Layunin
Minimize ang Total Cost of Ownership (TCO) sa buong 30-year lifecycle ng kagamitan. Ito ay matutupad sa pamamagitan ng sistemang pag-optimize ng disenyo at intelligent operation & maintenance (O&M) strategies, na epektibong nagbibigay ng balanse sa initial investment at long-term operational expenditures.
I. Core Cost Optimization Strategies
- Design & Simulation Optimization
- Gamitin ang electric field simulation software (e.g., ANSYS, COMSOL) upang maging precise ang pagkalkula ng creepage distance at mechanical strength ng insulator. Optimize ang taas, shed profile, at wall thickness ng insulator. Bawasan ang redundant materials habang sumusunod sa IEC/CNS standards, na nagbabawas ng raw material costs ng 15%-20%.
- Walang Kompromiso sa Performance: Ang optimized designs ay lalampas sa lahat ng type tests, kabilang ang power frequency withstand, lightning impulse, at pollution tests.
- Insulator Selection Strategy
- Medium Pollution Areas (ESDD ≤ 0.1mg/cm²): Gamitin ang composite insulators (silicone rubber material) upang palitan ang traditional porcelain insulators:
✓ Bawasan ang bigat ng 40% → Bawasan ang mga gastos sa transportasyon at installation.
✓ Ang hydrophobicity ay nagpapahaba ng oras bago magkaroon ng pollution flashover → Bawasan ang pagsisikat ng insulator.
✓ Mas mahusay na crack resistance → Maiiwasan ang unplanned replacements dahil sa breakage ng porcelain.
Tumaas ang cost-effectiveness ng higit sa 30% kumpara sa traditional porcelain.
II. Key Technologies for O&M Cost Control
- Maintenance-Minimized Structural Design
- Core-Lifting Free Design: Ang sealed oil tank ay gumagamit ng bellows-type expansion device + dual sealing rings, na nag-eeliminate ng pangangailangan para sa core-lifting maintenance sa loob ng 30 years. Maiiwasan ang traditional core-lifting costs (≈ $5,000/instance) at outage losses.
- Modular Desiccant Unit: Ang respirator desiccant ay maaaring palitan on-site nang mabilis (< 30 minutes), na hindi nangangailangan ng special equipment. Bawasan ang O&M costs ng 70%.
- Intelligent Condition Monitoring
- Integrated Monitoring Interfaces: Pre-wired interfaces para sa oil pressure/moisture/oil level sensors (IEC 61850 compliant), na sumusuporta sa integration sa SCADA systems.
- Basic Configuration: Standard mechanical oil gauge, pressure gauge, at moisture indicator para sa "visual" rapid diagnostics.
- Benefits: Nagbibigay ng early warning ng insulation degradation, na nagbabawas ng unplanned outages ng ≥90% at nagbabawas ng fault repair costs ng 50%.
III. Long-Term Energy Savings & Reliability Assurance
|
Technical Measures
|
TCO Contribution
|
|
Low-loss Supermalloy Core
|
Nabawasan ang no-load loss ng 40% kumpara sa national standards. Ang 30-year energy savings ay nag-o-offset ng initial investment premium.
|
|
High-Reliability Branded Components
|
MTBF ≥ 500,000 hours. Nababawasan ang fault replacement costs at outage losses ($100k+/instance).
|
IV. TCO Quantification Model (Example)
Assume a 220kV VT project:
TCO = Procurement Cost + Σ(t=1 to 30) [Annual O&M Cost / (1+r)^t] + Outage Loss Costs
(Where r = Discount Rate)
Key Parameters:
- Energy Savings: Low-loss design saves ≈ 1,200 kWh/year (≈$600/year).
- Reliability Gain: High-reliability brand ensures fault rate ≤ 0.2% → Reduces outage losses by $500k over 30 years.
Result: Investment payback period < 8 years. Total lifecycle cost reduced by 18%-25%.
Summary
Ang solusyon na ito ay gumagamit ng apat na pillar – design-source cost reduction (material optimization), O&M structural innovation (core-lifting free + modularity), continuous energy consumption control (low-loss core), at fault prevention system (condition monitoring + high reliability) – upang i-compress ang total lifecycle cost ng outdoor VTs/PTs ng higit sa 20%, habang sinisiguro ang seguridad at reliabilidad. Ito ay nagbibigay ng ekonomikal na napapatunayan na solusyon na validated sa loob ng 30 years para sa power grid enterprises.
Reference Standards: IEC 60044-2, GB/T 20840.2, CIGRE TB 583
Applicable Scenarios: 110kV~500kV substations, renewable energy booster stations, high-pollution industrial areas.