• Product
  • Suppliers
  • Manufacturers
  • Solutions
  • Free tools
  • Knowledges
  • Experts
  • Communities
Search


How to Calculate Solid-State Transformer Capacity Correctly

Edwiin
Edwiin
Field: Power switch
China

The transformer capacity refers to the apparent power at the transformer's main tap position, and the capacity indicated on the transformer nameplate is the rated capacity. In the operation of power transformers, there are cases of under-loading due to excessive capacity, as well as instances of overloading or overcurrent operation leading to equipment overheating and even burnout. These improper capacity matching practices directly affect the reliability and economy of power supply in electrical systems. Therefore, determining the appropriate transformer capacity is crucial to ensuring reliable and economical power system operation.

The capacity calculation for solid-state transformers must consider the following factors:

  • Input Voltage: The input voltage refers to the voltage value supplied to the transformer. Solid-state transformers typically have a specified input voltage range (e.g., 220V ~ 460V), and an appropriate transformer should be selected based on this range.

  • Output Voltage: The output voltage refers to the voltage value delivered by the transformer. Solid-state transformers also have a defined output voltage range (e.g., 80VAC ~ 480VAC), which must be considered when selecting a suitable transformer.

  • Rated Capacity: The rated capacity indicates the maximum load capacity the transformer can handle, usually expressed in kilovolt-amperes (kVA). The rated capacity is typically determined based on demand; if the load requires a large total current, a transformer with a larger capacity must be selected.

  • Input Power: Input power equals the input voltage multiplied by the input current, generally expressed in kilowatts (kW).

Therefore, considering these factors, the capacity calculation formula for a solid-state transformer can be expressed as:
Capacity (kVA) = Input Voltage (V) × Input Current (A) / 1000.

Note: Solid-state transformers differ from traditional power transformers. A solid-state transformer is a combination of a converter and a transformer, making it highly suitable for static power conversion applications. However, its calculation methods differ from those of conventional transformers.

The capacity calculation methods for single-phase and three-phase transformers are similar. The following explanation uses three-phase transformer capacity calculation as an example. The first step in transformer capacity calculation is to determine the maximum power per phase of the load (for single-phase transformers, this is simply the maximum single-phase load power).

Sum the load power independently for each phase (A, B, and C). For example, if the total load power on phase A is 10 kW, phase B is 9 kW, and phase C is 11 kW, take the maximum value, which is 11 kW.

Note: For single-phase devices, the power per unit is taken as the maximum value listed on the device nameplate. For three-phase equipment, divide the total power by 3 to obtain the per-phase power. For instance:
Total load power on phase C = (300W × 10 computers) + (2kW × 4 air conditioners) = 11 kW.

The second step in transformer capacity calculation is to determine the total three-phase power. Use the maximum single-phase power to calculate the total three-phase power:
Maximum single-phase power × 3 = Total three-phase power.

Using the maximum phase C load power of 11 kW:
11 kW × 3 (phases) = 33 kW. Thus, the total three-phase power is 33 kW.

Currently, over 90% of transformers available on the market have a power factor of only 0.8. Therefore, the total power must be divided by 0.8:
33 kW / 0.8 = 41.25 kW (required transformer apparent power in kW).

According to the Electrical Engineering Design Manual, transformer capacity should be selected based on calculated load. For a single transformer supplying a steady load, the load factor β is generally taken as around 85%. This is expressed as:
β = S / Se
Where:
S — Calculated load capacity (kVA);
Se — Transformer capacity (kVA);
β — Load factor (typically 80% to 90%).

Thus:
41.25 kW (apparent power requirement) / 0.85 = 48.529 kVA (required transformer capacity).
Therefore, a 50 kVA transformer would be suitable.

Give a tip and encourage the author!
Recommended
SST Technology: Full-Scenario Analysis in Power Generation, Transmission, Distribution, and Consumption
SST Technology: Full-Scenario Analysis in Power Generation, Transmission, Distribution, and Consumption
I. Research BackgroundPower System Transformation NeedsChanges in energy structure are placing higher demands on power systems. Traditional power systems are transitioning toward new-generation power systems, with the core differences between them outlined as follows: Dimension Traditional Power System New-Type Power System Technical Foundation Form Mechanical Electromagnetic System Dominated by Synchronous Machines and Power Electronic Equipment Generation-Side Form M
Echo
10/28/2025
SST Transformer Core Loss Calculation and Winding Optimization Guide
SST Transformer Core Loss Calculation and Winding Optimization Guide
SST High-Frequency Isolated Transformer Core Design and Calculation Material Characteristics Impact:Core material exhibits varying loss behavior under different temperatures, frequencies, and flux densities. These characteristics form the foundation of overall core loss and require precise understanding of nonlinear properties. Stray Magnetic Field Interference:High-frequency stray magnetic fields around windings can induce additional core losses. If not properly managed, these parasitic losses
Dyson
10/27/2025
Upgrade Traditional Transformers: Amorphous or Solid-State?
Upgrade Traditional Transformers: Amorphous or Solid-State?
I. Core Innovation: A Dual Revolution in Materials and StructureTwo key innovations:Material Innovation: Amorphous AlloyWhat it is: A metallic material formed by ultra-rapid solidification, featuring a disordered, non-crystalline atomic structure.Key Advantage: Extremely low core loss (no-load loss), which is 60%–80% lower than that of traditional silicon steel transformers.Why it matters: No-load loss occurs continuously, 24/7, throughout a transformer’s lifecycle. For transformers with low loa
Echo
10/27/2025
Design of a Four-Port Solid-State Transformer: Efficient Integration Solution for Microgrids
Design of a Four-Port Solid-State Transformer: Efficient Integration Solution for Microgrids
The use of power electronics in industry is increasing, ranging from small-scale applications such as chargers for batteries and LED drivers, to large-scale applications like photovoltaic (PV) systems and electric vehicles. Typically, a power system consists of three parts: power plants, transmission systems, and distribution systems. Traditionally, low-frequency transformers are used for two purposes: electrical isolation and voltage matching. However, 50-/60-Hz transformers are bulky and heavy
Dyson
10/27/2025
Send inquiry
Download
Get the IEE Business Application
Use the IEE-Business app to find equipment, obtain solutions, connect with experts, and participate in industry collaboration anytime, anywhere—fully supporting the development of your power projects and business.