Kituo cha usalama wa umeme cha kutokana na current ya kushoto (RCCB) ni kituo cha usalama cha umeme kinachohitaji na kutokomea mzunguko wa umeme wakati kukuna leakage current kwa chini. Linahifadhi watu na vifaa kutoka matukio ya mapata, moto, na hatari nyingine zinazotokana na mzunguko wa umeme uliyovunjika, failure ya insulation, au uchaguzi wa kuonekana na sehemu za umeme.
RCCB hufanya kazi kulingana na sheria ya Kirchhoff ya current, ambayo inasema kuwa jumla ya viwango vilivyofika node lazima iwe sawa na jumla ya viwango vilivyondoka node hiyo. Katika mzunguko wa umeme wa kawaida, current unayofika kwenye live wire na neutral wire ni sawa na upande hupoteza. Lakini, ikiwa kukuna tatizo katika mzunguko, kama vile insulation iliyovunjika au mtu anayemfikia live wire, baadhi ya current itapiga njia tofauti kwa chini. Hii hutengeneza imbalance kati ya live na neutral currents, ambayo hutambuliwa na RCCB na kuhimiza ili kutokomea mzunguko wa umeme ndani ya milliseconds.
RCCB unajumuisha transformer toroidal na coils tatu: moja kwa live wire, moja kwa neutral wire, na moja kwa sensing coil. Live na neutral coils huchapa magnetic fluxes sawa na upande hupoteza wakati viwango vinavyofanana. Wakati kukuna imbalance, residual magnetic flux hutengenezwa, ambao hutengeneza voltage kwenye sensing coil. Voltage hii huanza relay ambayo hupeleka contacts za RCCB na kutokomea mzunguko.

RCCB pia una button ya kutest kwa kutumia wanachama kupitia kucheck ufanisi wake kwa kutengeneza leakage current fupi katika mzunguko. Wakati ukimfunga, button ya test huchanganya live wire kwenye upande wa load na supply neutral, kutokea neutral coil ya RCCB. Hii huchanganya viwango na fluxes, ambayo inafanya RCCB ikutokomea. Ikiwa hakutokomea, inamaanisha kuwa RCCB ni mbaya au imefunika vibaya na linahitaji kurudishwa au kutengenezwa upya.
Kuna aina mbalimbali za RCCBs kulingana na uwezo wao wa kutambua leakage currents tofauti:
Type AC: Aina hii hujibu tu pure alternating currents (AC). Inafaa kwa maeneo ya awali ambapo hakuna vifaa vya electronics au variable frequency drives ambavyo hutengeneza direct au pulsating currents.
Type A: Aina hii hujibu AC na pulsating direct currents (DC). Inafaa kwa maeneo ambapo kunavuka vifaa kama computers, TVs, au LED lights ambavyo huchapa rectified au chopped currents.
Type B: Aina hii hujibu AC, pulsating DC, na smooth DC currents. Inafaa kwa maeneo ambapo kunavuka vifaa kama solar inverters, battery chargers, au magari ya umeme ambavyo huchapa smooth DC currents.
Type F: Aina hii hujibu AC, pulsating DC, smooth DC, na high-frequency AC currents hadi 1 kHz. Inafaa kwa maeneo ambapo kunavuka vifaa kama frequency converters, induction cookers, au dimmers ambavyo huchapa high-frequency currents.
Uwezo wa RCCB unatambuliwa pia kwa rated residual operating current (I∆n), ambayo ni leakage current chache ambacho litatambua. Maeneo yake ya asili ya I∆n ni 10 mA, 30 mA, 100 mA, 300 mA, 500 mA, na 1 A. Chache zaidi I∆n, protection level ya juu zaidi dhidi ya electric shocks. Kwa mfano, RCCB 30 mA inaweza hifadhi mtu kutokata cardiac arrest ikiwa atapata shock zaidi ya 0.2 sekunde.
Classification nyingine ya RCCBs ni kulingana na poles zao:
2-pole: Aina hii ina slots mbili kwa kutambua live wire na neutral wire. Inatumika kwa single-phase circuits.
4-pole: Aina hii ina slots nne kwa kutambua three live wires na neutral wire. Inatumika kwa three-phase circuits.
Baadhi ya faida za kutumia RCCBs ni:
Huzuia electric shocks kwa kutambua leakage currents kamili sana kama 10 mA.
Huzuia moto na damage kwa vifaa kwa kutokomea mzunguko wa umeme kwa haraka.
Hawafanikiwa kutengeneza na kutumia kwa buttons rahisi za kutest na reset.
Hawapatani na aina mbalimbali za loads na currents (AC, DC, high-frequency).
Waweza kutumika kama main disconnecting switches upstream ya MCBs zingine.
Baadhi ya dema za kutumia RCCBs ni:
Hawazuia overcurrents au short circuits, ambazo zinaweza sababisha overheating na melting ya wires. Hivyo basi, yanapaswa kutumika series na MCB au fuse ambayo inaweza kutumia rated current ya mzunguko.
Yaweza kutokomea bila sababu zisizo muhimu kutokana na vitu kama lightning, electromagnetic interference, au capacitive coupling. Hii inaweza sababisha inconveniences na loss of productivity.
Yaweza kutokomea kutokana na sababu zisizo muhimu kama corrosion, wear, au mechanical jamming. Hii inaweza kuathiri usalama wa mzunguko na watumiaji.
Yamekuwa mahali zaidi na mabasi kuliko MCBs au fuses.
Kutambua RCCB sahihi kwa mzunguko, facta zifuatazo zinapaswa kutambuliwa:
Aina ya load na current: RCCB lazima iwe sawa na aina ya load (AC, DC, high-frequency) na aina ya current (pure, pulsating, smooth) ambayo itahifadhi. Kwa mfano, type B RCCB lazima itumike kwa solar inverter ambaye huchapa smooth DC current.
Rated residual operating current (I∆n): RCCB lazima iwe chache zaidi I∆n ili kutambua protection ya juu zaidi dhidi ya electric shocks, lakini si chache zaidi kutokoma nuisance tripping. Kwa mfano, RCCB 30 mA inapendekezwa kwa domestic na commercial applications, na RCCB 100 mA ni sawa kwa industrial applications.
Rated current (In): RCCB lazima iwe chache zaidi In ili kutumia normal operating current ya mzunguko, lakini si chache zaidi kutokoma capacity ya MCB au fuse ambayo itakuwa na connection.
Number of poles: RCCB lazima iwe na number of poles sawa na supply voltage. Kwa mfano, 2-pole RCCB lazima itumike kwa 230 V single-phase circuit, na 4-pole RCCB lazima itumike kwa 400 V three-phase circuit.
Kutengeneza RCCB, steps zifuatazo zinapaswa kutumika:
Switch off the main power supply and isolate the circuit that needs to be protected by the RCCB.
Connect the live wire(s) from the supply side to the input terminal(s) of the RCCB marked as L1, L2, and L3.
Connect the neutral wire from the supply side to the input terminal of the RCCB marked as N.
Connect the live wire(s) from the load side to the output terminal(s) of the RCCB marked as L1’, L2’, and L3’.
Connect the neutral wire from the load side to the output terminal of the RCCB marked as N’.
Ensure that all connections are tight and secure and that no wires are loose or exposed.
Switch on the main power supply and test the RCCB by pressing the test button. The RCCB should trip and disconnect the circuit. If it does not, check for any wiring errors or faulty components and fix them before using the circuit.
Reset the RCCB by pressing the reset button. The RCCB should close and reconnect the circuit. If it does not, check for any wiring errors or faulty components and fix them before using the circuit.
RCCB ni kituo cha usalama cha umeme kinachohitaji na kutokomea mzunguko wa umeme wakati kukuna leakage current kwa chini. Linahifadhi watu na vifaa kutoka matukio ya mapata, moto, na hatari nyingine zinazotokana na mzunguko wa umeme uliyovunjika, failure ya insulation, au uchaguzi wa kuonekana na sehemu za umeme.
RCCB hufanya kazi kulingana na sheria ya Kirchhoff ya current, ambayo inasema kuwa jumla ya viwango vilivyofika node lazima iwe sawa na jumla ya viwango vilivyondoka node hiyo. Katika mzunguko wa umeme wa kawaida, current unayofika kwenye live na neutral wires ni sawa na upande hupoteza. Lakini, ikiwa kukuna tatizo katika mzunguko, baadhi ya current itapiga njia tofauti kwa chini. Hii hutengeneza imbalance kati ya live na neutral currents, ambayo hutambuliwa na RCCB na kuhimiza ili kutokomea mzunguko wa umeme ndani ya milliseconds.
RCCB unajumuisha transformer toroidal na coils tatu: moja kwa live wire, moja kwa neutral wire, na moja kwa sensing coil. Live na neutral coils huchapa magnetic fluxes sawa na upande hupoteza wakati viwango vinavyofanana. Wakati kukuna imbalance, residual magnetic flux hutengenezwa, ambao hutengeneza voltage kwenye sensing coil. Voltage hii huanza relay ambayo hupeleka contacts za RCCB na kutokomea mzunguko.
RCCB pia una button ya kutest kwa kutumia wanachama kupitia kucheck ufanisi wake kwa kutengeneza leakage current fupi katika mzunguko. Wakati ukimfunga, button ya test huchanganya live wire kwenye upande wa load na supply neutral, kutokea neutral coil ya RCCB. Hii huchanganya viwango na fluxes, ambayo inafanya RCCB ikutokomea. Ikiwa hakutokomea, inamaanisha kuwa RCCB ni mbaya au imefunika vibaya na linahitaji kurudishwa au kutengenezwa upya.
Kuna aina mbalimbali za RCCBs kulingana na uwezo wao wa kutambua leakage currents tofauti: type AC, type A, type B, na type F. Uwezo wa RCCB unatambuliwa pia kwa rated residual operating current (I∆n), ambayo ni leakage current chache ambacho litatambua. Maeneo yake ya asili ya I∆n ni 10 mA, 30 mA, 100 mA, 300 mA, 500 mA, na 1 A. Chache zaidi I∆n, protection level ya juu zaidi dhidi ya electric shocks.
Classification nyingine ya RCCBs ni kulingana na poles zao: 2-pole na 4-pole. Number of poles lazima iwe sawa na supply voltage ya mzunguko.
Baadhi ya faida za kutumia RCCBs ni: huzuia electric shocks, huzuia moto na damage kwa vifaa, hawafanikiwa kutengeneza na kutumia, hawapatani na aina mbalimbali za loads na currents, na hawezi kutumika kama main disconnecting switches. Baadhi ya dema za kutumia RCCBs ni: hawazuia overcurrents au short-circuits, yaweza kutokomea bila sababu zisizo muhimu kutokana na external factors, yaweza kutokomea kutokana na internal factors, na yamekuwa mahali zaidi na mabasi kuliko MCBs au fuses.
Kutambua na kutengeneza RCCB, facta zifuatazo zinapaswa kutambuliwa: aina ya load na current, rated residual operating current (I∆n), rated current (In), na number of poles. RCCB lazima iwe connected series na MCB au fuse ambayo inaweza kutumia rated current ya mzunguko. RCCB lazima iwe tested na reset mara kwa mara ili kutambua ufanisi wake na usalama.