| Brand | ROCKWILL |
| Model NO. | Pole Mount Shunt Capacitor Bank System supplier |
| Rated voltage | 36kV |
| Rated capacity | 2500kVA |
| Series | Qpole |
The pole mount capacitor system is a complete shunt reactive power compensation solution designed for overhead distribution networks. It is applicable for medium voltage systems up to 36 kV. This system improves power factor near the load side, stabilizes system voltage, releases grid capacity and reduces network power loss.
It can be configured as fixed or switched banks according to load characteristics: fixed banks for stable constant loads, switched banks for fluctuating variable loads. The system adopts single-phase or three-phase capacitor units, with wiring schemes of grounded wye, ungrounded wye or delta.
The switched version integrates capacitors, vacuum switches and controllers, with optional current sensors, surge arresters and fuse cutouts.
The pole mount capacitor system injects reactive power into the distribution network to compensate inductive reactive power of loads. The fixed bank runs continuously; the switched bank automatically switches vacuum switches on and off under the controller according to voltage, reactive power, current and temperature signals, realizing dynamic reactive power adjustment. It suppresses voltage fluctuation, improves power factor and cuts active power loss of overhead lines.
We provide fully factory pre-assembled pole mount capacitor systems. All core components comply with IEC, ANSI, IEEE and CSA international standards. The galvanized steel or aluminum frame is ready for direct pole mounting.
High-voltage terminals are equipped with bird guards to avoid animal-caused short-circuits and improve outdoor operational safety. We support flexible configuration: fixed or switched schemes, multiple wiring forms and optional auxiliary components.
Each unit is fully tested before delivery, with integrated control, protection and communication functions. It is an all-in-one, one-stop reactive compensation package for distribution EPC and utility projects.
| Category | Specification | Parameter |
|---|---|---|
| General | Rated Power | 150 ~ 3600 kvar |
| Rated Voltage | Up to 36 kV | |
| Insulation Level | Up to 50/125 kV BIL | |
| Frequency | 50 Hz / 60 Hz | |
| Wiring Arrangement | Grounded Wye, Ungrounded Wye, Delta | |
| Quantity of Capacitor Units | 3 / 6 / 9 units | |
| Control Voltage | 120 Vac / 240 Vac | |
| Ambient Temperature | -50 ℃ ~ +55 ℃ (fixed banks) | |
| Frame Material | Galvanized Steel / Aluminum | |
| Structure Accessories | Pole bracket, lifting eyes, bird guards | |
| Control Mode | Fixed / Switched | |
| Applicable Standards | IEC, ANSI, IEEE, CSA | |
| Mounting Hardware | Supplied | |
| Capacitor Unit | Phase Type | Single-phase / Three-phase |
| Discharge Resistor | Built-in | |
| Total Loss | ≤0.15 W/kvar (including discharge resistors) | |
| Dielectric Material | Polypropylene Film | |
| Impregnant | Non-PCB Faradol 810 | |
| Tank Material | 409 Stainless Steel (304 available upon request) | |
| Bushing | Grey Porcelain | |
| Vacuum Switch | Continuous Capacitive Current | 200 A / 300 A / 400 A |
| Open / Close Time | <100 ms | |
| Mechanical Endurance | 50,000 operation cycles | |
| Indicator & Manual Trip | Included | |
| Junction Box | Enclosure | UV-resistant PVC, IP64 (NEMA 3) |
| Control Cables | Standard cables with Amphenol connector, custom cables available | |
| Control Voltage Transformer | Rated Power | Min. 1.5 kVA |
| Type | Oil-filled / Dry resin | |
| Controller | Operation Mode | Automatic / Manual |
| Control Logic | Voltage, var, current, temperature, schedule control | |
| Communication | USB, radio (50 m); optional DNP3.0 via RS232 / Ethernet | |
| Function | Programmable delay, anti-hunting, daily operation limit, data logging (≥10,000 records) | |
| Enclosure | Lockable stainless steel, IP54, powder coated | |
| Mounting | Pole bracket / Meter socket |
Power factor correction and voltage stabilization projects for utility grid.
Yes. Our pole mount capacitor bank system is pre-assembled and pre-wired in our factory as a complete package. Core components including capacitors, switches, control cabinet and frame are assembled and tested together before shipment. It greatly reduces field wiring work and shortens on-site construction time for your overhead distribution projects.
The integrated system supports IEC, ANSI, IEEE and CSA standards, which meets the requirements of North American utility grids. We can adjust component selection, insulation coordination and protection scheme according to local utility specifications. We can also provide corresponding test reports and documentation for utility approval review.
Yes. The controller reserves communication interfaces. If you do not need remote communication at the initial order, we can keep the hardware reserve. When you upgrade later, you only need to activate the communication function and match the protocol, without replacing the whole capacitor bank system. We support mainstream grid communication protocols.
All high-voltage live terminals are equipped with bird guards as standard. Besides, we can also provide extra anti-bird accessories such as anti-bird spikes and insulating shielding covers upon request. The frame and wiring layout are optimized to reduce risks of bird nesting and short-circuit in overhead pole environments.
Sure. Our engineering team can customize the protection and control logic according to the harmonic condition of your industrial grid. We will evaluate harmonic distortion level and set overcurrent, overvoltage and harmonic protection thresholds, to avoid resonance and protect the capacitor bank from harmonic damage.