| Brand | ROCKWILL |
| Model NO. | Qpole Series Pole mount capacitor system |
| Rated voltage | 36kV |
| Rated capacity | 2500kVA |
| Series | Qpole Series |
Qpole pole mount capacitor system is an economical solution for shunt reactive compensation on overhead distribution networks. The Qpole is suitable for use in networks up to 36 kV.
● Power factor correction close to customer loads
● Voltage stability
● Increased network capacity
● Cost savings through lower losses
The Qpole is available as a fixed or switched system depending on the network profile. Fixed systems are preferred in networks with constant loading, whilst switched systems are more suited toward networks with variable loading.
The fixed and switched systems utilize single phase capacitors arranged in grounded Y, un-grounded Y or delta configurations. Three phase capac-itors are also available.
The switched system utilizes the complete range of components including capacitors, vac-uum switches and controller. Optional equipment in-cluding current sensors, surge arrestors and fuse cut-outs are also available.
The Qpole is factory assembled in a galvanised steel or aluminium frame which is suitable for pole mounting. All high voltage wiring and outdoor bushing terminals are provided with protective bird guards for increased safety and reliability.
The Qpole is unique as it offers customers a complete ‘one stop shop’ solution which has all major components manufactured. Each compo- nent is manufactured to a relevant international standard.
| General | |
| Power | 150 ... 3600 kvar |
| Voltage | Up to 36 kV |
| Insulation level | Up to 50/125 kV BIL |
| Frequency | 50 or 60 Hz |
| Arrangement | Grounded Y, Ungrounded Y or Delta |
| Number of capacitors | 3, 6 or 9 units |
| Control voltage | 120 or 240 Vac |
| Temperature range |
−50 to +55 °C for fixed banks* |
| Frame | Galvanized steel or aluminium |
| Features | Pole bracket, lifting eyes, bird guards |
| Control options | Fixed or switched |
| Standards | IEC, ANSI, IEEE & CSA |
| Mounting hardware | Included |
| Capacitor | |
| model | Single or three phase |
| Discharge resistors | Built-in |
| Losses |
≤ 0.15 W/kvar including resistors |
| Dielectric | Polypropylene film |
| Impregnant | Faradol 810 non-PCB |
| Container | Stainless steel, 409 high grade (304 high grade available on application) |
| Bushings | Grey porcelain |
| Vacuum switch | |
| model | PS15, PS17, PS25, PS36 |
| Continuous current rating | 200 A, 300 A or 400 A capacitive |
| Open/close time | < 100 msec |
| Mechanical endurance | 50,000 paired operations (open/close) |
| Position indicator/trip lever | Included (manual open only) |
| Junction box | |
| Enclosure | PVC UV resistant, IP64 (NEMA 3) rating |
| Cables |
3 × 1.3 mm² (switches) |
|
1 × 1.3 mm² (VT) |
|
| 5-pin or 7-pin Amphenol connector | |
| Other cables can be supplied if requested | |
| Control Voltage transformer | |
| Model | equivalent |
| Power | Min 1.5kVA |
| Design | Oil filled or dry resin |
| Controls | |
| Model | CQ900 |
| Control | Automatic and manual |
| Schedule, volt, temp, var, current | |
| Overrides | |
| Communication | Unit configuration and data log transfer via USB interface |
| radio(50 m range) | |
| Optional DNP3.0 protocol enabled via RS232 or Ethernet | |
| Switch on/off delays | Programmable |
| Other features | Single or seasonal schedule |
| Anti-hunting | |
| Maximum daily operations | |
| Data logging | 10,000+ record logs |
| Enclosure | Lockable IP54, power coated, stainless steel |
| Mounting | Pole bracket or meter socket |
| Surge arrester (optional) | |
| Parameter | Value |
| Model | MWK |
| Nominal discharge current |
10 kA peak (8/20 µs) |
| High current impulse |
100 kA peak (4/10 µs) |
| Class | 2 |
| Short circuit rating | 20 kA/0.2 s |
| Energy capability | 5.5 kJ/kV of Uc |
| Material | Silicon rubber |
| Current sensor (optional) | |
| Ratio |
600 A: 10 V ± 2% |
| Insulator | Polymer concrete |
| Fuse cutout (optional) | |
| model | V Series |
| Rated breaking capacity | Up to 12 kA asym |
| Fuse link | Type K and T |
| Insulators | Porcelain or silicon rubber |
| Mounting bracket | NEMA or direct to pole |
| Loadbreak | Recommended for fixed banks only |
| *For switched banks, refer to non-capacitor component temperature ratings.For detailed information on each component, please refer to component product literature. | |