Vacuum Circuit Breakers for Capacitor Bank Switching

Oliver Watts
Oliver Watts
Field: Inspection and testing
China

Reactive Power Compensation and Capacitor Switching in Power Systems

Reactive power compensation is an effective means to increase system operating voltage, reduce network losses, and improve system stability.

Conventional Loads in Power Systems (Impedance Types):

  • Resistance

  • Inductive reactance

  • Capacitive reactance

Inrush Current During Capacitor Energization

In power system operation, capacitors are switched in to improve power factor. At the moment of closing, a large inrush current is generated. This occurs because, during the first energization, the capacitor is uncharged, and the current flowing into it is limited only by the loop impedance. Since the circuit condition is close to a short circuit and the loop impedance is very small, a large transient inrush current flows into the capacitor. The peak inrush current occurs at the instant of closing.

If the capacitor is re-energized shortly after disconnection without sufficient discharge, the resulting inrush current can be up to twice that of the initial energization. This happens when the capacitor still holds residual charge, and re-closing occurs at the moment when the system voltage is equal in magnitude but opposite in polarity to the capacitor’s residual voltage, resulting in a large voltage difference and thus a high inrush current.

Key Issues in Capacitor Switching

  • Re-ignition

  • Re-strike

  • NSDD (Non-Sustained Destructive Discharge)

Re-ignition is permitted during capacitive current switching tests. Circuit breakers are classified into two categories based on their re-strike performance:

  • C1 Class: Verified by specific type tests (6.111.9.2), exhibiting low probability of re-strike during capacitive current switching.

  • C2 Class: Verified by specific type tests (6.111.9.1), exhibiting very low probability of re-strike, suitable for frequent and high-demand capacitor bank switching.

Improving Success Rate of Vacuum Circuit Breakers for Capacitor Switching

1. Enhance Dielectric Strength of Vacuum Interrupters

The vacuum interrupter is the heart of a vacuum circuit breaker and plays a critical role in successful capacitor switching. Manufacturers must optimize the design and materials to achieve:

  • Uniform electric field distribution

  • High resistance to welding

  • Lower current chopping level

Structural and material improvements are essential to ensure reliable interruption.

2. Control Vacuum Interrupter Manufacturing Process

  • Minimize and remove burrs during metal part machining; improve surface finish and cleanliness.

  • Perform ultrasonic cleaning of components before assembly to remove micro-particles.

  • Control humidity and airborne particles in the assembly room.

  • Reduce storage time of contact components and assemble promptly to minimize oxidation and contamination.

VCB..jpg

3. Improve Circuit Breaker Design and Assembly Quality

Ensure mechanical characteristics are within optimal ranges:

  • Conducting rod alignment and vertical installation to avoid stress.

  • Proper operating mechanism output energy.

  • Closing and opening speeds within acceptable limits.

  • Minimize closing bounce and opening rebound.

  • Strict control of component quality and assembly precision.

4. No-Load Operation and Conditioning (Burn-in)

After assembly, perform 300 no-load operations to stabilize mechanical characteristics. Conduct voltage and high-current conditioning on the complete switch to eliminate microscopic protrusions and reduce re-ignition rate during capacitor switching.

Parallel capacitor conditioning can rapidly enhance the dielectric strength of the product.

5. Optimize Opening Speed

After interruption, the contact gap of a vacuum circuit breaker must withstand twice the system voltage (2×Um) for up to 13 ms. The contacts must reach a safe open distance within this time. Therefore, the opening speed must be sufficient — especially for 40.5 kV circuit breakers.

6. Conditioning (Aging) of Vacuum Interrupters

  • Low-effect methods: High-voltage/low-current, low-voltage/high-current, or impulse voltage conditioning have limited effect in reducing re-ignition during capacitor switching.

  • Effective method: High-voltage and high-current single-phase conditioning can significantly improve performance.

  • Synthetic test circuit conditioning is also used to simulate real capacitor switching conditions.

For general applications, standard conditioning is applied. However, for capacitor switching duty, special conditioning is required to enhance electrical performance and initial breaking capability.

Conditioning Parameters:

  • Current Conditioning:
    3 kA to 10 kA, 200 ms half-wave, 12 shots per polarity (positive and negative).

  • Pressure Conditioning:

    • Static pressure (for axial magnetic field contacts): Apply 15–30 kN for 10 seconds.

    • Make-break conditioning (for transverse magnetic field contacts): Perform closing and opening operations on a test rig simulating actual breaker motion.

  • Voltage Conditioning:
    Apply 50 Hz AC voltage far exceeding rated voltage (e.g., 110 kV for a 12 kV interrupter) for 1 minute.

Test Parameters for Capacitor Switching

  • GB/T 1984: Back-to-back capacitor banks, inrush current 20 kA, frequency 4250 Hz.

  • IEC 62271-100 / ANSI Standards:

    • Capacitor bank switching: current 600 A, inrush 15 kA, frequency 2000 Hz

    • Switching current 1000 A, inrush 15 kA, frequency 1270 Hz

    • ANSI allows up to 1600 A for capacitor switching.

After proper conditioning, a 12 kV vacuum circuit breaker can typically pass:

  • 400 A back-to-back capacitor bank switching

  • 630 A single capacitor bank switching

However, for 40.5 kV systems, this is extremely challenging. Common solutions include:

  • Using SF₆ circuit breakers with gentler interruption characteristics

  • Using double-break vacuum circuit breakers, where two interrupters are connected in series. This significantly improves dielectric recovery strength, allowing it to exceed the rate of transient overvoltage rise during capacitor switching, thereby achieving successful arc extinction.

Give a tip and encourage the author!
Recommended
What are the causes of dielectric withstand failure in vacuum circuit breakers?
What are the causes of dielectric withstand failure in vacuum circuit breakers?
Causes of Dielectric Withstand Failure in Vacuum Circuit Breakers: Surface contamination: The product must be thoroughly cleaned before dielectric withstand testing to remove any dirt or contaminants.Dielectric withstand tests for circuit breakers include both power-frequency withstand voltage and lightning impulse withstand voltage. These tests must be performed separately for phase-to-phase and pole-to-pole (across the vacuum interrupter) configurations.Circuit breakers are recommended to be t
Felix Spark
11/04/2025
SST vs Traditional Transformer: Key Advantages
SST vs Traditional Transformer: Key Advantages
Solid-State Transformers (SST): The Future of Intelligent Power ConversionA solid-state transformer (SST), also known as a power electronic transformer (PET), is a static power conversion device that integrates power electronics, high-frequency transformation, and advanced control systems based on electromagnetic induction. It enables the conversion of electrical energy from one set of voltage, current, and frequency characteristics to another—while offering active control, bidirectional power f
Echo
10/27/2025
How SSTs Improve Power Quality & Grid Stability
How SSTs Improve Power Quality & Grid Stability
Solid-State Transformers (SST): Enabling Intelligent, Efficient, and Flexible Power SystemsThe solid-state transformer (SST), also known as an Electronic Power Transformer (EPT), is a static power conversion device that integrates power electronic circuitry with high-frequency energy transfer based on electromagnetic induction. It enables the transformation of electrical energy from one set of voltage, current, and frequency characteristics to another—while offering far greater control and funct
Echo
10/27/2025
What is a solid state transformer? How does it differ from a traditional transformer?
What is a solid state transformer? How does it differ from a traditional transformer?
Solid State Transformer (SST)A Solid State Transformer (SST) is a power conversion device that uses modern power electronics technology and semiconductor devices to achieve voltage transformation and energy transfer.Key Differences from Conventional Transformers Different Operating Principles Conventional Transformer: Based on electromagnetic induction. It changes voltage through electromagnetic coupling between primary and secondary windings via an iron core. This is essentially a direct "mag
Echo
10/25/2025
Related Products
Send inquiry
Download
Get the IEE Business Application
Use the IEE-Business app to find equipment, obtain solutions, connect with experts, and participate in industry collaboration anytime, anywhere—fully supporting the development of your power projects and business.