terram ad 15:29” “Notitia assignationis: 10kV Section 2 Phase A grounding desinit ad 15:47 ”
• Patrol ad confirmandum rumpere 127-1-28# branch lineae 121
• Temporalis inventio contactus fili rupti, ad evitandum viatores appropinquare electrocutio. Coniecturam facit ground jitter conductoris insulati rupti causat plures grounding. Post retractio nucleus metallici in stratum insulati, operatio phase loss resultabit in bus voltage rediens ad normale
• Durante hoc tempus, typhonus "Connie" pertransivit, ideo coniecturam facit disconnectio lineae fuit causa typhoni.
Usus Typicus PMU: Big Data + AI Identificatio Guida ad Inveniendum Commutatores Defectus

Est Systema Small resistance grounding, configuratio sensoris PMU.
totus processus identificationis et confirmationis defectus:
• 2020.11.25 - 2021.2.5, linea C28YC habuit 5 monitiones grounding, et omnes monitiones eadem characteristica, sed punctum defectus non potuit inveniri durante inspectione in situ.
• AI identificavit match inter characteristica secunda semicycli et forma undarum in database historica, et deduxit esse defectus commutatoris.
• Die 5 Februarii 2021, personale in situ habuit target in mente et invenit defectus commutatoris in columna 84.
Usus Typicus PMU: Monitio Insulationis Lineae - Causa: Catastropha Meteorologica

Modus Grounding Lineae Neutralis: bus 1 arc suppression coil, bus 2 ungrounded PMU Sensor Layout Details:

Tempora monitionis systematis: 13 tempora
Processus evolutionis defectus: post meridiem die 13 Augusti 2019, fuerunt 13 perturbationes, omnes indicantes quod occurrerunt in eodem sectione lineae. Sequens nulli voltage crescit continue ab 20V initio monitionis ad 30V finis. Sequens nulli currentis crescit ab 3A ad 5A, et insulatio lineae deterioratur. Propter accumulationem task emergency repair causata typhono unum diem ante, prioritas monitionis et eliminationis defectus fuit differenda. Post 9 horas deterioratio in short circuit, actio protectionis trip, resultans in power failure.
Usus Typicus PMU: Monitio Insulationis Lineae - Causa: Conflictus cum Arboribus

A hora 21 die 2020.5.25, fere centum eventus perturbationis tenuis percepti sunt, omnes in eodem loco.
Resistensia damping arc suppression coil in statione graviter calefacta est.
Personale maintenance patrulavit lineam secundum informationem monitionis.
Post clearance barrierae arboris et removal defectus, insulatio circa 14 punctis lineae perfecte restituta est et systema rediit ad normale.
Usus Typicus PMU: Monitio Defectus Lineae - Causa: Dammnum Avium Lineae Neutralis


Tempora monitionis systematis: 10
Processus evolutionis defectus: Ab 19:57:41 ad 22:48:18 die 7 Iulii 2018, decemina alarmorum levata est in eodem loco.
Tempus inter duos defectus fit brevius et frequentia fit altior, quod ostendit tendentiam ad evolvendum in defectus permanentes uniphase grounding. Circa horam 10:50, personale maintenance manu commutatoris in situ traxit, destruxit nido avium in sectione defectus, clausit commutatoris ad restituendum transmissionem potentiae, defectus desivit.
Usus Typicus UCMU : Monitio Defectus Equipmenti - Causa: Dammnum Externa Vi Cabilis

Modus grounding lineae neutralis: grounding per arc suppression coil SMS tempora monitionis: 1
Processus evolutionis defectus: Multiples grounding instantanea occurrerunt ab 15:22 die 24 Aprilis 2020, et systema plurima informationem monitionis impulit. Ad evitandum frequentem monitionem SMS causata perturbatione instantanea, systema ponit conditionem tres tempora grounding instantanea intra 20 minutos ut conditionem impulsionis monitionis SMS. Haec conditio potest meliorari per accumulationem et learning big data ponendo frequentiam. Ad 17:46, factum est permanentia grounding et duravit 55 minutos.
Usus Typicus PMU: Monitio Defectus Equipmenti - Causa: Deterioratio Insulationis Switchgear

Tempora monitionis systematis: 4
Processus evolutionis defectus: Durante periodum 2020.11.21 ad 2020.11.24, fuit 4 grounding instantanea et 1 grounding permanentia, et tandem evoluit in defectus short circuit. Systema registravit 5 defectus grounding cum eodem intervallo defectus, simili forma undarum et obviis characteribus arc pull, quae iudicatae sunt defectus insulationis in eodem loco.