• Product
  • Suppliers
  • Manufacturers
  • Solutions
  • Free tools
  • Knowledges
  • Experts
  • Communities
Search


PMU háðnámgilds dreifilyklar á sjálfsætis kerfi

PMU dreifingalína verndarvæði er nýtt dreifingalínu væðakerfi.

til að leysa núverandi vandamál, sérstaklega jörðavillur.

sem byggist á dreifneti samhliða fasaviðmælingu -μPMU.

PMU (phasor mælanó), óháð tæki eða eining. Spennu/straumur sýnigögn hafa allar BDS/GPS tímaskrár með nákvæmni á mikrosekúndustigi.

Grunnföll: • Fasur: styrkur, horn, • Tíðni (f) og breyting á tíðni (△f/△t)

μPMU Hlutverkakröfu Sniðmynd

Stórsvæðis mælanet (WAMS)
• PMU mælingar eru alveg samhliða heimsvísnum tíma (UTC)
• Stórsvæðis samhliða mæling með margum PMU í ólíkum staðsetningum
• Stærðfræðilegt útrydd spenna/straums tilgreining:

Höfuðstraumssensor i-WCS – Ein viðburður straum-PMU

Lausn fyrir dreifnetvandamál sem byggist á dreifneti PMU og stórsvæðis samhliða fasaviðmælingu.

• Hágæða og háfrekastofnun straumsgreining
• Stórsvæðis samhliða, orka induktion
• Lifandi uppsetning, IP67 vernd
• Stuttu tvívægða orkustraum eða hringnet hreyfingu
• 3G/4G/ 5G skilaboð:
a. Lokaverkefni hverja hermtón
b. Staðbundið atburður virkar gagnagreiðslu
c. Fjarverk umsókn og próf spefískt tímapunkt gagni

• 1μs stórsvæðis samhliða
• 12.8kHz sýnigögn frekari
• 60 mínútur bili og endurtekning
• 0.5 mæling nákvæmni
• 3.5A fullvirkja minnsti verkunarafl

Kabelgerð straumssensor RCMU – Margviðburðar straum-PMU

RCMU - undirjarðarkabel straumssensor

• 1μs stórsvæðis samhliða
• 12.8kHz sýnigögn frekari
• 0.5 mæling nákvæmni
• 60 mínútur gagni endurtekning
• 3 straum mæling
• Gervitunga/bundið fjarsenda

• Sækja þrjár straum, eins og yfirborð gerð, viðeigandi fyrir hringhlut, skiptastöð, undirstöðu.
• Stórsvæðis samhliða, induction power, eða 24V/48V DC aflafl
• Staðbundið villuvinnsla reiknirit á straumi:
a. Skammhlaup ofstraum
b. Jafnvægur straum
c. Ósamhengi straum
• Bili kallað mæling, stuttu dreifð villu staðfesting
• Stuttu tvívægða orkustraum eða hringnet hreyfingu
• 3G/4G/5G eða netfang skilaboð

Buss sameignar eining BDCU – Ein/margir spenna-PMU

Innri tegund og utanbúin tegund

• 220V AC/24V DC aflafl • Ljósleið, bundið, gervitunga
• IEC 60870-5- 101/104/DNP3 • 300 straumssensor geta aðgangs Spenna Greining:
• 1μs stórsvæðis samhliða
• 1.0 mæling nákvæmni
• 12.8kHz sýnigögn frekari
• 60 mínútur bili endurtekning

Fyrir einfaldur jörðavilla með jörðstraum meira en 1A, greining og staðfesting nákvæmni er 100%, með 0 ranga upplýsingar
• Sækja jafnvægur spenna, byrja taka á jörðavilla
• Sækja og vinna við taka á bili, og þverskilgreina villu almennt
• Öryggis aðgangur að aðal orkudreifistöð 
a. Notað sem aðal stöð jörðar geislar insuleringar athugasemdir
b. Notað sem stöð jörðar geislar insuleringar athugasemdir
c. Ekki árekstur aðal stöð til að ljúka villu

Samsetning af snertilegum dreifneti staða viðhorfsmælingu kerfi byggð á PMU mælingu

Dreifnet notendurit

Typical Use of PMU - Line Condition Assessment

Typical Use of PMU - Distributed Wave Recording 

Taka gögn alla mælingarstaða í línanum og stöð er merkt með alveg tími á mikrosekúndustigi. Eftirfarandi tæki getur virkað taka þegar forstilltar byrjunar skilyrði eru fullnægjandi. Veita "snapshot" af öllum neti á grundvelli tíma tilbókar hvaða atburður á hvaða stað til tekin gögn allra sensora. Það veitir almennt gögn fyrir í smáatriðum greiningu atburða og hjálpar við ferli innskipting, traðability, og varskoðunar óvenjuleg staða, o.s.frv.

Typical Use of PMU - Power Quality Monitoring

Sensorinn getur reiknað og skilað harmonics í rauntíma. Byggð á stórsvæðis samhliða gögnum, hægt er að reikna ýmis orku gæða mælingar eins og þrjár straum ójöfnu, net tíðni og tíðni breytingu hraða, og lokastaða mótmæli lausn.

Typical Use of PMU - Electricity Anti-stealing

Eftir notanda hágildis hliða lagastöðu gögn og straumur form, lagastöðu eiginleika greining og greining, og endurtekning endanotanda elektrísk áhorf, sem má nota til fjarskyggnar endurtekning og greining af stöðu elektrísk tæki.

Typical Use of PMU: Fault Warning, Traceability and Process Inversion

Varslu:
• 2017-10-30 12:15:39:081719, lína 115, stöng 1# 64#, A-phás til jörðar
• 2017-10-30 12:15:39:093125 , lína 117, stöng 29#, B-phás jörðar skammhlaup, toppafl yfir 1000A
• 2017-10-30 12:15:39:115468 , Lína 115, milli stanganna 1# og 64#, A og C phás skammhlaup, toppafl stöng 1# yfir 5000A Svæði feedback og villuferli inversion:
• Bílbrot gerðist á stöng 52# á línu 115
• Athugað var brúnmark í kabelskáp sumstað á bakvið stöng 29# á línu 117
• Spekulað er að A-phás leiðar af línu 115 falla af krossarm og gera jörðar, og elektrísk spenna af ekki-villu phás eykst, sem leiðir til brotnings á svæði B-phás á bakvið stöng 29# af línu 117, mynda skammhlaup A og B-phás mismunandi línur og framleiða toppafl yfir 1000A
• Eftir nokkrar millisekúndur, C-phás leiðar á stöng 52# af Lína 115 falla af krossarm, mynda skammhlaup A og C. Þegar topp skammhlaupsströmm yfir 5000A, relé skydd á útlet línu er virkað. Eftir skipta slökkt, kerfi keyrir venjulega, sem bendir að insulering á uprunalegu brotningspunkt stöng 29# af línu 117 er endurheimt.

Typical Use of PMU: Disconnection grounding fault location

• 2018-10-05,15:27:45:395312, Fyrsta varsla, úthluta tilkynning er móttekin.
“Úthluta tilkynning: 10kV Section 2 Phase A er tengdur við jörðina kl. 15:29”  “Úthluta tilkynning: 10kV Section 2 Phase A jörðar tenging dregur kl. 15:47 ”
• Ferð til að staðfesta brot af 127-1-28# af Lína 121 deild
• Timely discovery of broken wire contact, to avoid passers-by close to the electric shock. It is speculated that the ground jitter of the broken insulated conductor causes multiple grounding. After the metal core is retracted into the insulation layer, the phase loss operation will result in the bus voltage returning to normal
• During this time, typhoon "Connie" passed through, so it is speculated that the disconnected line was caused by typhoon.

Typical Use of PMU: Big Data + AI Identification Guide to Find Fault Switches

It is Small resistance grounding system, PMU sensor configuration.

whole process of fault identification and confirmation:
• 2020.11.25 - 2021.2.5, C28YC line had 5 grounding alarms, and all the alarm had the same characteristics, but the fault point could not be found
during on-site inspection.
• The AI identified a match between the characteristics of the second half of the cycle and a type of waveform in the historical database, and deduced that it was a switch defect.
• On February 5, 2021, the on-site personnel had a target in mind and found the switch fault at pole 84.

Typical Use of PMU: Line Insulation Warning - Reason: Meteorological Disaster

Line Neutral Grounding Mode: bus 1 arc suppression coil, bus 2 ungrounded PMU Sensor Layout Details:

System warning times: 13 times
Fault evolution process: on the afternoon of August 13, 2019, there were 13 disturbances, all indicating that they occurred in the same line section. The zero-sequence voltage rises continuously from 20V at the beginning of the warning to 30V at the end. The zero-sequence current increases from 3A to 5A, and the insulation of the line deteriorates. Due to the backlog of emergency repair tasks caused by typhoon one day ago, the priority of early warning and shortage elimination work has been postponed. After 9 hours deterioration into a short circuit, protective action trip, resulting in power failure.

Typical Use of PMU: Line Insulation Warning - Cause: Conflict with Trees

Starting from 21 o 'clock on 2020.5.25, nearly one hundred weak disturbance events were perceived, all of which occurred in the same place.
The damping resistance of the arc suppression coil in the station is seriously heated.
The maintenance personnel patrolled the line according to the warning information.
After clearing the tree barriers and removing the defects, the insulation of about 14 points of the line was completely restored and the system returned to normal.

Typical Use of PMU: Line Fault Warning - Cause: Bird Damage Line Neutral

System warning times: 10
Fault evolution process: From 19:57:41 to 22:48:18 on July 7, 2018, dozens of alarms were raised in the same place.
The time between two faults is getting shorter and the frequency is getting higher, which shows the trend of developing into permanent single-phase grounding faults. At around 10:50, the  maintenance personnel manually pulled the switch on the site, destroyed the bird's nest in the fault section, closed the switch to restore power transmission, the fault disappeared.

Typical Use of UCMU : Equipment Failure Warning - Cause: External Force Damage the Cable

Line neutral grounding mode: neutral grounding through arc suppression coil SMS warning times: 1

Fault Evolution Process: Multiple instantaneous grounding occurred since 15:22 on April 24, 2020, and the system pushed multiple warning information. In order to avoid frequent warning of short messages caused by instantaneous disturbance, the system sets three instantaneous grounding times within 20 minutes as the condition for pushing warning short messages. This condition can be improved through the accumulation and learning of big data by setting frequency. By 17:46, it became permanently grounded and lasted for 55 minutes.

Typical Use of PMU: Equipment Failure Warning - Cause: Switchgear Insulation Deterioration

System Warning Times: 4
Fault Evolution Process: During the period of 2020.11.21 to 2020.11.24, there was 4 instantaneous grounding and 1 permanent grounding, and it eventually evolved into a
short circuit fault. The system recorded 5 grounding faults with the same fault interval, imilar waveform and obvious arc pull characteristics, which were judged to be insulation faults at the same location.

03/21/2025
Mælt með
Procurement
Einkunn förmanna og lausna fyrir einfás dreifitránsmar í samanburði við hefðbundna tránsmar
1. Byggingarreglur og hagnýtingarþættir​1.1 Byggingardulköf sem áhrifa hagnýtingu​Einfasavarnar og þrefasavarnar sýna mikilvægar byggingardulköf. Einfasavarnar nota oft E-snið eða valdar kerastrengi, en þrefasavarnar nota þrefasker eða hópsnið. Þessi byggingardulki hefur bein áhrif á hagnýtingu:Valdir kerastrengir í einfasavarnum optímísa magnflæðisdreifingu, minnka hára stafhljóð og tengd tap.Gögn bera vitni að einfasavarnar með valda kerastrengi hafa 10%–25% lægri óhlaðna tap og ~50% lægri óhl
Procurement
Samþætt lausn fyrir einfaldtraða dreifitransformatora í orkuraforkunnotum: Teknologísk nýsköpun og margnotkun á mismunandi atburðum
1. Bakgrunn og údfordrur​Útvegs sameining endurnýjanlega orku (sólarorka (PV), vindorka, orkuspönn) leggur nýjar krav á dreifitransformatora:​Þróunarskynsamleikur:​​Útflutningur endurnýjanlegar orkur er veðuráhættuþeginn, sem krefst að transformatorarnir hafi hátt yfirbyggða orkuaðgerð og getu farið með breytingum.​Tónlagshækkun:​​Rafmagnsvæðingartæki (inverterar, hitastöðvar) bera tónlag, sem valdir flæði og aldur á tækinu.​Margfaldar atburðarstefnur:​​Þarf að vera samhæft mismunandi stefnum ei
Procurement
Einfaldar einfás tranformatora lausnir fyrir SUA: Spenna orkustöðu og veðuráhætturnar
1. Kerfisafn í orkugjöf Súðursýslunnar​1.1 ​Fjölbreytt spennaarmál​Flókin spennur á Súðursýslunni: Í bæjarbrúkum er oft notað 220V/230V einfás; í verksgögnum krefst 380V þrívís, en óvenjulegar spennur eins og 415V finnast í fjarlægum svæðum.Háspenna (HV): Venjulega 6,6kV / 11kV / 22kV (sumir lönd eins og Indónesía nota 20kV).Lágspenna (LV): Staðlað 230V eða 240V (einfást tveggja- eða þriggjaþráðakerfi).1.2 ​Loftslagi og rásarskilyrði​Há hiti (meðal ársins >30°C), há rauðvötn (>80%) og
Procurement
Pad-Mounted Transformer Solutions: Framleiðsla á yfirborði með tranformatorum: Þjóttari rýmisnotkun og kostnaðarvænningar í burtu við hefðbundna tranformatora
1. Samþættað útfærsla- og verndaratriði á bandarísku stöðuþverfum1.1 Samþættað útfærsluskipulagBandarísku stöðuþverfur nota sameiningarúpsgert skipulag þar sem aðalþættir - þverfurmið, spennuvafur, hágildisflýtispund, fússpund, skyldspund - eru samþætt inn í einn oljutank með olju sem skýrsl og kylning. Byggingin hefur tvö aðalhluti:​Frammynda:​​Hágildis- og lággildisvirknissvæði (með bogplugg tengingum sem leyfa virkni á framan).​Aftamynda:​​Oljustaðsvæði og kjölvingar (oljuhleðrað kjölakerfi).
Senda fyrirspurn
Sækja
Sækja IEE Business forrit
Notaðu forritið IEE-Business til að finna úrust, fá lausnir, tengjast sérfræðingum og taka þátt í samstarfi á sviði næringar hvar sem er og hvenær sem er—fullt stuðningur við þróun orkustofnana og viðskipta þinna