| Brand | ROCKWILL |
| Series | ZHN |
| Rated voltage | 24 kV |
| Rated normal current | 15,000 A |
| Insulation level | 24 / 50 / 125 kV |
| Rated frequency | 50 / 60 Hz |
The Rockwill electric brake switch is designed for rapid electrical braking and shutdown of large hydro-turbine generating units. It connects the generator to a braking resistor to dissipate kinetic energy during the deceleration phase, providing a controlled and wear-free braking method compared to mechanical braking systems.
The equipment consists of three single poles, each in an individual enclosed metal enclosure mounted on a common chassis. The brake switch uses SF6 as the insulation and arc-extinguishing medium, with arcing contacts made of ablation-resistant copper-tungsten material for high electrical endurance. An earthing switch is integrated and uses air insulation with a motor operating mechanism.
The brake switch is equipped with a hydraulic spring operating mechanism, and all three poles are driven via a three-phase mechanical linkage. A pressure relief device is fitted at the top; if the internal gas pressure exceeds 1.2 MPa due to an abnormal event, the gas is safely released.
| Parameter | Value |
|---|---|
| Rated voltage (Ur) | 24 kV |
| Rated normal current (Ir) | 15,000 A |
| Rated frequency | 50 / 60 Hz |
| Insulation level (Um / PF / BIL) | 24 / 50 / 125 kV |
| Rated making and breaking current | 28,000 A |
| Braking current (load break capability) | 30,000 A |
| Mechanical endurance | 10,000 operations |
| Operating mechanism (brake switch) | Hydraulic spring |
| Operating mechanism (earthing switch) | Motor-operated |
| Insulating medium (brake switch) | SF6 |
| Insulating medium (earthing switch) | Air |
| Cooling method | Natural |
| Pressure relief threshold | 1.2 MPa |



Electric braking is controlled and wear-free, avoiding mechanical friction loss and frequent maintenance of mechanical braking systems.
It is designed for large conventional hydropower stations and pumped storage power plants with high-inertia hydro-turbine generating units.
Yes, it supports generator deceleration control for pumped-storage and conventional hydro stations.
This electric brake switch realizes energy dissipation through braking resistors. It achieves controlled deceleration without friction contact, so there is no wear on brake pads. It can shorten shutdown time, reduce routine maintenance work and avoid dust pollution caused by mechanical friction, which is especially suitable for large inertia hydro turbine units.
Yes. The air-insulated earthing switch is integrated within this complete set. It adopts motor-driven operation. After the brake switch opens, the earthing switch can provide reliable grounding isolation for maintenance work, matching the safety interlock requirements of hydropower station design.
The three poles share a mechanical linkage structure. The hydraulic spring mechanism drives all three phases together. This design ensures consistent and synchronous switching action of each pole, prevents phase asynchronous operation, and maintains stable braking performance during unit deceleration.