Types and Common Fault Analysis of High-Voltage Switchgear

Leon
Leon
Field: Fault Diagnosis
China

Types and Common Fault Analysis of High-Voltage Switchgear

High-voltage switchgear is a critical electrical device in power systems. Deterioration in switchgear operation is one of the main causes of power system failures. What are the common faults in high-voltage switchgear?

(1) Outdoor and Indoor Types

Based on installation environment, high-voltage switchgear can be classified as outdoor or indoor types. Equipment rated at 10 kV and below is mostly installed indoors. According to primary circuit configurations, they can be further categorized as incoming/outgoing line switchgear, tie-oil switchgear, bus section switchgear, etc.

Indoor 10 kV incoming/outgoing switchgear typically houses minimum-oil or vacuum circuit breakers. These breakers are usually equipped with spring or electromagnetic operating mechanisms, though some use manual or permanent-magnet operating mechanisms. Different switchgear designs vary significantly in structure, which directly affects the selection and installation of sensors.

(2) Fixed and Withdrawable Types

Based on usage and design, high-voltage switchgear can be divided into fixed and withdrawable (draw-out) types. Historically, power plants preferred withdrawable switchgear for station service systems, while fixed types were more common in utility power supply systems.

With advances in technology and new product development, traditional practices are evolving. For example, the metal-enclosed armored withdrawable switchgear evolved from fixed-type switchgear. This type features a fully enclosed design with functionally separated compartments. It offers enhanced operational safety, improved anti-misoperation interlocks, and easier maintenance, greatly increasing operational reliability.

(3) Development of High-Voltage Switchgear

In recent years, with the advancement and widespread use of compact vacuum circuit breakers, the mid-mounted switchgear (also known as "switchgear with withdrawable unit mounted in the middle compartment") has rapidly developed as a new type of metal-enclosed armored withdrawable switchgear.

Mid-mounted switchgear offers several advantages, the most significant being miniaturization of the withdrawable unit and mechanized manufacturing processes, which allow for more precise alignment between the trolley and guide rails. Some manufacturers even ship the circuit breaker trolley and cabinet separately, enabling easy on-site assembly and commissioning with high reliability.

Due to excellent interchangeability, these switchgear units are less affected by floor leveling at the installation site. With high operational reliability and convenient maintenance, mid-mounted metal-clad withdrawable switchgear is increasingly adopted in power supply systems.

II. Common Fault Analysis of High-Voltage Switchgear

Faults in high-voltage switchgear primarily arise from issues in insulation, current conduction, and mechanical systems.

(1) Failure to Operate or Maloperation

This is the most common type of fault in high-voltage switchgear and can be attributed to two main causes:

  • Mechanical faults in the operating mechanism and transmission system, such as mechanism jamming, component deformation, displacement, or damage; loose or stuck closing/tripping plungers; broken or loose pins; and latch failure.

  • Electrical faults in control and auxiliary circuits, including poor contact in secondary wiring, loose terminals, incorrect wiring, burnt-out closing/tripping coils (due to mechanism jamming or faulty selector switches), malfunctioning auxiliary switches, and failures in the control power supply, closing contactors, or limit switches.

(2) Switching and Closing Faults

These faults originate from the circuit breaker itself.

  • In minimum-oil circuit breakers, common issues include oil spraying during short circuits, arc chamber damage, insufficient breaking capacity, and explosions during closing.

  • In vacuum circuit breakers, typical faults include leakage in the arc chamber or bellows, reduced vacuum level, restriking when switching capacitor banks, and ceramic tube cracking.

(3) Insulation Failures

Insulation performance must properly balance the various voltages acting on the insulation (including normal operating voltage and transient overvoltages), protective measures (such as surge arresters), and the dielectric strength of the insulation material. The goal is to achieve a safe, economical, and cost-effective design.

Common insulation faults include:

  • External insulation flashover to ground

  • Internal insulation flashover to ground

  • Phase-to-phase flashover

  • Lightning overvoltage-induced flashover

  • Flashover, pollution flashover, puncture, or explosion of porcelain or capacitor bushings

  • Flashover of support rods

  • Flashover, puncture, or explosion of current transformers (CTs)

  • Porcelain insulator fracture

(4) Current-Carrying Faults

At voltage levels of 7.2–12 kV, current-carrying faults are mainly caused by poor contact at the isolation disconnects (joints), leading to overheating and melting of contacts.

(5) External Forces and Other Faults

These include faults caused by foreign object impacts, natural disasters, animal-induced short circuits, and other unpredictable external or accidental factors.

Give a tip and encourage the author!
Recommended
MVDC: Future of Efficient, Sustainable Power Grids
MVDC: Future of Efficient, Sustainable Power Grids
The Global Energy Landscape Is Undergoing a Fundamental Transformation toward a "fully electrified society," characterized by widespread carbon-neutral energy and the electrification of industry, transportation, and residential loads.In today’s context of high copper prices, critical mineral conflicts, and congested AC power grids, Medium-Voltage Direct Current (MVDC) systems can overcome many limitations of traditional AC networks. MVDC significantly enhances transmission capacity and efficienc
Edwiin
10/21/2025
Grounding Causes of Cable Lines and the Principles of Incident Handling
Grounding Causes of Cable Lines and the Principles of Incident Handling
Our 220 kV substation is located far from the urban center in a remote area, surrounded primarily by industrial zones such as Lanshan, Hebin, and Tasha Industrial Parks. Major high-load consumers in these zones—including silicon carbide, ferroalloy, and calcium carbide plants—account for approximately 83.87% of our bureau’s total load. The substation operates at voltage levels of 220 kV, 110 kV, and 35 kV.The 35 kV low-voltage side mainly supplies feeders to ferroalloy and silicon carbide plants
Felix Spark
10/21/2025
Overhead Power Lines & Towers: Types, Design & Safety
Overhead Power Lines & Towers: Types, Design & Safety
Besides ultra-high voltage AC substations, what we encounter more frequently are power transmission and distribution lines. Tall towers carry conductors that leap across mountains and seas, stretching into the distance before reaching cities and villages. This is also an interesting topic—today, let's explore transmission lines and their supporting towers.Power Transmission and DistributionFirst, let’s understand how electricity is delivered. The electric power industry primarily consists of fou
Encyclopedia
10/21/2025
Automatic Reclosing Modes: Single, Three-Phase & Composite
Automatic Reclosing Modes: Single, Three-Phase & Composite
General Overview of Automatic Reclosing ModesTypically, automatic reclosing devices are categorized into four modes: single-phase reclosing, three-phase reclosing, composite reclosing, and disabled reclosing. The appropriate mode can be selected based on load requirements and system conditions.1. Single-Phase ReclosingMost 110kV and higher transmission lines employ three-phase single-shot reclosing. According to operational experience, over 70% of short-circuit faults in high-voltage overhead li
Edwiin
10/21/2025
Related Products
Send inquiry
Download
Get the IEE Business Application
Use the IEE-Business app to find equipment, obtain solutions, connect with experts, and participate in industry collaboration anytime, anywhere—fully supporting the development of your power projects and business.