Primary distribution switchgear with no SF6 in the tank — G3 clean gas, dry air and conditioned-air RMUs plus air-insulated primary panels, from 12kV to 40.5kV, built for zero-GWP networks.

Primary SF6-free switchgear does the same job as a conventional primary SF6 ring main unit — receive, sectionalise and protect the feeders below a substation transformer — but replaces SF6 with a dielectric that has no global warming potential: G3 clean gas, dry air, conditioned air, or simply atmospheric air in air-insulated panels.
The switching medium does not change: sealed vacuum interrupters still break the current. Only the insulation changes, which is why an SF6-free board can carry the same 630–1250A and 20–31.5kA ratings as the SF6 unit it replaces.
The practical driver is regulatory and procurement, not performance. F-gas rules are progressively closing the market for new SF6 medium-voltage equipment, and utilities increasingly write "SF6-free" into tenders before the rules require it. Choosing the route early avoids redesigning the switch room later.
Three SF6-free routes, one voltage class. Each product links to its dedicated page with full specifications.
Sealed G3 clean-gas primary RMU covering 12kV to 40.5kV in one tank family, near-zero GWP with no F-gas reporting.
G3 clean-gas ring main unit for 33kV through 40.5kV primary distribution — sealed for life, no gas top-up.
REC-series eco-friendly gas-insulated RMU for 12kV distribution, 1250A busbar with SF6-free insulation.
Dry-air insulated RMU integrating LBS, VCB, earthing switches, CT/VT and protection relays in a sealed assembly, with IEC 61850 / DNP3 communication.
Pure air or nitrogen insulated RMU, maintenance-free with zero SF6, covering 12kV up to 36kV.
Conditioned-air, SF6-free primary RMU with sealed vacuum interruption — 2 ring incomers plus transformer feeder.
Conditioned-air primary switchgear with sealed VCB, panel types for incomer, feeder, metering, bus-tie and transformer protection. 36kV on request.

All four eliminate SF6. They differ in footprint, pressure, and how much of the switch room you have to rebuild.
| G3 clean gas | Dry air (sealed) | Conditioned air | Atmospheric air | |
|---|---|---|---|---|
| Dielectric | Fluoro-ketone gas mix | Dry air under pressure | Conditioned air in a sealed tank | Air at atmospheric pressure |
| GWP | Near zero | 0 | 0 | 0 |
| Footprint | Compact | Compact | Compact tank | Largest — needs a switch room |
| Pressure | Sealed, low pressure | Sealed, low pressure | Sealed, near atmospheric | No tank pressure |
| Best for | Closest drop-in for SF6 RMU | Coastal, humid, polluted sites | Indoor primary distribution | Substations with space and ventilation |
| ROCKWILL range | Primary Gas Insulated RMU (G3) G3 RMU 33/35/40.5kV Eco-Friendly GIS RMU 12kV |
Dry Air RMU 12–40.5kV Pure Air / N₂ RMU 12–36kV |
Primary Air Insulated RMU 12/24kV Primary Air Insulated Switchgear |
Metal-Clad AIS Panel 12kV Metalclad AIS Panel 24kV |
| Project situation | Recommended route | Why |
|---|---|---|
| Replacing an SF6 RMU in an existing room | G3 gas RMU | Same compact footprint and cable positions, minimal civil work |
| Tender explicitly requires zero GWP | Dry air / conditioned air | GWP 0 with no fluorinated gas at all |
| Coastal, humid or heavily polluted site | Dry Air RMU | Sealed tank immune to humidity and salt, IP65 option |
| New indoor substation with space | Primary Air Insulated Switchgear | Withdrawable VCB, easy maintenance, lowest equipment cost |
| Smart-grid / automation requirement | Dry Air RMU | IEC 61850, DNP3 and IEC 60870-5-101/104 built in |
Common clauses IEC 62271-1, circuit breakers IEC 62271-100, disconnectors and earthing switches IEC 62271-102, RMUs IEC 62271-103, metal-enclosed assemblies IEC 62271-200.
Dielectric, temperature-rise, short-circuit and mechanical endurance type tests at recognised laboratories; routine dielectric and operation tests on every unit.
Single-line drawings, gas data, IP ratings and IEC test reports issued with the offer, so the SF6-free claim can be verified by the reviewer.

Tell us the voltage class, single-line diagram and whether the project requires zero GWP. We will propose the right dielectric route with a type-tested datasheet and quote.
Primary distribution switchgear that performs the same duty as an SF6 ring main unit but uses a zero-GWP dielectric instead — G3 clean gas, dry air, conditioned air or atmospheric air — with vacuum interrupters still doing the switching.
No. Voltage, current and fault ratings are set by the vacuum interrupter and the tank design, not by the gas. ROCKWILL SF6-free units cover 12–40.5kV, 630–1250A and 20–31.5kA, matching equivalent SF6 models.
G3 is the closest drop-in for an existing SF6 RMU because the footprint barely changes. Dry air suits coastal, humid or polluted sites and adds smart-grid communication. Conditioned air is the economical choice for new indoor primary substations.
Usually yes if the replacement keeps the same tank envelope and cable termination positions — which is why G3 units are preferred for retrofit. Where space is generous, air-insulated panels can also be used with modified civil works.
IEC 62271-1 with IEC 62271-100, -102 / -103 and -200 depending on the switching devices and assembly type, supported by type-test reports and routine tests per unit.