Integrated Solution: Pad Mounted Transformers Enhancing Efficiency and Reliability in Distributed Solar PV Systems

Vziman
4yrs + staff 10000+m² US$0+ China

1. The Core Role of Pad Mounted Transformer (PMT) in Distributed PV Systems

A Pad Mounted Transformer (PMT) is a fully sealed, box-type transformer installed directly on a ground-level concrete pad (pad). It is suitable for voltage step-up and grid interconnection in distributed photovoltaic (PV) power plants. Its primary functions include:

  • Voltage Transformation:​Steps up the low-voltage electricity output from PV inverters (e.g., 0.8kV) to 10kV or 35kV to meet grid interconnection requirements.
  • System Integration:​Integrates high-voltage switches, protection devices, and metering equipment, reducing the footprint and enhancing system reliability.
  • Safety Isolation:​The fully enclosed design provides dustproof, moisture-proof, and corrosion-resistant capabilities, enabling operation in harsh outdoor environments.

2. Pad Mounted Transformer Key Technical Parameters and Selection Guidelines

2.1 Capacity Matching Principle

  • Capacity Calculation:​Must be slightly larger than the PV system's maximum output power (typically configured at 1.1~1.2 times the rating).
  • Example: A 19.9MW PV project equipped with 8 units of 2.5MVA PMTs (total capacity of 20MVA).
  • Voltage Level:​Select 10kV or 35kV based on the grid connection point voltage (e.g., an 8.3MW project in Shanghai utilizes 10kV grid connection).

2.2 Core Selection Parameters

Parameter

Requirement

Efficiency

≥98.5%, reducing transmission losses

Protection Class

IP54 or higher (dustproof and waterproof)

Insulation Material

Epoxy resin cast dry-type transformer (fire-resistant, pollution-free)

Cooling Design

Forced air cooling or natural cooling, with temperature rise ≤85℃

2.3 Compatibility Design

  • Inverter Matching:​The input voltage range must cover the inverter's output voltage (e.g., 0.8kV → 10kV).
  • Protection Device Integration:​Built-in fuses, surge arresters (lightning arresters), and temperature sensors; interfaces for external anti-islanding protection and fault isolation devices.

3. Pad Mounted Transformer System Integration Schemes

Intelligent Monitoring Integration

  • Sensor Configuration:​Real-time monitoring of temperature, current, and voltage.
  • Communication Interface:​Supports Modbus or IEC 61850 protocol for integration into PV monitoring systems (e.g., Acrel-1000DP).
  • Safety Protection:

Anti-islanding device:Disconnects within 0.5 seconds after detecting grid power loss.

Arc detection:AI-enabled intelligent arc fault identification (e.g., Huawei solution).

4. Pad Mounted Transformer Typical Application Case Studies

4.1 19.​9MW Distributed PV Project

  • PMT Configuration:​8 units of 2.5MVA pad-mounted transformers, deployed near 4 substations for close connection to 10kV distribution rooms.
  • Results:​Annual power generation of 14.95 million kWh, system efficiency >80%, reduced cable length by 30%.

4.2 ​Shanghai 8.3MW Rooftop PV Project

  • Solution Features:
    • 5 PMTs (2 units of 2.5MVA + 2 units of 1.6MVA + 1 unit of 0.8MVA) matched to groups of inverters with different capacities.
    • Fiber optic ring network for data transmission, enabling remote power forecasting and dispatch response.

4.3 ​Environmental Interference Resistance Design

  • High Wind Areas:​Strengthened mounting bracket fixtures (e.g., wind load-resistant components).
  • High Humidity Environments:​Use anti-salt spray coatings (for coastal projects) and inverters with Potential Induced Degradation (PID) recovery function.

5. Economic Benefits and O&M Optimization

5.1 ​Investment Return (ROI):

  • Changchun 500kW Project:Annual generation 584,000 kWh, self-consumption rate of return 12.2%, payback period ≈5.3 years.

5.2 ​Operations & Maintenance (O&M) Strategy:

  • Intelligent Diagnostics:IV curve scanning for real-time fault component localization.
  • Preventive Maintenance: Overload risk alerts for transformers based on temperature data.
06/18/2025
Recommended
Analysis of Advantages and Solutions for Single-Phase Distribution Transformers Compared to Traditional Transformers
1. Structural Principles and Efficiency Advantages​1.1 Structural Differences Affecting Efficiency​Single-phase distribution transformers and three-phase transformers exhibit significant structural differences. Single-phase transformers typically adopt an E-type or ​wound core structure, while three-phase transformers use a three-phase core or group structure. This structural variation directly impacts efficiency:The wound core in single-phase transformers optimizes magnetic flux distribution, ​
Integrated Solution for Single Phase Distribution Transformers in Renewable Energy Scenarios: Technical Innovation and Multi-Scenario Application
1. Background and Challenges​The distributed integration of renewable energy sources (photovoltaics (PV), wind power, energy storage) imposes new demands on distribution transformers:​Volatility Handling:​​Renewable energy output is weather-dependent, requiring transformers to possess high overload capacity and dynamic regulation capabilities.​Harmonic Suppression:​​Power electronic devices (inverters, charging piles) introduce harmonics, leading to increased losses and equipment aging.​Multi-Sc
Single-Phase Transformer Solutions for SE Asia: Voltage, Climate & Grid Needs
1. Core Challenges in the Southeast Asian Power Environment​1.1 ​Diversity of Voltage Standards​Complex voltages across Southeast Asia: Residential use often 220V/230V single-phase; industrial zones require 380V three-phase, but non-standard voltages like 415V exist in remote areas.High-voltage input (HV): Typically 6.6kV / 11kV / 22kV (some countries like Indonesia use 20kV).Low-voltage output (LV): Standardly 230V or 240V (single-phase two-wire or three-wire system).1.2 ​Climate and Grid Condi
Pad-Mounted Transformer Solutions: Superior Space Efficiency and Cost Savings over Traditional Transformers
1.Integrated Design & Protection Features of American-Style Pad-Mounted Transformers1.1 Integrated Design ArchitectureAmerican-style pad-mounted transformers employ a combined design integrating key components - transformer core, windings, high-voltage load switch, fuses, arresters - within a single oil tank, using transformer oil as both insulation and coolant. The structure consists of two main sections:​Front Section:​​High & Low Voltage Operation Compartment (with elbow plug-in conne