| Marca | ROCKWILL |
| Numerus Modeli | Commutator aeris alti voltaginis |
| Votum nominatum | 12kV |
| currus electricus nominatus | 630A |
| Frequenta nominata | 50/60Hz |
| Series | FKN |
Product Overview
Altae tensio aeris rupturae commutatores et eorum combinata apparatus electrica sunt indoor alta tensio apparatu pro AC 12kV, 50Hz. Haec commutator rupturae praebet alta specifica technica parameter et fida actionem. Basis formae mechanismi operationis est manuale spring-energia-storaginis typus, et potest etiam adhiberi electromagneti spring operans mechanismus. Super pneumatico arc-extinguendo principio, potest plures vicibus interrumpere absque substitutione arc-extinguendi tubi.
Commutator altae tensionis potest claudere, portare et aperire oneris currentes sub normalibus circuiti conditionibus, et habet facultatem claudendi brevis circuitus currentes et aperiendi brevis circuitus currentes intra specie definitum breve tempus.
Commutatores rupturae posse adhiberi cum terre interruptores. Terre interruptor habet idem brevis circuitus faciens capacitas sicut commutator rupturae, tamquam et dynamica et calor stabilis capacitas, et habet strictam mechanicam interlock cum commutatore rupturae, assecurans quod misoperation sit impossibile in structura.
Key Features
Cum FKN12 - 12 commutator rupturae adhibetur cum alta tensio limitans fusus (cum percussore) ad formandum commutator rupturae-fusus combinationem, servit ut supercarga et brevis circuitus protectio pro oneribus (sicut potentia transformatoribus). Cum una vel plures phase fusus exardescunt, tres phases commutator rupturae automaticiter aperiunt.
Commutator altae tensionis aptus est ad installationem in ring-main unit switch cabinets et alii species switch cabinets pro recipiendo et distribuendo electricam energiam.
Technical Parameters
Serial No. |
Name |
Unit |
Value |
1 |
Rated Voltage |
KV |
12 |
2 |
Rated Frequency |
Hz |
50 |
3 |
Rated Current |
A |
630 |
4 |
Maximum Rated Current of Fuse |
A |
100 |
5 |
Rated Active Load Breaking Current, Rated Closed-loop Breaking Current |
A |
630 |
6 |
Rated Short-time Withstand Current (2S) |
KA |
20 |
7 |
Rated Short-circuit Making Current, Rated Peak Withstand Current |
KA |
50 |
8 |
1min Power Frequency Withstand Voltage, Phase-to-phase and to-ground / Break |
KV |
42/48 |
9 |
Lightning Impulse Withstand Voltage (Peak Value), Phase-to-phase and to-ground / Break |
KV |
75/85 |
10 |
Rated Cable Charging Breaking Current |
A |
10 |
11 |
Rated Breaking of No-load Transformer |
KVA |
1250 |
12 |
Mechanical Life |
Times |
2000 |
13 |
Rated Breaking Transfer Current |
A |
1150 |
14 |
Rated Short-circuit Breaking Current of Fuse |
KA |
31.5 |
Main Mechanical Characteristics of Load Break Switch
Serial No. |
Name |
Unit |
Value |
Remarks |
1 |
Phase-to-phase Center Distance |
mm |
210 ± 3 |
|
2 |
Total Stroke of Conductive Rod |
mm |
215 ± 5 |
|
3 |
Distance Between Moving and Static Arc at Opening Position |
mm |
>160 |
|
4 |
Over-stroke of Electrical Contact of Moving Contact Rod |
mm |
42 ± 3 |
|
5 |
Just-Closing Speed |
m/s |
3.8 <sup>+0.7</sup><sub>-0.2</sub> |
|
6 |
Just-Opening Speed |
m/s |
>2.7 |
|
7 |
Three-phase Closing Asynchronism |
ms |
>10 |
Contact between moving contact rod and contact fingers |
8 |
Three-phase Opening Asynchronism |
ms |
>5 |
Separation between moving contact rod and contact fingers |
Altitude: Non supra 1000m.
Ambient Temperature: Maximum +40°C, Minimum -10°C.
Relative Humidity: Daily average non supra 95%, Monthly average non supra 90%.
Seismic Intensity: Minus 8 gradus.