| Brand | ROCKWILL |
| Model NO. | Generator Circuit Breaker for Power Plant Protection |
| Rated voltage | 24kV |
| Rated normal current | 27000A |
| Series | RZHN |
The complete generator circuit breaker set is designed for large hydro, thermal and nuclear power generating units, providing protection and switching between the generator and the step-up transformer. It was appraised by the China Machinery Industry Federation and successfully applied in the Xiangjiaba project, achieving complete localization of large-capacity generator circuit breaker technology.
The set integrates current transformers, voltage transformers and lightning arresters with the circuit breaker, and each unit is equipped with intelligent online monitoring for conductor temperature, mechanical characteristics and insulating gas condition. The compact drive design, high insulation level and comprehensive pressure-relief protection ensure reliable power plant operation.
The product consists of three single poles, and each pole has an individual enclosed metal enclosure mounted on the same chassis.
Circuit breaker is equipped with hydraulic spring operating mechanism; The disconnector and earthing switch are equipped with motor operating mechanism; The driving modes are all three-phase mechanical linkage.
Each operating mechanism is installed on the side of the product close to the control cabinet.
SF6 is used as internal insulation and arc-extinguishing medium for circuit breaker, and adopts self-energy arc extinguishing principle. It is mainly composed of the main contact system, arc extinguishing system and driving system.
Air is used as insulation medium to isolate the break of the disconnector, the isolation moving contact adopts telescopic direct-acting structure, and the fixed contact adopts inner and outer two-layer contact finger structures, when closing, both the inner and outer surfaces of the moving contact are in contact with the contact finger, thus ensuring sufficient current capacity. Double guiding devices are used to ensure smooth closing of the moving contact.
Air is used as insulation medium to isolate the break of the earthing switch. The fixed contact is installed on the support of the main circuit, and the moving contact is installed on the bottom plate of the single pole enclosure.



160 kA intelligent generator circuit breaker not only has basic protection function, but also integrates potential transformer, current transformer, lightning arrester and other components. Each product is equipped with a set of intelligent on-line monitoring device to realize on-line monitoring of conductor temperature, mechanical characteristics of circuit breaker, SF6 gas condition and so on.
| NO | Item | Unit | Parameters | Remarks | |
| 1 | Rated voltage | kV | 24 | The product meets the service environment of 3,000m above sea level. | |
| 2 | Rated current | A | 27000 | ||
| 3 | Rated frequency | Hz | 50 | ||
| 4 | Rated insulation level | Short-time power frequency withstand voltage (1min) | kV | 80 | |
| Lightning impulse withstand voltage (peak) | kV | 150 | |||
| 5 | Rated short circuit breaking current | kA | 160 | ||
| 6 | Rated short circuit making current (peak) | kA | 440 | ||
| 7 | Mechanical life | Circuit breaker | times | 5000 | |
| Disconnector/Earthing switch | 10000 | ||||