1. Design of 20 kV Single - phase Distribution Transformer
20 kV distribution systems usually adopt cable lines or mixed cable - overhead line networks, and the neutral point is mostly grounded through a small resistance. When a single - phase grounding occurs, there will be no problem that the phase voltage will rise by more than √3 times as in the case of a single - phase fault in a 10 kV system. Therefore, the single - phase distribution transformer of the 20 kV system can adopt the type of grounding the end of the coil. This can reduce the main insulation of the single - phase distribution transformer, making the volume and cost of the 20 kV single - phase distribution transformer not much different from those of the 10 kV one.
2. Selection of Impulse and Test Voltages
For the basic impulse level (BIL) and insulation test level of the 20 kV single - phase distribution transformer, considerations are as follows:
The American National Standard ANSI C57.12.00—1973 (IEEE Std 462—1972) stipulates that the basic impulse level (BIL) of the high - voltage side (20 kV) is 125 kV; the rated voltage of the high - voltage component is 15.2 kV, and the AC withstand voltage (60 Hz/min) is 40 kV.
The insulation test stipulates that the applied voltage test is not required, but the induced voltage test must be carried out. During the test, after applying a voltage to the outgoing terminal of one winding, the voltage of each high - voltage outgoing terminal to the ground reaches 1 kV plus 3.46 times the rated voltage of the transformer winding. That is, in the induction test (frequency - doubled and voltage - doubled test), the high - voltage is:
2.1 Low-voltage Side (240/120 V)
2.2 According to China’s National Transformer Quality Supervision Test Regulations
High-voltage side:
Basic Impulse Level (BIL): 125 kV (full wave), 140 kV (chopped wave)
AC Induced Withstand Voltage (200 Hz/min): 40 kV
Low-voltage side:
Applied Voltage (50 Hz/min): 4 kV
3. Structure and Features of 20 kV Single-phase Distribution Transformers
Two specifications (50 kVA and 80 kVA) were prototyped, both adopting an outer - iron structure. To reduce main insulation, an end - insulation structure was added. A single bushing is used for lead - out. The end of the high - voltage coil is grounded and connected to the tank. The low - voltage winding is a single - coil structure.
3.1Technical Performance Comparison Between Prototyped 20 kV and 10 kV Single-phase Distribution Transformers
4. 20 kV∥10 kV Single - phase Dual - voltage Distribution Transformer
Upgrading a 10 kV to a 20 kV distribution system involves replacing key equipment like distribution transformers. High - cost replacements and power outages disrupting production make designing a dual - voltage (10 kV/20 kV) single - phase transformer a solution to ease these issues.
4.1 Design
Based on the 10 kV wound - core single - phase distribution transformer, this dual - voltage variant leverages the 20 kV = 2×10 kV relationship, using series - parallel primary coils. With two parallel high - voltage coils, two core columns get high - voltage/low - voltage windings (high - voltage coils parallel). Two low - voltage coils series at the “mid - point” output ±220 V - ground for two users. Let W1 (high - voltage turns) and W2 (low - voltage turns). In parallel, U1/U2 = W1/W2 = 10 kV/220V, and total high - voltage current doubles a single coil’s. In series, high - voltage input current equals coil current.
4.2 Switching Application
Capacity stays consistent for 20 kV or 10 kV high - voltage inputs. At 20 kV input, two high - voltage coils in series mean each bears 10 kV. With high - voltage current I1, capacity S1 = I1×20 = 20I1(kVA). Switched to 10 kV, parallel high - voltage coils give 2I1 input current, so S1 = 2I1×10 = 20I1 (kVA). Thus, S1 = S2).
4.3 Structure
4.4 Advantages of Single - phase Dual - voltage Transformer
5. Conclusion