• 27kV MV outdoor Auto Circuit vacuum recloser
27kV MV outdoor Auto Circuit vacuum recloser
$5000.00
Model
RCW-E27G/1250-25
RCW-E27G/800-20C
RCW-E27G/800-20
RCW-E27G/630-16C
RCW-E27G/630-16
RCW-E27G/400-12.5C
RCW-E27G/400-12.5
Basic info
Brand ROCKWILL
Model NO. 27kV MV outdoor Auto Circuit vacuum recloser
Rated voltage 27kV
Rated normal current 1250A
Rated short circuit breaking current 25kA
Power frequency withstand voltage 70kV/min
Rated lightning impulse voltage 150kV
manual closing No
Mechanical lock No
Series RCW
Product Detail

Description:

The RCW   series automatic circuit reclosers can use on overhead distribution lines as well as distribution substation applications for allvoltage classes 11kV up to 38kV at 50/60Hz power system.  and it’s rated current can reach 1250A.The RCW   series automatic circuit reclosers integrates the functions of control, protection, measurement, communication, fault detection, on-line monitoring of closing or opening.The RCW   series vacuum recloser is mainly combined with integration terminal, current transformer, permanent magnetic actuator and it’s recloser controller.

Features:

  • Optional grades available in rated current range.

  • With optional relay protection and logic for user selection.

  • With optional communication protocols and I/O ports for users to choose.

  • PC software for controller testing, setup, programming, updates.

Parameters:

image.png

image.png

External dimensions:

企业微信截图_17103058136732.png


Environmental requirement:

image.png

Product show:

正方形最新环氧聚脂带手和.png

 What are the key points for the selection of outdoor vacuum reclosers?

  • System Parameter Matching: Choose a recloser that matches the rated voltage, rated current, and short-circuit current levels of the power system. Ensure that the rated voltage of the recloser is equal to or higher than the system voltage, the rated current meets the requirements of the line load current, and the rated short-circuit breaking and making currents are greater than the maximum possible short-circuit current in the system.

  • Reclosing Performance Requirements: Consider the specific requirements of the power system for the reclosing function, such as the number of reclosures, reclosing time intervals, and reclosing success rate. Based on different application scenarios and power supply reliability requirements, select a recloser with appropriate reclosing performance. For example, for critical power supply lines, a recloser with a higher number of reclosures and flexible reclosing time intervals may be required.

  • Type of Operating Mechanism: Choose an appropriate operating mechanism based on actual needs. Spring-operated mechanisms are suitable for outdoor environments where high reliability is required and maintenance conditions are relatively poor. Permanent magnet-operated mechanisms are better suited for applications requiring high action speed and frequent operations.

  • Environmental Adaptability: Given the harsh conditions of outdoor environments, consider the environmental adaptability of the recloser. This includes weather resistance, pollution resistance, and water and dustproof performance. Selecting a recloser with good environmental adaptability ensures stable performance during long-term outdoor operation.

  • Brand and Quality: Choose well-known brands and high-quality recloser products. These products have strict quality control systems in design, manufacturing, and testing, ensuring the performance and reliability of the product. Additionally, good after-sales service is an important factor to consider when choosing a brand, as it ensures timely resolution of issues that may arise during equipment operation.

Know your supplier
ROCKWILL
Rockwill Electric Group Global Manufacturer of High voltage and medium-voltage power equipment and smart grid solutions. Headquartered in Wenzhou, China. Serving 100+ countries with quality, innovation, and trust. What We Offer: • HV-MV switchgear (VCB, SF₆ circuit breakers, RMU, GIS) • Distribution transformers and substations • Smart grid and monitoring systems • Solar, wind, EV charging, and energy storage solutions • EPC turnkey power projects Certified: ISO 9001 / ISO 14001 / ISO 45001
Main Categories
High voltage
Business Type
Design/Manufacture/Sales
Highest Annual Export (USD)
$150,000,000
Professional Experience
16 years
Workplace
108000m²m²
占位
占位
Related Products
Related Knowledges
Analysis of Partial Discharge Principle (1)
Analysis of Partial Discharge Principle (1)
Analysis of Partial Discharge Principle (1)Under the action of an electric field, in an insulation system, discharge occurs only in some regions and does not penetrate between the conductors with the applied voltage. This phenomenon is called partial discharge. If partial discharge occurs near a conductor surrounded by gas, it can also be called corona.Partial discharge can occur not only at the edge of a conductor but also on the surface or inside an insulator. The discharge occurring on the su
Leon
07/19/2025
What types of FACTS controllers are there?
What types of FACTS controllers are there?
According to the type of connection FACTS Controller with the power system, it is classified as;Series Connected ControllerShunt Connected ControllerCombined Series-Series ControllerCombined Shunt-Series ControllerSeries-Connected ControllersSeries controllers introduce a voltage in series with the line voltage, typically using capacitive or inductive impedance devices. Their primary function is to supply or absorb variable reactive power as needed.When a transmission line is heavily loaded, the
Edwiin
07/19/2025
What are FACTS and related technologies?
What are FACTS and related technologies?
FACTS (Flexible Alternating Current Transmission System) refers to a power electronics-based system that uses static devices to enhance the power transfer capability and controllability of AC transmission networks.These power electronic devices are integrated into conventional AC grids to boost key performance metrics, including:Power transfer capacity of transmission linesVoltage stability and transient stabilityVoltage regulation precisionSystem reliabilityThermal limits of transmission infras
Edwiin
07/19/2025
What are the differences between HVAC and HVDC?
What are the differences between HVAC and HVDC?
Difference Between HVAC and HVDCElectricity generated in power plants is transmitted over long distances to electrical substations, which then distribute it to consumers. The voltage used for long-distance power transmission is extremely high, and we will explore the reasons for this high voltage later. Additionally, the transmitted power can be in either alternating current (AC) or direct current (DC) form. Therefore, power can be transmitted using either HVAC (High Voltage Alternating Current)
Edwiin
07/19/2025
What are the Advantages of HVDC over HVAC?
What are the Advantages of HVDC over HVAC?
What are the Advantages of HVDC over HVAC?Electricity travels long distances before reaching consumers. Power plants, often remote, supply electricity through hundreds of miles and multiple substations. High-voltage transmission reduces line losses, with both AC and DC used. Though AC is familiar via utility poles and home outlets, HVDC offers unique advantages in power transmission.The goal of power transmission is to minimize losses and costs. While both face influencing factors, HVDC has more
Edwiin
07/19/2025
Is the neutral - point grounding method of the power grid of 110kV and above only the neutral - point direct grounding method?
Is the neutral - point grounding method of the power grid of 110kV and above only the neutral - point direct grounding method?
Neutral - Point Grounding Modes and Protection of Transformers in Power GridsFor systems ranging from 110 kV to 500 kV, an effective grounding method shall be adopted. Specifically, under all operating conditions, the ratio of zero - sequence reactance to positive - sequence reactance X0/X1 of the system should be a positive value and not exceed 3. Meanwhile, the ratio of zero - sequence resistance to positive - sequence reactance R0/X1should also be a positive value and not exceed 1.In 330 kV a
Leon
07/19/2025
×
Inquiry