RDK Three-Phase Electronic Auto Sectionalizer
RDK three-phase electronic sectionalizer: 12-40.5kV, 200-315A, lightning impulse 75-220kV, 1-4s short-time 10kA, making peak 16-25kA. For overhead-line fault isolation with upstream reclosers.
RDK three-phase electronic sectionalizer: 12-40.5kV, 200-315A, lightning impulse 75-220kV, 1-4s short-time 10kA, making peak 16-25kA. For overhead-line fault isolation with upstream reclosers.
RDK pole‑mounted three‑phase electronic sectionalizer adopts CT energy‑harvesting without external auxiliary supply, distinguishes temporary / permanent faults by counting upstream trips, with visible open gap, manual closing by insulated stick and maintenance‑free. It meets relevant IEC/ANSI sectionalizer standards with configurable pickup‑current & counting‑times.
Three-phase electronic pole mounted sectionaliser for 12kV 40.5kV systems, enabling fast fault isolation and enhanced overhead grid reliability.
Pole-mounted vacuum automatic sectionalizer for 12kV and 24kV lines, enabling smart fault isolation to improve grid reliability.
Rockwill voltage-time type intelligent sectionalizer complete set for 12kV distribution automation. Fault isolation, power restoration, remote monitoring via GPRS/fiber.
Es ist keine externe Hilfsstromquelle erforderlich. Es bezieht seine Energie aus dem integrierten Stromwandler und realisiert die Fehlerstromerkennung und Zähllogik über den internen Mikrocontroller.
Nach Beseitigung des Permanentfehlers können Bediener den Schalter manuell mit einer isolierten Bedienstange schließen. Es ist kein Austausch von Ersatzteilen erforderlich. Bei vorübergehenden Fehlern, bei denen der Zählenschwellenwert nicht erreicht wird, erfolgt eine automatische Rückstellung.
Drei Bedingungen müssen gleichzeitig erfüllt sein: Der Fehlerstrom überschreitet den Ansprechwert; die voreingestellten Zählvorgänge (1-4 Mal) werden erreicht; die Leitung verliert die Spannung und der Reststrom liegt unter 300 mA.