| Brand | ROCKWILL |
| Model NO. | IEC Standard Gas Insulated Switchgear for Power Generation-252kV |
| Rated voltage | 252kV |
| Rated normal current | 3150A |
| Series | RHG |
The RHG-252 GIS is a high-voltage SF6 gas-insulated switchgear designed for 252kV power transmission and distribution substations. Composed of standard modular components with flanged joints, it enables flexible substation optimization through modular combinations while saving space.
The circuit breaker features a special arc-extinguishing chamber with spring operating mechanism. The self-developed three-position disconnecting and earthing switch integrates isolation and grounding functions. The three-phase encapsulated main busbar and compact design achieve a minimum bay width of 1670mm.
The GIS is KEMA type-tested with high parameter levels and advanced structural design. Insulation performance meets applicable IEC and GB requirements. The double-sealing-ring structure ensures an annual SF₆ leakage rate ≤0.1%. The product is suitable for cold, humid, salt fog, coastal, and high-altitude environments.
| NO. | Items | Units | Parameter value | |
|---|---|---|---|---|
| 1 | Rated voltage | KV | 252 | |
| 2 | Rated current | A | 2500/3150/4000 | |
| 3 | Rated 1 min power frequency withstand voltage (1min RMS) | Phase-to-phase,phase-to-ground | KV | 395 |
| Across the isolating distance | 460 | |||
| 4 | Rated lightning impulse voltage (peak) | Phase-to-phase,phase-to-ground | KV | 950 |
| Across the isolating distance | 1050 | |||
| 5 | Rated short circuit breaking current | KA | 50 | |
| 6 | Rated short-time withstand current/rated duration of short-time | KA/S | 50/3 | |
| 7 | Rated peak withstand current | KA | 125 | |
Due to the excellent insulation performance, arc extinguishing performance and stability performance of SF6 gas, GIS equipment has the advantages of small footprint, strong arc extinguishing ability and high reliability, but the insulation ability of SF6 gas is greatly affected by the uniformity of the electric field, and it is easy to have insulation abnormalities when there are tips or foreign objects inside the GIS.
GIS equipment adopts a fully enclosed structure, which brings the advantages of internal components without environmental interference, long maintenance cycle, low maintenance workload, low electromagnetic interference, etc., while also having problems such as complex single overhaul work and relatively poor detection methods, and when the closed structure is eroded and damaged by the external environment, it will further bring a series of problems such as water ingress and air leakage.
The insulating property of SF₆ gas relies on its stable molecular structure, which makes electron escape and collision ionization difficult under normal operating voltages, ensuring high insulation resistance. In GIS, insulation is precisely maintained by controlling gas pressure, purity, and electric field distribution to guarantee a uniform and stable electric field between high-voltage conductors and the grounded enclosure.