RDK Three-Phase Electronic Auto Sectionalizer
RDK three-phase electronic sectionalizer: 12-40.5kV, 200-315A, lightning impulse 75-220kV, 1-4s short-time 10kA, making peak 16-25kA. For overhead-line fault isolation with upstream reclosers.
RDK three-phase electronic sectionalizer: 12-40.5kV, 200-315A, lightning impulse 75-220kV, 1-4s short-time 10kA, making peak 16-25kA. For overhead-line fault isolation with upstream reclosers.
RDK pole‑mounted three‑phase electronic sectionalizer adopts CT energy‑harvesting without external auxiliary supply, distinguishes temporary / permanent faults by counting upstream trips, with visible open gap, manual closing by insulated stick and maintenance‑free. It meets relevant IEC/ANSI sectionalizer standards with configurable pickup‑current & counting‑times.
Three-phase electronic pole mounted sectionaliser for 12kV 40.5kV systems, enabling fast fault isolation and enhanced overhead grid reliability.
Pole-mounted vacuum automatic sectionalizer for 12kV and 24kV lines, enabling smart fault isolation to improve grid reliability.
Rockwill voltage-time type intelligent sectionalizer complete set for 12kV distribution automation. Fault isolation, power restoration, remote monitoring via GPRS/fiber.
Не требуется внешний источник вспомогательного питания. Устройство получает энергию от встроенного трансформатора тока, выполняет обнаружение тока повреждения и реализует логику подсчета с помощью внутреннего микроконтроллера.
После устранения устойчивого повреждения операторы могут вручную включить его с помощью изолированной оперативной штанги. Замена запасных частей не требуется. Устройство автоматически сбрасывается, если повреждение носит временный характер и не достигло порогового значения счетчика.
Должны одновременно выполняться три условия: ток повреждения превышает уставку срабатывания; достигается заданное число срабатываний (1–4 раза); напряжение в линии пропадает, а остаточный ток составляет менее 300 мА.