Sistema awtomatiku ta’ protezzjoni tal-linja PMU huwa sistema ġdida ta’ awtomazzjoni ta’ distribuzzjoni tal-linja.
biex jilgħas is-suġġett attwali, partikularment il-problema tal-falt tal-terra.
li hija mbasata fuq Distributive Network Synchronous Phasor Measurement-μPMU.
PMU (phasor measurement unit), dispositiv jew modul indipendenti. Id-data tal-mixja tal-voltàġġ/korrent kollox huma mibbażati fuq timestammp ta’ BDS/GPS preċiż għal livell ta’ US.
Funzjonijiet bażi:• Fazur: amplitud, angolu fazjali,• Frequenza (f) u Varjazzjoni tal-Frequenza (△f/△t)

μPMU Diagramma tal-Arkitettura ta’ l-Hardware
Sistema ta’ Mifteħ fil-Area Larga (WAMS)
• Il-misjurijiet tal-PMU huma assolutament sinkronizzati mal-Ħin Standard tas-Silġ
• Sinkronizzazzjoni ta’ misjurijiet fil-area larga ta’ multi PMU iminstallati f’postijiet differenti
• Eżpressjoni matematika tal-senjal tal-voltàġġ/korrent:

Sensor tal-Korrent Overhead i-WCS – Single Channel Current PMU
Soluzzjoni għall-problemi tal-reti tal-distribuzzjoni mbasata fuq il-PMU tal-rete tal-distribuzzjoni u teknoloġija ta’ misur għarraf sinkronizzat fil-area larga.
• Aċquisizzjoni tal-korrent b’preċiżjoni u frequenza ħafiża
• Sincronizzazzjoni fil-area larga, induzzjoni tal-potenza
• Installazzjoni viva, protezzjoni IP67
• Supporta flus tal-potenza bidirezzjonali jew operazzjoni ta’ rete anellu
• Komunikazzjoni 3G/4G/ 5G:
a. Rapport periodiku ta’ kwalunkwe armoniku
b. Avvenimenti lokali jiġġibu l-upload tad-data
c. Call u test ta’ data speċifiċa minn dawk remota

• 1μs Sincronizzazzjoni fil-area larga
• 12.8kHz Frequenza tal-mixja
• 60 min Registrazzjoni u riproduzzjoni tal-onda
• 0.5 Aċċessità ta’ misur
• 3.5A Kurrent operattiv minimu ta’ funzjonalità kollha
Cable Type Current Sensor RCMU – Multichannel Current PMU

RCMU - Sensor tal-korrent tal-kablu sottoterrenu
• 1μs Sincronizzazzjoni fil-area larga
• 12.8kHz Frequenza tal-mixja
• 0.5 Aċċessità ta’ misur
• 60 min Riproduzzjoni tad-data
• 3 misur tal-korrent
• Trasmissjoni remot wireless/wired
• Jikkoġġi tri-faz tal-korrent, bħal prinċipju tal-tip overhead, addattat għal ring main unit, switching station, substation.
• Sincronizzazzjoni fil-area larga, induzzjoni potenza, jew fornituri ta’ potenza DC 24V/48V
• Algoritmu lokali ta’ deċiżjoni tal-falt bażat fuq il-korrent:
a. Sovrapass tal-korrent ta’ short-circuit
b. Sovrapass tal-korrent zero sequenzjali
c. Korrent fazjali asimmetriku
• Registrazzjoni tal-ondata mixta, supponi lokazzjoni distributiva tal-falt
• Supponi flus tal-potenza bidirezjonali jew operazzjoni ta’ rete anellu
• 3G/4G/5G jew komunikazzjoni tal-riz
Bus Collecting Unit BDCU – Single/Multiple Voltage PMU


Tip Intern u Tip Estern
• Fornituri ta’ potenza AC 220V/DC 24V • Fibra ottika, wired, wireless
• IEC 60870-5- 101/104/DNP3 • 300 sensors tal-korrent jistgħu jiġu aċċessati Aċquisizzjoni tal-Voltàġġ:
• 1μs Sincronizzazzjoni fil-area larga
• 1.0 Aċċessità ta’ misur
• 12.8kHz Frequenza tal-mixja
• 60 min Riproduzzjoni tal-registrazzjoni tal-ondata
Għal falt tal-grounding ta’ faza waħda bl-kurrent tal-terra akbar mill-1A, l-aċċessità ta’ detezzjoni u lokazzjoni hi 100%, b’subjettività 0
• Jikkoġġi voltàġġ zero sequenzjali, ibda l-registrazzjoni tal-falt tal-terra
• Jikkoġġi u jipproċessa l-registrazzjoni tal-ondata, u jdetermina l-falt komplutament
• Aċċess swiġġ tal-potenza distributtiva prinċipali
a. Uża bħala monitor tal-insulazzjoni grounding tal-stazzjoni
b. Uża bħala monitor tal-insulazzjoni grounding intern stazzjoni
c. Ma jidherx fuq il-stazzjoni prinċipali biex ikmpli tfalt
Il-Komposizzjoni tal-Sistema ta’ Monitoragg ta’ Stat ta’ Distribuzzjoni Intelligenti Bazata fuq Misur PMU

Skeneriji ta’ Użu tal-Rete ta’ Distribuzzjoni

Użu Tipiku tal-PMU - Assessjar ta’ Stat tal-Linja

Użu Tipiku tal-PMU - Registrazzjoni Distributta tal-Onwa

Id-data tal-monitoraggi ta’ kwalunkwe punt fit-telfa u fil-stazzjoni hija etikitjata b’ħin assolut għal livell ta’ mikroskond. Kwalunkwe dispositiv jista’ jiġġibu l-registrazzjoni meta jsiru l-kundizzjonijiet ta’ avviż predefiniti. Jipprovdi "snapshot" tal-riz intera bsad ta’ recall tal-ħin ta’ kwalunkwe avveniment f’l-ogħo post up to l-data registrata ta’ kwalunkwe sensor. Jipprovdi data globali għal analisi dettagljata ta’ avvenimentijiet u jifacilita inversion, traceability, u warning ta’ stat anomalu, etc.
Użu Tipiku tal-PMU - Monitoragg tal-Qwalità tal-Potenza

Użu Tipiku tal-PMU - Anti-stealing tal-Elettricità

Meta tanalizza u tiddeffenda l-caratteristici tal-load mid-data tal-waveform tal-korrent tal-parti ta’ alta voltàġġ, tmonitora il-behavior elettriku tal-utent terminal, li jista’ jiġi użat għal monitoring u diagnosi ta’ status ta’ ekiparienti elettrika remotely.
Użu Tipiku tal-PMU: Avviż tal-Falt, Traceability u Inversion tal-Proċess

Avviż:
• 2017-10-30 12:15:39:081719, line 115, pole 1# 64#, phase A to ground
• 2017-10-30 12:15:39:093125 , line 117, pole 29#, phase B grounded short circuit, peak flow exceeds 1000A
• 2017-10-30 12:15:39:115468 , Line 115, between poles 1# and 64#, phase A and C short circuit, Peak current at pole 1# exceeds 5000A Field feedback and fault process inversion:
• A car collision accident occurred at pole 52# on line 115
• The inspection found a burn mark in the cable cabinet somewhere behind the pole 29# on line 117
• Speculating that phase A conductor of line 115 falls down the cross arm and causes grounding, and the electric voltage of the non-fault phase increases, which leads to the breakdown of the insulation weak point phase B behind the pole 29# of line 117, forming the short circuit of the phases A and B of different lines and generating the peak current over 1000A
• After tens of milliseconds, the phase C conductor at the pole 52# of Line 115 also falls off the cross arm, causing short circuit of Phase A and C. When the peak of short-circuit current exceeds 5000A, the relay protection at the outlet of the line is operated. After the switch trips, the system runs normally, indicating that the insulation of the original breakdown point of the pole 29# of the line 117 is restored.
Użu Tipiku tal-PMU: Lokazzjoni tal-Falt tal-Grounding tal-Disconnessjoni

• 2018-10-05,15:27:45:395312, First alarm, the assignment notice is received. "Allocation notice: 10kV Section 2 Phase A is connected to the ground at 15:29" "Allocation notice: 10kV Section 2 Phase A grounding disappear at 15:47"
• Patrol to confirm the break of 127-1-28# of Line 121 branch
• Timely discovery of broken wire contact, to avoid passers-by close to the electric shock. It is speculated that the ground jitter of the broken insulated conductor causes multiple grounding. After the metal core is retracted into the insulation layer, the phase loss operation will result in the bus voltage returning to normal
• During this time, typhoon "Connie" passed through, so it is speculated that the disconnected line was caused by typhoon.
Użu Tipiku tal-PMU: Big Data + AI Identification Guide to Find Fault Switches

It is Small resistance grounding system, PMU sensor configuration.
whole process of fault identification and confirmation:
• 2020.11.25 - 2021.2.5, C28YC line had 5 grounding alarms, and all the alarm had the same characteristics, but the fault point could not be found during on-site inspection.
• The AI identified a match between the characteristics of the second half of the cycle and a type of waveform in the historical database, and deduced that it was a switch defect.
• On February 5, 2021, the on-site personnel had a target in mind and found the switch fault at pole 84.
Użu Tipiku tal-PMU: Avviż tal-Insulazzjoni tal-Linja - Raġuni: Diżgrazzja Meteoroloġika

Mod Neutral Grounding tal-Linja: bus 1 arc suppression coil, bus 2 ungrounded PMU Sensor Layout Details:

Numeri ta’ Avviżi tal-Sistema: 13
Proċess ta’ Evoluzzjoni tal-Falt: f’tarax fil-pomer ta’ 13 Agost 2019, kien hemm 13 disturbs, kollox indikaw li ġew fis-sekonda stess tal-linja. Il-voltàġġ zero sequenzjali kien jirkupru kontinwament mill-20V fil-bidu tal-avviż sa 30V fil-fine. Il-korrent zero sequenzjali kien jirkupru mill-3A sa 5A, u l-insulazzjoni tal-linja kienet tiġi peggju. Minħabba l-backlog ta’ task ta’ emergency repair causat mill-ħarġ tal-typhoon il-ġimgħa qabel, il-priorità ta’ l-avviż u l-eliminazzjoni ta’ l-defetti kienet tipposta. Wara 9 orijiet, il-falt kien jevolwi f’short circuit, il-protezzjoni kienet tieħu l-azione, il-switch kien jagħmel trip, u s-sistema kienet tirkupru l-operazzjoni normale, indikanti li l-insulazzjoni tal-punt originari tal-breakdown tal-pole 29# tal-linja 117 kienet tirgħad.
Użu Tipiku tal-PMU: Avviż tal-Insulazzjoni tal-Linja - Raġuni: Konflitt ma’ l-Isħagħ

Mill-21 o'clock ta' 2020.5.25, kien hemm għoxrin disturbjuts żgħar, kollox kienu ssiru fil-post stess. Il-resistanza ta’ dampening tal-arc suppression coil fis-stazzjoni kienet tinsa serjusa. Il-personnel tal-manutenzjoni kien jpatrolla l-linja skont l-informazzjoni tal-avviż. Wara li kkanjġjaw l-barriers tal-isħagħ u l-defetti, l-insulazzjoni ta’ madwar 14 punkti tal-linja kienet tirgħad totalment u s-sistema kienet tirkupru l-operazzjoni normale.
Użu Tipiku tal-PMU: Avviż tal-Falt tal-Linja - Raġuni: Danni tal-Birds


Numeri ta’ Avviżi tal-Sistema: 10
Proċess ta’ Evoluzzjoni tal-Falt: Mill-19:57:41 sa 22:48:18 ta’ 7 Julju 2018, kien hemm dozzini ta’ avvisi f’post waħid. Il-ħin bejn it-tnejn falt kien jkurci u l-frekwenza kienet tirkupru, li indikaw trend ta’ evoluzzjoni f’fault permanenti ta’ grounding ta’ faza waħda. Qabel 10:50, il-personnel tal-manutenzjoni kien jagħmlu switch manualment fuq is-sit, iddestru n-nid tal-birds f’dan is-silġ, wara kkanjġjaw is-swith u rikupraru l-trasferiment tal-potenza, il-falt kien jżomm.
Użu Tipiku tal-UCMU : Avviż tal-Falt tal-Equipament - Raġuni: Danni tal-Forza Esterna

Mod Neutral Grounding tal-Linja: neutral grounding through arc suppression coil SMS warning times: 1
Proċess ta’ Evoluzzjoni tal-Falt: Kkelim kbir ta’ grounding momentani kien jissodisfa minn 15:22 ta’ 24 April 2020, u s-sistema kien tpoġġi informazzjoni ta’ avviż. Biex timniex mill-avvisi ta’ messaġġ ta’ short frequenti minn disturbs momentani, s-sistema setta tat-tliet grounding momentani f’20 minuti bħal kondizzjoni għal poġġi tal-avviż tal-messaġġ. Din il-kondizzjuna tista’ tkun tmilġħa permezz tal-kumulazzjoni u l-apprendiment ta’ big data. Sa 17:46, kien permament grounding u ddurar 55 minuti.
Użu Tipiku tal-PMU: Avviż tal-Falt tal-Equipament - Raġuni: Deterioration tal-Insulazzjoni tal-Switchgear

Numeri ta’ Avviżi tal-Sistema: 4
Proċess ta’ Evoluzzjoni tal-Falt: Fl-period ta’ 2020.11.21 sa 2020.11.24, kien hemm 4 grounding momentani u 1 grounding permanenti, u infine evolvija f’fault ta’ short circuit. Is-sistema kienet tregistra 5 faults ta’ grounding b’interval ta’ falt identiku, waveform simili u karattrističi tal-arc pull evidenti, li kienu judġġa bħal insulazzjoni ta’ falt fil-lokalità stess.