| Brand | ROCKWILL |
| Model NO. | 40.5kV series SF6 gas-insulated switchgear |
| Rated voltage | 40.5kV |
| Rated frequency | 50/60Hz |
| Series | NG7 |
NG7-40.5 series SF6 gas-insulated switchgear is a new generation of miniaturized products designed and manufactured by Rockwill according to IEC 62271-200.It has a variety of combinations and can be flexibly extended, which not only meets the requirements of power distribution, but also meets the needs of various secondary distribution application for flexible compact switchgear. It is widely used in public power grids, rail transit, new energy E-house, solar farm, wind farm, data center and other new energy fields.
Product Advantages
Parameters
|
Item |
Unit |
Value |
||
|
Load switch unit (C) Circuit breaker unit (V |
Load switch unit (C) Circuit breaker unit (V |
|||
|
Rated voltage (IEC/GB) |
kV |
36 / 40.5 |
||
|
Rated frequency |
Hz |
50 (60) |
||
|
Rated normal current * |
A |
630(x1.1) |
630/1250(x1.1) |
|
|
Rated short-duration power frequency voltage (1min) |
To earth & between phases (IEC/GB) |
kV |
70 / 95 |
|
|
Across the isolating distance (IEC/GB) |
80 / 118 |
|||
|
Rated lightning impulse voltage |
To earth & between phases (IEC/GB) |
kV |
170 / 185 |
|
|
Across the isolating distance (IEC/GB) |
195 / 215 |
|||
|
Rated power frequency voltage of control and auxiliary circuits (1min) |
kV |
2 |
||
|
Rated short-time withstand current & duration ** |
kA |
25/4 (20/4) |
||
|
Rated peak withstand current ** |
kA/s |
63 (52) |
||
|
Rated short-circuit breaking current ** |
kA |
- |
25 (20) |
|
|
Rated short-circuit making current ** |
kA |
63 (52) |
||
|
Mechanical endurance |
Circuit breaker |
- |
- |
10000 |
|
Load switch / Disconnector |
5000 |
|||
|
Earthing switch |
3000 |
|||
|
Rated functional pressure for insulation and interruption (relative at 20°C) |
Mpa |
0.04 |
||
|
Minimum functional pressure for insulation and interruption (relative at 20°C) |
Mpa |
0.02 |
||
|
Gas leakage rate |
/year |
≤ 0.01% |
||
|
Degree of protection |
Gas tank |
- |
IP67 |
|
|
Gas tank |
- |
IP4X, IK10 |
||
|
Internal arc classification AFLR |
kA/s |
16/1, 20/1, 25/1 |
||
|
Altitude |
m |
≤ 5000 |
||
|
Dimension (Width x Depth x Height) *** |
mm |
420 x 1000 x 1650 500 / 550 x 1000 x 1650 |
420 x 1000 x 1650 500 / 550 x 1000 x 1650 |
|