
1. Tarihi na Projekt
Sistem na kofa mai taimaka 15 na motoci masu sanka ta ƙarfin wata da suka yi aiki a wurin hanyoyi. A cikin ɗaya daga cikin hanyoyi, ana iya kara mafi yawan muhimmanci ga motoci kuma haɗa sa. Don ƙarin ingantaccen gudanar da taimakawa masu kyau a lokacin da motoci ya faru, an samu fadada tsari na VCF (Vacuum Contactor-Fuse) don taimakawa masu sanka ta ƙarfin wata da 6kV. Wannan bayanin ya bayyana matsayin na fadada, muhimmanci, da kuma tushen bayanai na VCF, wanda ke taimaka waɗanda suke aiki a wurin hanyoyi na ɗaya.
- Muhimmanci da Fadada Tsarin VCF
2.1 Na'urar Barazan da Fadada Tsarin Kwalbar
- Tsarin Baraza: Wannan baya ne ke amfani da VCF mai tsarin da za a iya kula da shi, a kunshi da ake kula da shi da kuma ake salo shi.
- Fadada Tsarin: An amfani da kompozit mai kwalbar da resin epoxy da Automatic Pressure Gelation (APG) don kwalbar, wanda ke zama da shi a kan vacuum interrupter, wanda ke zama da shi a kan resin epoxy, wanda ke zama da shi a kan kwalbar, mahimmanci, da kuma ƙarfin tsarin al'amuran.
- Mahimmiyar Gidajen: Mahimmiyar gidajen an yi aiki da shi da kula da shi da kuma ake kula da shi.
2.2 Ƙananan Tsarin da Muhimmancin Ingantacce
- Tsarin Baraza: VCF an samun tsarin mai yadda da high-voltage current-limiting fuses (wanda ke iya kara mafi yawan muhimmanci ga short-circuit currents) da VCX vacuum contactors, wanda ke iya aiki da shi har zuwa lokacin, wanda ke samun tsarin F-C.
- Muhimmanci: Yana da zaman lafiya mai yawa, ƙarfin tsarin, da kuma ƙarfin lafiya.
- Ingantacce: Ana amfani da shi a cikin power systems na thermal power plants, da kuma a cikin industries na metallurgical, petrochemical, da mining. Yana da zaman lafiya don kawo ƙarfin da kuma taimakawa masu sanka ga high-voltage motors, transformers, da induction furnaces.
2.3 Ƙarfin Ingantacce da Fadada Tsarin Lafiya
- Barazan na Cabinet: VCF withdrawable unit yana da tsarin da yake da circuit breaker withdrawable units a 800mm-width middle-mounted switchgear, wanda ke iya kula da shi saboda hakan.
- Barazan na Kula da Shiga: Tsarin withdrawable yana iya kula da shi da kuma ake kula da shi da kula da shi a kan cabinet.
- Barazan na Holding: Vacuum contactor zai iya amfani da electrical ko mechanical holding saboda abubuwan customer.
- Fadada Tsarin Phase-Loss: An amfani da phase-loss protection. Idan ana karɓe phase, fuse zai iya kula da shi da kuma ake kula da shi don kula da VCF motor circuit, wanda ke taimaka waɗanda suke aiki a wurin hanyoyi na ɗaya.
- Muhimmanci na Fadada Tsarin (7.2kV Rating)
|
Parameter
|
Value
|
|
Rated Voltage
|
7.2 kV
|
|
Rated Power Frequency Withstand Voltage (Phase-to-Phase and Phase-to-Ground)
|
32 kV
|
|
Rated Power Frequency Withstand Voltage (Isolation Gap)
|
36 kV
|
|
Lightning Impulse Withstand Voltage (Phase-to-Phase and Phase-to-Ground)
|
60 kV
|
|
Lightning Impulse Withstand Voltage (Isolation Gap)
|
68 kV
|
|
Rated Current
|
315 A
|
|
Maximum Rated Current of Compatible Fuse
|
315 A
|
|
Short-Circuit Breaking Current
|
50 kA
|
|
Short-Circuit Making Current
|
130 kA (Peak)
|
|
Transfer Current
|
4 kA
|
|
Mechanical Life (Electrical Holding)
|
500,000 operations
|
|
Mechanical Life (Mechanical Holding)
|
300,000 operations
|
|
Rated Operating Supply Voltage
|
220V AC/DC
|
- Principle na Taimakawa Masu Sanka
VCF taimakawa masu sanka an samun mafi yawan muhimmanci:
- Low Current Range (< 4kA): Vacuum contactor ke iya kula da shi don kula da shi da kuma ake kula da shi.
- High Current Range (> 4kA): High-voltage fuse ke iya kula da shi don kula da shi da kuma ake kula da shi.
- Curve Coordination: Protection curve na contactor an samun mafi yawan muhimmanci saboda curve na circuit breaker, wanda ke taimaka waɗanda suke aiki a wurin hanyoyi na ɗaya. Saboda hakan, an samu fadada tsarin da take da shi da kuma ake kula da shi don kula da shi.
- Muhimmanci na VCF vs. Vacuum Circuit Breaker
Don motor loads na ƙarfin faru da kula da shi, VCF yana da muhimmanci masu yawa saboda vacuum circuit breakers:
|
Comparison Dimension
|
VCF (Vacuum Contactor-Fuse)
|
Vacuum Circuit Breaker
|
|
Operational Life
|
Extremely high, up to 500,000 operations, ideal for frequent switching
|
Not suitable for frequent starts/stops, lacks high operational count advantage
|
|
Fault Interruption Speed
|
Very fast; fuse interrupts high fault currents within 10-15ms, effectively protecting motor insulation
|
Slower; fastest interruption takes ≥100ms, fault currents may cause thermal aging or damage to motor insulation
|
|
Switching Overvoltage
|
Low; vacuum contactor contacts use soft materials with low current chopping, minimizing impact on motor insulation
|
Higher; circuit breaker contacts use hard materials with high current chopping, leading to significant switching overvoltage
|
- Core of VCF Selection: Fuse Selection Guide
The performance of VCF hinges on correct fuse selection, considering the following factors:
Working voltage, working current, motor starting time, starts per hour, motor full-load current, and short-circuit current at the installation point.
6.1 Selection Rules and Steps
- Rated Voltage: The fuse’s rated voltage must not be lower than the system working voltage (7.2kV in this case).
- Rated Current Calculation:
- Use the formula: Iy=N×In×δI_y = N \times I_n \times \deltaIy=N×In×δ
- IyI_yIy: Equivalent current during starting (A)
- NNN: Starting current to full-load current ratio (typically 6)
- InI_nIn: Motor rated full-load current (A)
- δ\deltaδ: Comprehensive coefficient (based on starts per hour, n, from the table below)
|
Starts per Hour (n)
|
≤4
|
8
|
16
|
|
Comprehensive Coefficient (δ)
|
1.7
|
1.9
|
2.1
|
- Curve Matching: Plot the calculated IyI_yIy value and the motor’s starting time on the fuse manufacturer’s time-current characteristic curve. Select the fuse rated current corresponding to the curve immediately to the right of this point.
- Additional Check: The selected fuse’s rated current must be **> 1.7 times the motor’s full-load current**.
6.2 Selection Example
For a 7.2kV system with a directly started 250kW high-voltage motor:
In=30AI_n = 30AIn=30A, 16 starts per hour, starting time of 6s.
- Calculation: Iy=6×30A×2.1=378AI_y = 6 \times 30A \times 2.1 = 378AIy=6×30A×2.1=378A
- Selection: On the fuse time-current curve, locate the curve to the right of the point (378A, 6s), corresponding to a fuse rated current of 100A.
- Verification: 100A > 1.7 × 30A (51A), meeting the requirement. Thus, a 100A or higher-rated high-voltage motor protection fuse can be selected.
- Conclusion
From a comprehensive cost-performance analysis:
- While vacuum circuit breakers have lower procurement costs, their shorter operational life makes them unsuitable for frequent starts/stops, leading to higher long-term maintenance costs and failure risks.
- The VCF solution combines the advantages of vacuum contactors (long life, low overvoltage, suitability for frequent operation) and fuses (ultra-fast interruption of short-circuit currents), all at an economical overall cost.
- For the coal conveying system and other applications with frequent operation and heavy-load starting characteristics, VCF is an ideal solution offering high performance, reliability, and cost-effectiveness.