Carrier Current Protection of Transmission Lines

05/06/2025

Carrier Current Protection Scheme for Transmission Lines

The carrier current protection scheme is predominantly employed for safeguarding long - distance transmission lines. Unlike conventional protection methods that focus on comparing actual current values, this scheme operates by comparing the phase angles of the currents at the two ends of the line. Based on the phase - angle relationship, it can accurately determine whether a fault is occurring within the protected line section (internal fault) or outside of it (external fault). The carrier communication channel, a crucial component of this protection system, consists of four main elements: a transmitter, a receiver, coupling equipment, and a line trap.

The carrier current receiver is tasked with capturing the carrier current transmitted from the transmitter located at the far - end of the line. Once received, it converts this carrier current into a direct - current (DC) voltage. This DC voltage serves as a control signal, which can be harnessed by relays or other electrical circuits to execute specific protective functions. Notably, when no carrier current is being received, the output voltage of the receiver drops to zero, indicating a disruption in the communication link or a potential change in the system's operating state.

The line trap, positioned between the bus - bar and the connection of the coupling capacitor to the transmission line, is a parallel LC (inductor - capacitor) network meticulously tuned to resonate at high frequencies. Its primary function is to confine the carrier current within the protected line section. By doing so, it effectively prevents interference from other adjacent carrier current channels, ensuring the integrity and accuracy of the protection system's operation. Additionally, the line trap plays a vital role in minimizing the loss of the carrier current signal to the neighboring power circuits, thus enhancing the overall reliability of the carrier communication link and the associated protection functions.

image.png

Carrier Current Protection: Components and Methods

The coupling capacitor serves a dual - purpose function in the carrier current protection system. It connects the high - frequency equipment to one of the line conductors, enabling the transmission of carrier signals. At the same time, it isolates the power equipment from the high - voltage of the power line. Under normal operating conditions, the electrical current flows solely through the line conductor. However, when it comes to the high - frequency carrier current, it circulates along the line conductor equipped with high - frequency traps, passing through the trap capacitor and then to the ground.

Methods of Carrier Current Protection

There are several methods of carrier current protection, with the two fundamental forms being Directional Comparison protection and Phase Comparison Protection. These methods are described in detail below:

1. Directional Comparison Protection

In the directional comparison protection scheme, the protection mechanism relies on comparing the direction of power flow during a fault at the two ends of the transmission line. The protective relays operate only when the power at both ends of the line is flowing from the bus towards the line. After comparing the directions, the carrier pilot relay conveys information about how the directional relays at the opposite end respond to a short - circuit event.

Relays located at both ends of the line work together to isolate the fault from the bus. In the case of an internal fault within the protected section, the power flow is in the protective direction. Conversely, for an external fault, the power flow is in the opposite direction. During a fault, a simple signal is transmitted via the carrier pilot from one end of the line to the other. Pilot protection relaying schemes used for transmission line protection can be mainly categorized into two types:

  • Carrier Blocking Protection Scheme: This scheme restricts the operation of the relay. It functions by blocking the fault before it can enter the protected section of the electrical system. The carrier blocking protection scheme is highly regarded for its reliability, as it effectively safeguards system equipment from potential damage.

  • Carrier Permitting Blocking Scheme: In contrast to the blocking scheme, this protective scheme allows the fault current to enter the protected section of the system.

2. Phase Comparison Carrier Protection

The phase comparison carrier protection system focuses on comparing the phase relationship between the current entering the pilot zone and the current leaving the protected zone. Notably, it does not involve comparing the magnitudes of these currents. This protection method primarily provides main or primary protection, and as such, it is essential to supplement it with backup protection. The circuit diagram of the phase comparison carrier protection scheme is illustrated in the figure provided below.

image.png

Operation and Advantages of Carrier Current Protection

The current transformers (CTs) installed on the transmission line supply power to a network. This network converts the output current from the CTs into a single - phase sinusoidal output voltage. This voltage is then fed into both the carrier current transmitter and the comparer. Similarly, the output of the carrier current receiver is also directed to the comparer. The comparer plays a crucial role in controlling the operation of an auxiliary relay, which in turn triggers the tripping of the transmission line circuit breaker when necessary.

Advantages of Carrier Current Protection

Carrier current protection schemes offer several significant benefits, which are outlined below:

  • Simultaneous and Rapid Circuit Breaker Operation: One of the key advantages is the ability to achieve fast and simultaneous tripping of circuit breakers at both ends of the transmission line. This coordinated action ensures that faults are isolated promptly, minimizing the duration of abnormal conditions in the electrical system.

  • Efficient Fault Clearing: The system features a swift fault - clearing process. By quickly interrupting the flow of fault current, it effectively prevents severe impacts on the electrical system, reducing the risk of damage to equipment and maintaining system stability.

  • Integrated Signaling: Carrier current protection eliminates the need for separate signaling wires. Instead, the power lines themselves are utilized to transmit both electrical power and communication signals. This simplifies the overall system design, reduces installation costs, and minimizes the potential for signal interference from external sources.

  • Ultra - Fast Tripping: It enables the circuit breakers at both ends of the line to trip within just one to three cycles. This extremely rapid response time is crucial for protecting modern, high - capacity electrical systems and ensuring the reliable supply of electricity.

  • Compatibility with Modern Equipment: The carrier current protection system is highly compatible with modern, fast - acting circuit breakers. This synergy allows for even more efficient and reliable relaying, enhancing the overall performance and protection capabilities of the electrical grid.

  • Versatile Applications: Historically, power line carrier technology has been widely used for various purposes, including supervisory control, telephone communication, telemetry, and relaying. This versatility makes it a valuable asset in electrical power systems, enabling seamless integration of multiple functions within a single infrastructure.

The Electricity Encyclopedia is dedicated to accelerating the dissemination and application of electricity knowledge and adding impetus to the development and innovation of the electricity industry.

What is the difference between a dielectric and an insulator?
What is the difference between a dielectric and an insulator?
Dielectrics and insulators are distinguished primarily by their applications. One of the main differences is that a dielectric can store electrical energy by becoming polarized in an electric field, whereas an insulator resists the flow of electrons to prevent current conduction. Other key differences between them are outlined in the comparison chart below.Definition of DielectricA dielectric material is a type of insulator that contains few or no free electrons. When subjected to an electric fi
08/30/2025
Cable Fault Detection, Testing, Location and Repair
Cable Fault Detection, Testing, Location and Repair
I. Methods for Cable Testing and Inspection:Insulation Resistance Test: Use an insulation resistance tester to measure the insulation resistance value of the cable. A high insulation resistance value indicates good insulation, while a low value may suggest insulation problems requiring further investigation.Voltage Withstand Test: Apply a high-voltage test using a high-voltage tester to verify whether the cable can withstand high voltage under its rated operating conditions. Under normal circums
08/29/2025
Difference Between Optical fiber and Coaxial Cable
Difference Between Optical fiber and Coaxial Cable
Both optical fiber and coaxial cable are types of guided transmission media. However, several key factors distinguish the two. The most fundamental difference lies in the type of signal they transmit: optical fiber is designed to carry optical (light) signals, whereas coaxial cable is used for transmitting electrical signals.Definition of Optical FiberOptical fibers are flexible, transparent waveguides used to transmit light signals from one end to another with minimal loss. They are primarily m
08/27/2025
Transformer Connection Sections
Transformer Connection Sections
Transformer Connection DesignationsThe transformer connection designation indicates the winding connection method and the phase relationship between the line voltages of the primary and secondary windings. It consists of two parts: letters and a number. The letters on the left denote the connection configurations of the high-voltage and low-voltage windings, while the number on the right is an integer from 0 to 11.This number represents the phase shift of the low-voltage winding's line voltage r
08/15/2025
Inquiry
Download
IEE-Business is dedicated to serving the personnel in the global power industry.
Join IEE-Business, not only can you discover power equipment and power knowledge, but also canhnd like - minded friends!