Search


110 - 500kV Composite-Housed Line Surge Arresters

  • 110 - 500kV Composite-Housed Line Surge Arresters
  • 110 - 500kV Composite-Housed Line Surge Arresters
  • 110 - 500kV Composite-Housed Line Surge Arresters

Key attributes

Brand ROCKWILL
Model NO. 110 - 500kV Composite-Housed Line Surge Arresters
Rated voltage 220kV
Rated frequency 50/60Hz
Series YH10CX
Description

Description

110 - 500kV Composite-Housed Line Surge Arresters are specialized protective devices designed for high-voltage transmission lines operating within the 110kV to 500kV range. Encased in durable composite housings (typically silicone rubber), they integrate advanced metal oxide varistor (MOV) technology. Installed directly on transmission lines, these arresters serve as a critical defense against overvoltages caused by lightning strikes, switching transients, and other electrical disturbances. By rapidly diverting surge currents to the ground and clamping voltage levels to safe thresholds, they prevent damage to line components, minimize power outages, and ensure the stable and efficient operation of 110 - 500kV transmission networks.

Features

Broad Voltage Compatibility:Tailored to cover the 110kV to 500kV range, these arresters are engineered to match the specific voltage requirements of high-voltage transmission lines. This versatility allows them to provide consistent and reliable protection across various segments of the power grid within this voltage spectrum.

Durable Composite Housing:The composite (silicone rubber) housing offers exceptional performance. It exhibits strong resistance to environmental factors such as UV radiation, extreme temperatures, moisture, and pollution, ensuring long-term stability even in harsh outdoor conditions. Additionally, its lightweight nature simplifies installation and reduces the load on transmission line structures.

High-Performance MOVs:Equipped with high-quality metal oxide varistors, these arresters feature excellent nonlinear resistance characteristics. During overvoltage events, the MOVs quickly conduct large surge currents, effectively limiting voltage spikes. In normal operation, they maintain a high-resistance state, minimizing leakage current and energy loss.

Line-Specific Design:Designed specifically for integration with transmission lines, they have a compact and streamlined structure that fits seamlessly into line configurations. This design ensures minimal impact on line performance while providing optimal protection, making them suitable for both overhead and certain underground transmission line setups.

Superior Surge Handling:Capable of withstanding high impulse currents generated by severe lightning strikes and switching surges. Their robust surge handling capacity ensures that even under extreme electrical disturbances, the arresters can effectively mitigate the impact, safeguarding line insulators, conductors, and other critical components.

Low Maintenance Requirements:The composite housing is resistant to aging and corrosion, reducing the need for frequent maintenance. The MOVs are designed for long-term reliability, with stable performance over extended periods, minimizing downtime and operational costs associated with upkeep.

Compliance with Standards:Adheres to international industry standards such as IEC 60099 - 4 and ANSI/IEEE C62.11, ensuring compatibility with global transmission systems. Compliance with these standards guarantees that the arresters meet strict safety and performance criteria, providing confidence in their operational effectiveness.

Enhanced Grid Reliability:By preventing line tripping and equipment damage caused by overvoltages, these arresters contribute significantly to the overall reliability of the power grid. They help maintain continuous power transmission, reducing the frequency and duration of outages, which is crucial for meeting the demands of industrial, commercial, and residential users.

Model 

Arrester

System

Arrester Continuous Operation

DC 1mA

Switching Impulse

Nominal Impulse

Steep - Front Impulse

2ms Square Wave

Nominal

Rated Voltage

Nominal Voltage

Operating Voltage

Reference Voltage

Voltage Residual (Switching Impulse)

Voltage Residual (Nominal Impulse)

Current Residual Voltage

Current - Withstand Capacity

Creepage Distance

kV

kV

kV

kV

kV

kV

kV

A

mm

(RMS Value)

(RMS Value)

(RMS Value)

Not Less Than

Not Greater Than

Not Greater Than

Not Greater Than

20 Times

 
       

(Peak Value

(Peak Value

(Peak Value

(Peak Value

 

YH10CX1-102/296

102

110

81.6

148

 

296

 

600

5438

YH10CX1-204/592

204

220

159

296

 

592

 

600

10600

YH20CX1-396/1050

396

500

297

561

 

1050

 

1200

23310

YH10CX1-204/592K

204

220

159

296

 

592

 

600

5400

YH10CX1-288/755

220

330

216

408

 

755

 

600

16100

Know your supplier

Online store
On-time delivery rate
Response time
100.0%
≤4h
Company overview
Workplace: 108000m² Total staff: 700+ Highest Annual Export(usD): 150000000
Services
Business Type: Design/Manufacture/Sales
Main Categories: Medium and High Voltage Switchgear/Power and Distribution Transformers/Instrument Transformers and Sensors/Lightning Protection and Electrical Insulation/Substations and E-Houses/Electrical Panel and Controlgear
Send inquiry
+86
Click to upload file
Download
Get the IEE Business Application
Use the IEE-Business app to find equipment, obtain solutions, connect with experts, and participate in industry collaboration anytime, anywhere—fully supporting the development of your power projects and business.
Login
or continue with
New here?
Register